Central ventilation unit –
KWL 220/340 D
Installation and Operating Instructions
EN
EN
16
The metal trays prevent the accumulation of condensate in this area and they must be checked for correct
positioning (cf. Fig. 23 and Fig. 24).
2. Attach mounting bracket with anti-vibration dampers (4x; included in delivery) to the lower side walls with metal
screws (see Fig. 25 and Fig. 26).
3. Mount the unit to the ceiling with long M8 threaded rods (see Fig. 26).
4.3 Install ball siphon
4.3.1 Variant 1: Installation on unit
During heating periods, condensate may form in the heat exchanger due to the heat recovery process. The condensa-
te must be able to drain freely from the unit. The provided ball siphon (scope of delivery) must be installed in the base
tray of the unit for this purpose.
1. Open ball siphon. Turn the mounting part a 1/4 turn (see Fig. 27).
2. Plug the mounting part in the condensate outlet from below, until the claw fasteners snap to the sheet edge of the
Fig. 23
Fig. 24
4x mounting bracket
Fig. 25
Mounting bracket
Duct
connection
sockets
Fig. 26
Fig. 27
View below
View above
Fig. 28
Mounting part with
seal elements
Locking part
Float ball
Siphon casing
Hose connector
Summary of Contents for KWL 220 D
Page 37: ...Zentrales Lüftungsgerät KWL 220 340 D Montage und Betriebsvorschrift DE 36 ...
Page 73: ...Central ventilation unit KWL 220 340 D Installation and Operating Instructions EN 36 ...
Page 109: ...Unité de ventilation centrale KWL 220 340 D Notice de montage et d utilisation FR 36 ...
Page 110: ...Unité de ventilation centrale KWL 220 340 D Notice de montage et d utilisation FR 37 ...
Page 111: ...Unité de ventilation centrale KWL 220 340 D Notice de montage et d utilisation FR 38 ...