Basic fan speed
= 1
Maximum fan speed
= 8
(CO
2
)-adjustment
= 900 ppm CO
2
Basic humidity level
= value chosen either automatically or manually
Adjustment intervall
= 10 min.
Freezing protection (cell)
= 3 °C
Freezing protection hysteresis
= 3 °C
Preheating setpoint
= -3 °C (change to +5 °C if you want to enable the function)
Maintenance reminder
= 4 months
Cell bypass
= 10 °C
Cascade control
= not active
Humidity level (RF level) adjustment
= automatic
Switchtyp
= fireplace switch
Supply fan
= 100 %
Extract fan
= 100 %
1.4. Factory Settings
Unit KWL EC 300 Pro has the following factory settings:
(CO
2
)-adjustment
= 1000 ppm CO
2
Preheating setpoint
= 5 °C
Note to software reset:
If the KWL-unit is set back via the remote control in the setting menu factory settings
(page 14, section 1.3.8) the above-mentioned data will be transferred with exception of:
FACTORY SETTINGS
17