3 .0 Technical data
Type overview EVS
Housing
/
control cabinet
without
connection for centrifugal cooling air fan
Housing
/
control cabinet
with
connection for centrifugal cooling air fan and integrated air-flow monitors
CHAPTER 3
INSTALLATION
EVS-FUEC
EVS-W
EVS-D
EVS-SD
EVS-DA
Switching
0-10 V
Direct
Direct
Y/
d
Y/ YY
Power input
Arbitrary
up to 4.00 kW
up to 4.00 kW
up to 55.00 kW
up to 55.00 kW
Nominal voltage
230 V
230 V
400 V
400 V
400 V
Phases
1~
1~
3~
3~
3~
Current
Alternating
Alternating
Three-phase
Three-phase
Three-phase
Frequency
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
Control voltage
24 V
24 V
24 V
24 V
24 V
Control fuse
6 A
6 A
6 A
6 A
6 A
Y
/
d
start-up time
–
–
–
1.5 - 30 sec.
–
Start-up time
–
–
–
–
1.5 - 30 sec.
Reset spin time
–
–
–
–
3.0 - 60 sec.
Cable entries
8 n
8 n
8 n
12 n
12 n
Ambient temperature
0 °C to +40 °C
0 °C to +40 °C
0 °C to +40 °C
0 °C to +40 °C
0 °C to +40 °C
Protection category
IP54
IP54
IP54
IP54
IP54
Rated output (Type)
Material
Dimensions (H x W x D)
Protection cat . Prot . class
4 kW (EVS-W, EVS-D, EVS-FUEC)
Plastic
320 x 240 x 130
IP54
II
4 kW (EVS-SD, EVS-DA)
Plastic
400 x 320 x 130
IP54
II
5 .5 kW (EVS-SD, EVS-DA)
Plastic
400 x 320 x 190
IP54
II
7 .5 kW (EVS-SD, EVS-DA)
Plastic
400 x 320 x 190
IP54
II
11 kW (EVS-SD, EVS-DA)
Plastic
400 x 320 x 190
IP54
II
15 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
18 .5 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
22 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
30 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
II
45 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
II
55 kW (EVS-SD, EVS-DA)
Sheet metal
800 x 800 x 300
IP54
II
Rated output (Type)
Material
Dimensions (H x W x D)
Protection cat . Prot . class
4 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 130
IP54
II
5 .5 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
7 .5 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
11 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
15 kW (EVS-SD, EVS-DA)
Plastic
480 x 400 x 190
IP54
II
18 .5 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
I
22 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
I
30 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
I
45 kW (EVS-SD, EVS-DA)
Sheet metal
600 x 600 x 250
IP54
I
55 kW (EVS-SD, EVS-DA)
Sheet metal
800 x 800 x 300
IP54
I
EN
Summary of Contents for EVS Series
Page 9: ...7 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 10: ...8 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 11: ...9 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 12: ...10 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS D DE ...
Page 13: ...11 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 14: ...12 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 15: ...13 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 16: ...14 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS SD DE ...
Page 17: ...15 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 18: ...16 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 19: ...17 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 20: ...18 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS DA DE ...
Page 21: ...19 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 22: ...20 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 23: ...21 Entrauchungsventilatoren Steuerung EVS Montage und Betriebsvorschrift EVS W DE ...
Page 62: ...30 Smoke exhaust fan control system EVS Installation and Operating Instructions ...
Page 63: ...31 Smoke exhaust fan control system EVS Installation and Operating Instructions ...