PTM-1100
Operators
Manual
4
TOUCH SCREEN INTERFACE
MAIN MENU
Main menu allows you to access different area of the system. The PTM-1100™ features a
touch screen display for easy navigation and operation of the system. Click or touch on the
button you wish to access.
JOB
– Displays the current job. Press to go to job screen.
PEAK TONNAGE
– Displays the peak tonnage value.
CAM INPUT
– Pilot is set when Cam input is on (high).
HIGH TONNAGE
– Displays the current High Capacity Alarm Set point. Pilot is set when
there is a High tonnage alarm.
Pilot can be set and relay is off, if in calibrate mode.
LOW TONNAGE
– Displays the current Low Capacity Alarm Set point. Pilot is set when there
is a Low tonnage alarm.
Pilot can be set and relay is off, if in calibrate mode.
SPM
– Displays the current Strokes Per Minute, which is calculated based on the duration of
time between cam pulses.
HOME
– This button is inactive on the main screen, but will return the user to the main
screen when pressed.
FAULT RESET
– This button will clear all displayed faults and fault relay outputs.
SETUP SCREEN
– Pressing this will prompt the user for the Setup Password. By pressing
the 0-9 number button the user can navigate to the keypad and enter the numeric password.
Once entered, press the Enter (Carriage Return, in lower right corner). Then press OK and
press the setup screen button again. The password privileges will automatically reset after 5
minutes of screen inactivity.