4215-109 G
10/30/09
Electrical installation must be made by a licensed electrician in
accordance with the National Electrical Code and local regulations.
Remove the screws from the CB PK box to access the electrical
connections. Secure CB PK box to the wall in the sauna room according
to Diagram 1. (4 screws provided in the box) Route the wires through
the holes provided on the bottom of the control box and connect the
wires to the terminal block. To determine the correct wire size, refer to
Diagram 2. Use copper supply wire only, suitable for minimum 90
degrees C. The heater must be grounded! See Diagram 6 for proper
connections.
Refer to the Installation and Operation Manual for all electrical
questions about the traditional sauna heater.
Connect low voltage cable from the SaunaLogic IS control to JT1 of the
circuit board in the CB PK Box. Connect sensor cable to JT2 of the
circuit board in the CB PK Box. Connect the color therapy light cable to
Color Lamp of the circuit board in the CB PK Box. Connect the cable
from Interior lights to the connector labels Interior Lights. Connect the
cable from exterior lights to the connector labels Exterior Lights.
Connect the high limit sensor cable to JT13 of the circuit board in the
CB PK Box. (Traditional sauna heater is optional)
IR Emitter Installation
Connnect IR emitters to the preinstalled wires in the walls. Each IR
emitter is provided with an electical junction box. All IR emitters
should be grounded.
Refer to the wiring diagrams for electical connections. Completed
connections and install cover on electrical box. Push excess wires in the
wall and secure the IR emitters to the wall with the 3" screws provided.
SECTION 3: ELECTRICAL INSTALLATION SUMMARY
Page 6
Feed the 17 ft "low voltage" sensor wire from the sensor location to the CB PK box location. Sensor wire must be
routed completely separate (as per low voltage electrical wiring codes) from any wiring carrying over 50 volts. It
may be necessary to drill holes to string the wire through the studs or ceiling joists.
Using a flat tip screwdriver, unsnap sensor cover from sensor. Mount sensor to a finished wall directly above
heater and two (2) inches down from ceiling using two (2) screws (provided) as shown in Diagrams 1, 3 & 5.
Connect wires to JT2 on the circuit board inside the CB PK box.
SECTION 4: TEMPERATURE SENSOR