background image

Ground-to-Air Heat Exchanger LEWT Kit

3

  ELECTRICAL CONNECTIONS

The thermostat must be mounted outside on the north side of the building in a 
weatherproof position at a height of at least 1 m. (The thermostat has protection 
class IP54).
Direct sunlight and installation above windows, ventilation outlets or other heat 
sources must be avoided.
The temperature range for switching the bypass shutter must be set on the ther­
mostat (recommended setting range: minimum direct intake temperature 5 °C; 
max. direct intake temperature 20 °C). In case of outside temperatures which are 
above or below the set value, the outside air will be taken in via the heat exchanger 
duct. The thermostat controls the bypass shutter when “Thermostat operation” is 
activated in the set temperature ranges. The thermostat and servomotor of the 

bypass shutter must be connected to the control box according to SS­798 (see 
SS­798).

Note:
–  The electrical connections must be carried out by an authorised electrician.
–  Fuses, wiring and earthing must be carried out according to local provisions.
–  The servomotor of the bypass shutter must be surge­protected.
–  The power supply must be interrupted before any work on the thermostats, 

control box and servomotor.

  ACCESSORIES, SWITCHES AND CONTROL ELEMENTS

The use of accessory parts which are not recommended or offered by Helios is 
not permissible. Any potential damages are not covered by warranty.

  WARRANTY CLAIMS – EXCLUSION OF LIABILITY

If the preceding versions are not observed, 

the warranty 

and handling on a good­

will basis shall cease. The same applies to liability claims against the manufacturer.

  CERTIFICATES – GUIDELINES

If the unit is installed correctly and used for its intended purpose, it conforms 
to all applicable provisions and CE guidelines at its date of manufacture

.   

  TECHNICAL DATA

Dual thermostat for LEWT controller

Capacity: 

16 A (4A ind.)

Voltage: 

230 V~

Protection class: 

IP54

Temperature range:  2 x 0–40 °C 
 adjustable

Servomotor

Voltage: 

220–260 V

Power consumption:  1.5 W
Protection class: 

IP54

Pressure loss diagram Outside air intake

with filter G3 and 40 m undersoil collector duct in pure condition

Fig. 1: Basic diagram for installation in buildings with basements

Pressure loss Slatted hood with filter G3 in pure condition

Summary of Contents for LEWT Series

Page 1: ...BETRIEBS VORSCHRIFT Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicher heit sind alle nachstehenden Vor schriften genau durchzulesen und zu beachten EMPFANG Sendung sofort bei Anl...

Page 2: ...die Zuluft angesaugt Die Au enluft Ansaugs ule ist aus rostfreiem Edelstahl Oberfl che der Klasse III C Innerhalb der Au enluft S ule ist ein Kegelfilter der Klasse G3 integriert der ein Ein drin gen...

Page 3: ...en sind nach den rtlichen Vor schrif ten auszuf hren Der Stell Antrieb der Bypassklappe ist vor berspannungsst en zu sch tzen Vor jedem Eingriff in den Thermostaten der Elektrobox und des Stellantrieb...

Page 4: ...Siemensstra e 15 6023 Innsbruck Colchester Essex CO4 9HZ Au enluft Erdw rme M N L L auf 2 5 3 1 6 4 Wippen L1 N L1 L1 L1 N PE PE N PE 1 2 Stellmotor auf 1 Ruhezustand Erdw rme Von 5 C bis 20 C wird A...

Page 5: ...INSTALLATION AND OPERATING INSTRUCTIONS All the following provisions must be read carefully and observed in order to ensure correct functioning and for safety purposes RECEIPT Please check delivery im...

Page 6: ...is made from stainless steel surface class III C A cone filter class G3 is integrated in the outside air intake duct which prevents the intrusion of small animals insects and contaminants APPLICATION...

Page 7: ...according to local provisions The servomotor of the bypass shutter must be surge protected The power supply must be interrupted before any work on the thermostats control box and servomotor ACCESSORIE...

Page 8: ...me Von 5 C bis 20 C wird Au enluft direkt geschaltet Au enluft direkt Au enluft ber Erdw rme 2 fach Thermostat Schalter Manuell Thermostat Stellmotor f r Klappenantrieb 1 2 3 Thermostat Betrieb manuel...

Reviews: