background image

4215-109 G                                                                                                                                                                                                                                                            

10/30/09                                                                                                                                                                                                                                                    

                                                                                                                                                                                                                                                          

WARNING

     SECTION 10: WARNING PLACARDS

     SECTION 11: ROOM CONSTRUCTION

For safety purpose sauna 

door must open out and not 

lock.

Never use a wood stain, seal 
or preservative on the inside 

of your sauna room.

Light fixtures get very hot 

during operation.  Locate 

light fixture where it will 

not be a burn hazard.

Two metal placards are included in the Installation Instruction 
Envelope packaged with every Sauna Heater. The CAUTION placard 
must be attached to the interior wall of the sauna room directly above 
the heater where it is visible to the bather. The WARNING placard 
must be attached to the door of the sauna room.

The "CAUTION" and 

"WARNING" placards 

must be mounted in 

accordance with Section 10.

For safety and reliability, the following rules must be addressed.
- No permanent locking or latch system is to be used on the sauna 
door.  
- Acceptable door fittings are:  magnetic catches, friction catches, 
spring or gravity loaded closures.  
- The door must always open outwards.
- No shower may be installed in a sauna room.
- No electrical receptacle shall be installed inside the sauna room.
- The enclosed WARNING:  Reduce the risk of overheating … 
warning plate must be mounted on or alongside the door outside the 
sauna room at about eye level.
- The enclosed CAUTION:  Reduce the risk of fire … caution plate 
must be mounted on the interior wall above the heater.
- If an intercom speaker is installed, it should be  as close to the floor 
as possible.
- Fire sprinkler systems installed inside any sauna room should be
properly rated for sauna room temperatures.
- Always mount the heaters according to these installation instructions
- Typical wall design, 2x4 studs, insulation, foil vapor barrier, and 
tongue and groove boards. Refer to Diagrams 3 and 8.

     SECTION 12: VENTILATION

VENTILATION  In a private sauna, the air should be changed 
about 6 times an hour.  This can be achieved by making a vent 
opening (fresh air inlet) in the sauna wall directly below the heater.  
The air outlet must be lower than the upper benches, as far as 
possible from the heater and about two feet higher than the fresh air 
inlet vent, See Diagram 9. It is recommended that ventilation 
openings meet the requirements of UL Specification 875.  The 
minimum opening should be determined using one of the following 
formulas:
             For     R

<

31,     V

9.3,      For     R

31,     V

0.3R

where    R = the floor area of the room in square feet and
             V = the minimum vent size in square inches

Page 11

Summary of Contents for IS 200

Page 1: ...gets hot during operation and should not be touched or burns may result Minors should be adequately supervised whenever near a hot or warming sauna Infrared Sauna Series Models IS 200 IS 300 IS 400 I...

Page 2: ...materials to be sure you have the proper minimum distances DIAGRAM 2 Page 2 OBSERVING MINIMUM DISTANCES IS REQUIRED TO REDUCE FIRE HAZARD Sauna Heater Optional Equipment Sauna Heater Denotes an option...

Page 3: ...4215 109 G 10 30 09 Typical IS Installation with a tradiontal sauna heater Refer to Diagram 1 for minimum spacing requirements...

Page 4: ...ize information Step 3 Will the wires be installed in the walls or surface mounted If preinstalled pull 12 2 AWG wire w ground from the CB PK Box to closest IR emitter Leave 18 of wire sticking out th...

Page 5: ...allation Optional Equipment SaunaLogic IS is capable of operating ONLY a lighting package purchased with the system The lighting package consists of 3 color therapy lights 2 interior lights 3 exterior...

Page 6: ...Interior Lights Connect the cable from exterior lights to the connector labels Exterior Lights Connect the high limit sensor cable to JT13 of the circuit board in the CB PK Box Traditional sauna heat...

Page 7: ...4215 109 G 10 30 09 Page 7 WIRING DIAGRAM CONTROL AND HEATER MODELS...

Page 8: ...4215 109 G 10 30 09 Page 8 WIRING DIAGRAM CONTROL AND HEATER MODELS...

Page 9: ...stem to heat slower which may result in less effective performance Press the Traditional Sauna button on the SaunaLogic IS and the default settings for the temperature ispreset to 176 F the bath time...

Page 10: ...igh limit continually shuts off the heater contact a service representative at 1 888 780 4427 The sauna like a bathroom should be kept clean and odor free Towels or mats should always be used on bench...

Page 11: ...ed WARNING Reduce the risk of overheating warning plate must be mounted on or alongside the door outside the sauna room at about eye level The enclosed CAUTION Reduce the risk of fire caution plate mu...

Page 12: ...rmation There is one high limit for each system Need to determine which system is operating to know which high limit is alarming System won t start to heat ensure the system is not in the delay mode I...

Reviews: