  7

PTM MODULE 

 

STRAIN GAGE SENSOR INPUT 

 

The strain gage sensor wires are connected at the green 5-pole  
Weidmuller connector at the bottom of the module.  Connections include 
 “+ Gage”, “+ Signal”, and “Shield”.  For ease of wiring at the  
connector, it can be removed from the module while making the 5 connections at the  
screw terminals.  
 

INITIAL SET-UP AND CALIBRATION 

 

Zero Balance 

 
After the proper wiring connections are made, the module should be set up by connecting a 
good quality voltmeter to the 0-10 VDC analog voltage “Track” output terminals (“Track” and 
“Acom”).  There should be no load on the sensor, and the external timing input signal should 
be off (between cycles).  Set the small 3-position calibration toggle switch at the top of the 
module to the center “Off” position.  Adjust the “Gain” pot CCW until it reaches the stop, a 
click will be felt. Adjust the small “Bal” (Balance) pot below the switch so that the voltmeter 
reads 0.00 volts.  This electronically “zero balances” the sensor to the module circuit. 
 

Calibration: For Strain gage installations 

 
The machine to which the sensors are mounted should be “field calibrated” using portable 
calibration load cells and instrumentation to verify the actual developed tonnages. 
 

1.  With the small 3-position calibration toggle switch at the top of the module to the 

center “Off” position, cycle the press and record developed tonnage. 

2.  Adjust the gain pot CW, and cycle the press again. 
3.  Compare the “Peak Output” scaled value on the display meter to the display of the 

calibration equipment, and continue to adjust the gain pot and cycle the press. 

 
Note: If the value remains 0 (zero), continue to increase the gain by rotating Clock-wise, 

until the unit displays the developed value. 

 
If there is not enough gain with the toggle switch at the tower LOW GAIN 140K position, 
move it to the upper HIGH GAIN 1 Megohm position, then repeat the zero balance. The 
corresponding voltage “Calibration Number” can be read from the track output with a 
voltmeter, with the 3-postion calibration toggle switch in the “Cal” position. 
 
The two available calibration resistor values available for the PTM-1 module are: 
 

HIGH GAIN (1 MEGOHM CAL RESISTOR): UPPER SWITCH POSITION 

This is for use typically with HT-400 Strain Gain sensors or other sensor 
types where the deflection and signal output is low. 

 
LOW GAIN (140K OHM CAL RESISTOR): LOWER SWITCH POSTION 

This can be used with HT-400 Strain Gain sensors, in press load monitoring 
applications where high deflection and signal output is present.  It should 
also be used with load cells having mid-range output (approx. 0.50-1.00 
mV/V) or having high output (greater than 1.00 mV/V). 

 
When the “Zero Balance” and “Calibration” procedures are completed, the toggle switch 
should be set to the lower “A/Z” (Auto-Zero) position for normal operation. 
 
 

Summary of Contents for PTM-1100 Series

Page 1: ...1 HELM INSTRUMENT CO INC PTM 1100 USER MANUAL REV 1 JUNE 2010 Helm Instrument Company Inc 361 West Dussel Drive Maumee Ohio 43537 USA 419 893 4356 Fax 419 893 1371 www helminstrument com...

Page 2: ...ring or replacing any defective Product at no additional charge and returning Product to customer freight paid Repair parts and replacement Products shall be furnished on an exchange basis and shall b...

Page 3: ...IONS 3 CUSTOMER SUPPLIED POWER 3 CAM INPUT 3 HIGH LOW CAPACITY FAULT RELAY OUTPUT 3 STRAIN GAGE INPUT 3 TOUCH SCREEN INTERFACE 4 MAIN MENU 4 SETUP SCREEN 5 JOB RECIPE SCREEN 6 PTM MODULE 7 STRAIN GAGE...

Page 4: ...MODULE PTM is a single channel strain gage sensor input module to process the signal of the strain gage to analog output PTM provides Auto Zero feature patented by Helm Instrument Co Inc The Auto Zero...

Page 5: ...ded 24VDC and DC common or Use the supplied DC1 24VDC through a dry contact to A1 and connect DC2 0VDC to A2 This input can be triggered with a proximity switch or a PLC output This input is the look...

Page 6: ...t Low Capacity Alarm Set point Pilot is set when there is a Low tonnage alarm Pilot can be set and relay is off if in calibrate mode SPM Displays the current Strokes Per Minute which is calculated bas...

Page 7: ...capacity of the press HIGH TONNAGE Displays the current High Capacity Alarm Set point Pilot is set when there is a High tonnage alarm Pilot can be set and relay is off if in calibrate mode LOW TONNAG...

Page 8: ...e the desired recipe 1 20 UP ARROW Used to move to higher value recipe DOWN ARROW Used to move to lower value recipe HIGH TONNAGE Press to set the recipe High Capacity Alarm Set point LOW TONNAGE Pres...

Page 9: ...the module to the center Off position cycle the press and record developed tonnage 2 Adjust the gain pot CW and cycle the press again 3 Compare the Peak Output scaled value on the display meter to the...

Page 10: ...the Peak Capture for the new machine cycle Normal Operation After the set up and calibration have been completed the 3 position calibration toggle switch should be set to the lower A Z Auto Zero posi...

Page 11: ...PTM 1100 Operators Manual 9 PTM MODULE DRAWING...

Page 12: ...PTM 1100 Operators Manual 10 PTM MODULE WIRING...

Page 13: ...PTM 1100 Operators Manual 11 PTM MODULE SIGNAL DIAGRAM...

Page 14: ...PTM 1100 Operators Manual 12 PTM 1100 USER CONNECTIONS...

Reviews: