Cold Water Cooling Register AIR1-KR KW
Installation and Operating Instruc
tions
9
When using the cooling register below, the corresponding AIR1 XC unit must be suspended lower from the ceiling (see
table,Fig.10).
– for ventilation units AIR1 XH and RH
When installing the unit, the following criteria must be observed when installing the unit to ensure easy accessibility for
maintenance and maintenance work (Fig.11).
A:
Minimum distance for servicing the cooling register.
2�2�1 Cold water cooling register for AIR1 XC ventilation units
The AIR1 unit must be fully isolated from the mains power supply before all maintenance and installation work
and opening the terminal compartment! The electrical connections must be carried out in accordance with the
following wiring diagrams and must only be carried out by qualified electricians� The electrical connection must
be fully isolated until the final assembly!
1. The cooling register has 4 mounting brackets for installation (see Fig.12). Suspend the cooling register with these
mounting brackets using the rubber dampers. Before suspension, apply sealing strips where the cooling register is
joined together with the AIR1 unit.
Type
H (mm)
AIR1-KR KW XC 700
35
AIR1-KR KW XC 1400
40
Fig�10
H
Fig�11
Type
A (mm)
AIR1-KR KW RH 1500
960
AIR1-KR KW RH 2000
1060
AIR1-KR KW RH 3000
1170
AIR1-KR KW RH 5000
1440
AIR1-KR KW RH 6000
1560
AIR1-KR KW RH 8000
1810
AIR1-KR KW RH 9500
1910
AIR1-KR KW RH 12000
2060
AIR1-KR KW RH 15000
2310
Type
A (mm)
AIR1-KR KW XH 1000
985
AIR1-KR KW XH 1500
995
AIR1-KR KW XH 2500
1215
AIR1-KR KW XH 3500
1375
AIR1-KR KW XH 4500
1425
AIR1-KR KW XH 5500
1635
AIR1-KR KW XH 7000
1935
AIR1-KR KW XH 8500
2285
m
DANGER
Fig�12