16
Parameter 15
(“FtH”) –
Floor Temperature Maximum (Highest level)
This Parameter is the floor temperature high limit
–
reading the external NTC temperature sensor. It only comes into effect
if AF or tF are selected as the source sensor in Parameter 11. The Parameter value can be selected from 2.0°C to 37.0°C.
Through the Z-Wave network the value of this Parameter should be x10, e.g. for 22.5°C set the value 225. The factory
default value is 32°C (320 through Z-Wave network).
Note:
The
FtH value cannot be lower than (FtL + 1)°C.
Parameter 16 (“FtC”) –
Floor Temperature Calibration
This Parameter defines the offset value for floor temperature. If the external floor temperature sensor is not calibrated
properly, then manual calibration can be made by adjusting the values up to ±10.0°C. This value will be added or
subtracted from the floor temperature sensor reading. Through the Z-Wave network the value of this Parameter should
be x10, e.g. for 1.5°C set the value 15. The factory default value is 0.
Parameter 17
(“AtC”) –
Air Temperature Calibration
This Parameter defines the offset value for room air temperature. If the internal air temperature sensor is not correctly
calibrated, then manual calibration can be made by adjusting the values up to ±10°C. This value will be added or
subtracted from the internal air temperature sensor reading. Through the Z-Wave network the value of this Parameter
should be x10, e.g. for 1.5°C set the value 15. The factory default value is 0.
Parameter 18
(“HyS”) –
Temperature Hysteresis (HyS)
This Parameter defines the hysteresis value for temperature control. The HE-HT01 will stabilize the temperature with
selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS is set for 0.5°C the HE-HT01 will
change the state to IDLE if the temperature reaches 25.0°C, but it will change the state to HEATING if the temperature
becomes lower than 24.5°C. The hysteresis can be changed from 0.2°C to 10.0°C range. Through the Z-Wave network
the value of this Parameter should be x10, e.g. for 1.2°C set the value 12. The factory default value is 0.5°C (5 through
Z-Wave network).
Time Configurations
Parameter 19
(“tCr”) –
Time Correction by Main Controller
If this Parameter value = 1 and the HE-HT01 is connected to a Z-Wave gateway, the HE-HT01 time and day will be
periodically polled and corrected from the gateway. To switch off auto-correction set the Parameter value to 0. The factory
default value is 1.
Parameter 20
(“tFo”) –
Time Format
Either 24 hour or 12-hour time formats may be selected. Parameter value 0 = 24 hour format, Parameter value 1 = 12
hour (AM/PM) format. The factory default value is 0.
Parameter 21
(“dAy”) –
Day of the Week Manual Adjustment
This Parameter allows manually adjustment of the day of the week in case the HE-HT01 is not connected to any Z-Wave
gateway or auto-correction is disabled (Parameter 19 value is 0). 1 = Monday, 2 = Tuesday, 3 = Wednesday, 4 = Thursday,
5 = Friday, 6 = Saturday, 7 = Sunday. The factory default value is 1.
Parameter 22
(“
tIA
”) –
Time Manual Adjustment
This Parameter allows manual adjustment of Time. To select between hours and minutes press the
Clock “ ” button
. To
raise or lower the time, press the
“
+
”
and
“–
buttons.
Parameter 23
(“tOn”) –
Time Regulation ON Time
This Parameter defines floor HEATING time in minutes when Time Regulator (
“t”
,
“tA”
or
“t
F
”
) is selected as the source
sensor in Parameter 11. Time values can be changed in the range from 10 to 240 minutes. The factory default value is
30 minutes.
Parameter 24
(“tOF”) –
Time Regulation OFF Time
This Parameter defines floor IDLE time in minutes when Time Regulator (
(“t”, “tA” or “tF”
) is selected as the source sensor
in Parameter 11. Time can be changed in the range from 10 to 240 minutes. Factory default value is 30 minutes.
Parameter 25
(“dr1”) –
Dry Time
This Parameter specifies how long in minutes the Heating Thermostat will be in HEATING mode when the DRY mode is
selected. After this time the HE-HT01 will enter the mode specified in Parameter 26. The time range can be selected from
5 to 90 minutes. Factory default time is 30 minutes.
Parameter 26
(“dr2”) –
Mode To Switch After Dry Mode Operation Completion
This Parameter indicates the mode that will be set when Dry Time (Parameter 25) passed: 1 = COM, 2 = TIME, 4 = ECO,
5 = VAC, 6 = MAN mode with IDLE state. The factory default value is 1.