– Translation of the original user manual - 2.0 | 2019
42
6.5
FIXED SAFETY CONTACT STRIPS
The fixed safety contact strips (8.2 kΩ) for the protection of the gate can be
connected directly to the plug-in terminals at the bottom right on the input
terminal block.
Terminals nos. 9 and 10 are labelled “SKL open” on the printed circuit board. The
strip can be connected in the OPEN direction of the gate at these terminals.
Terminals nos. 11 and 12, labelled “SKL close”, are provided for the connection of
the safety contact strip in the CLOSE direction.
Fig.
no.
Terminal
no.
Designati
on
Input function
10.3
9, 10
SKL open Fixed safety contact strips (OPEN direction)
10.4
11, 12
SKL close Fixed safety contact strip (CLOSE direction)
The contact strip signals are evaluated in the control system software.
Indus system with accompanying safety contact strips
6.5.1
The evaluation of the ISK inductive cable transmission system from manufacturer
ASO GmbH for the gate-accompanying safety contact strips (8.2 kΩ) is already
integrated into the control system, if the INDUS onboard 70-757 board (5.2 FULL
VIEW OF THE CONTROL SYSTEM no. 12) is plugged in. The SPK55 fixed coil core
can be connected directly to the two right-hand terminals, numbered 11 and 12,
on the upper input terminal block with the designation “ISK”. The signals from
the accompanying safety contact strips will then be evaluated in terms of safety in
the control system.
Fig.
no.
Terminal
no.
Designati
on
Input function
11.4
11, 12
ISK
INDUS onboard 70-757 input
(fixed coil core)
The evaluation of a connected ISK system is activated by default. To
retrospectively activate the ISK system (and deactivate JCM), the menu item
“Activate ISK” must be selected in the menu “Settings”; “Safety”.
Summary of Contents for HMD Basic
Page 2: ...EN Translation of the original user manual 2 0 2019 2...
Page 75: ...EN Translation of the original user manual 2 0 2019 75 Appendix A Declarations Dop DoC...
Page 76: ...EN Translation of the original user manual 2 0 2019 76...
Page 77: ...EN Translation of the original user manual 2 0 2019 77 Appendix B ELECTRIC DIAGRAM HMD24...
Page 78: ...EN Translation of the original user manual 2 0 2019 78...
Page 79: ...EN Translation of the original user manual 2 0 2019 79...
Page 80: ...EN Translation of the original user manual 2 0 2019 80...
Page 81: ...EN Translation of the original user manual 2 0 2019 81...
Page 82: ...EN Translation of the original user manual 2 0 2019 82...
Page 83: ...EN Translation of the original user manual 2 0 2019 83...
Page 84: ...EN Translation of the original user manual 2 0 2019 84...
Page 85: ...EN Translation of the original user manual 2 0 2019 85...
Page 86: ...EN Translation of the original user manual 2 0 2019 86...
Page 87: ...EN Translation of the original user manual 2 0 2019 87...
Page 88: ...Local supplier stamp Lokal terf rs ljare st mpel...