CSG

70

GAS SUPPLY-CSG

RIGHT

MINIMUM PULL of equipment away from 
wall permissible for accessibility to
Quick Disconnect Device

WRONG

AVOID SHARP BENDS AND KINKS when
pulling equipment away from wall. (Maximum
pull will kink ends, even if installed properly,
and reduce Connector life.)

Couplings and hose should be installed in
the same plane as shown at left. DO NOT
OFFSET COUPLINGS – this causes torsional
twisting and undue strain causing premature
failure.

This is the correct way to install metal hose
for vertical travers. Note the single, natural
loop.

Allowing a sharp bend, as shown at right,
strains and twists the metal hose to a point of
early failure at the coupling.

Maintain the minimum or larger bending
diameter between the couplings for longest
life.

Closing in the diameter at the couplings, as
shown at right, creates double bends causing
work fatigue failure of the fittings. 

In all installations where “self-draining” is not
necessary, connect metal hose in a vertical
loop.

DO NOT CONNECT METAL HOSE
HORIZONTALLY...unless “self-draining”
is necessary then use support on lower plane
as shown at left.

CABLE RESTRAINT

Please refer to the illustration below when
installing cable restraint on all moveable units.

I-bolt is to be secured to the building using
acceptable building construction practices.

DRYWALL CONSTRUCTION

Secure I-bolt to a building stud.
DO NOT attach to drywall only. Also,
locate the I-bolt at the same height as
the gas service. Preferred installation is
approximately six inches to either side
of service. Cable restraint must be at
least six inches shorter than flexible
gas line.

Utilize elbows when necessary to avoid
sharp kinks or excessive bending. For
ease of movement, install with a “lazy”
loop. Gas appliance must be discon-
nected 

prior to maximum

movement.

(Minimum movement is permissible for
hose disconnection.)

Summary of Contents for B-1020

Page 1: ...e Back Side CSB CSM CSL 6 10 1020 6 150mm 2 50mm 2 50mm NOTE 14 350mm is recommended at the left side of the unit for service purposes Place the combi steamer on an original Henny Penny stand or on a...

Page 2: ...shing oven racks into unit The oven rack must be positioned vertically in the unit not tilting For minor unevenness in floor the oven rack can be leveled using the optional leveling device If necessar...

Page 3: ...70 1990 NOTE All connections must comply with the oven data plate A separate fused disconnect switch or circuit breaker not furnished MUST be installed in the electrical supply line FOR EACH OVEN NOTE...

Page 4: ...or local plumbing codes The unit has an integrated vented drain system which acts as a reverse flow check valve so it may be connected directly with a P trap to the drain system Installation Electric...

Page 5: ...ill provide easy loading and unloading without interfering with the final assembly of food orders Installation Gas Units Do Not puncture the cabinet with any objects such as drills or screws as electr...

Page 6: ...version The stacked version kit comprises two different draft hoods one with a single outlet and the second with a double outlet A flue riser completes the stacked version flue assembly Fix the singl...

Page 7: ...n integrated vented drain system which acts as a reverse flow check valve so it may be connected directly with a P trap to the drain system Should the water pressure exceed 87 psi a pressure regulator...

Page 8: ...all electrical connections are to be made in accordance with the CAN CGA B149 1 or 2 installation code and or local code and the Canadian electrical code Part 1 CSA C22 1 Before connecting incoming p...

Page 9: ...reates double bends causing work fatigue failure of the fittings In all installations where self draining is not necessary connect metal hose in a vertical loop DO NOT CONNECT METAL HOSE HORIZONTALLY...

Page 10: ...nces in the kitchen are on high flame The mini mum and maximum incoming line flow pressures should be as follows Natural 7 11 water column Propane 11 water column Installation Gas Units continued Neve...

Page 11: ...be taken by installing a gas pressure gauge on the front of the unit s main gas valves test port This should be done with all gas appliances in operation on the same gas supply line Should the manifol...

Reviews: