17
Settings (available through Z-Wave network only)
All configuration parameters are accessed through Z-Wave COMMAND_CLASS_CONFIGURATION
Time Mode Schedule
Parameters 41-44
–
Schedule Time
Use these Parameters to manual set the Morning, Day, Evening and Night times for the Temperature Schedule.
The value of these Parameters has format HHMM, e.g. for 08:00 use value 0800 (time without a colon). From 00:00 to
23:59 can be selected.
The factory default value for Morning (Parameter 41) is 0600.
The factory default value for Day (Parameter 42) is 0900.
The factory default value for Evening (Parameter 43) is 1800.
The factory default value for Night (Parameter 44) is 2300.
Parameters 45-72
–
Schedule Temperature
Use these Parameters to manual set the temperature for each day Schedule (see the Parameters table on the page 19
of this manual). The value of this Parameter should be x10, e.g. for 22.5°C set value 225. From 1°C (value 10) to 37°C
(value 370) can be selected.
The factory default Morning temperature for all 7 days (Parameters 45, 49, 53, 57, 61, 65, 69) is 24.0°C (value 240).
The factory default Day temperature for all 7 days (Parameters 46, 50, 54, 58, 62, 66, 70) is 20.0°C (value 200).
The factory default Evening temperature for all 7 days (Parameters 47, 51, 55, 59, 63, 67, 71) is 23.0°C (value 230).
The factory default Nigh temperature for all 7 days (Parameters 48, 52, 56, 60, 64, 68, 72) is 18.0°C (value 180).
Sensors Report Interval
Parameter 141
–
Energy Consumption Meter Consecutive Report Interval
When the device is connected to the Z-Wave gateway (controller), it periodically sends to the gateway reports from its
energy consumption sensor even if there is no change in the value. This Parameter defines the interval between
consecutive reports of real time and cumulative energy consumption data to the gateway. The value can be adjusted
from 1 min to 120 min. The factory default value is 10 min.
Note:
If the consumption changes, the device will send the report to the gateway regardless of this Parameter value
(the report will be sent according to value in Parameter 142).
Note:
In order not to increase traffic on your network, it is not recommended to reduce the value of this Parameter. We
recommend reducing the value of this Parameter only in case of poor connection, when reports from the device does
not always reach the gateway.
Parameter 142
–
Energy Consumption Report Threshold
This Parameter determines the change in the load power resulting in the consumption report being sent to the gateway.
From 1 to 50 can be selected. Use the value 0 if there is a need to stop sending the reports. The factory default value is
25.
Note:
When the thermostat is turning ON, the consumption data will be sent to the gateway once, even if the value of this
Parameter is 0.
Parameter 143
–
Sensors Consecutive Report Interval
When the device is connected to the Z-Wave gateway (controller), it periodically sends to the gateway reports from its
room & floor temperature, humidity and light sensors even if there are not changes in the values. This Parameter
defines the interval between consecutive reports. The value can be adjusted from 1 min to 120 min. The factory default
value is 10 min.
Note:
If the sensor readings change, the device will send the report to the gateway regardless of this Parameter value
(the report will be sent according to values in Parameters 144, 145 and 146).
Note:
In order not to increase traffic on your network, it is not recommended to reduce the value of this Parameter. We
recommend reducing the value of this Parameter only in case of poor connection, when reports from the device does
not always reach the gateway.
Parameter 144
–
Air & Floor Temperature Sensors Report Threshold
This Parameter determines the change in temperature level (in °C) resulting in temperature sensors report being sent to
the gateway. The value of this Parameter should be x10, e.g. for 0.4°C use value 4. From 0.1°C (value 1) to 10°C (value
100) can be selected. Use the value 0 if there is a need to stop sending the reports. The factory default value is 2 (0.2°C).
Note:
When the thermostat is turning ON, the sensor data will be sent to the gateway once, even if the value of this
Parameter is 0.
Note:
It is recommended not to decrease the value of this Parameter, in order not to increase the load on your Z-Wave
network traffic.