Central Ventilation Units KWL EC 800 S/1200 S/1800 S/2600 S Pro/WW
Installation and Operating Instructions
6.9 Troubleshooting
Fault
Unit behaviour
Problem
Solution
4 - Supply air fan fault
Unit does not operate
Fan overheating or damage
to the thermal contacts of
the supply air fan
Determine cause of fan overheating (faulty bearing, mechani-
cal problem, short circuit,...). If necessary, replace the fan.
5 - Extract air fan fault
Unit does not operate
Fan overheating or damage
to the thermal contacts of
the extract air fan
Determine cause of fan overheating (faulty bearing, mechani-
cal problem, short circuit,...). If necessary, replace the fan.
6 - Supply air filter blocked
Unit ventilates
Filter blocked
Check condition of filter and replace if necessary.
7 - Extract air filter blocked
Unit ventilates
Filter blocked
Check condition of filter and replace if necessary.
8 - Preheater 1 failure
Unit ventilates
Pre-heater overheated
Check whether the air can freely flow through the unit and
the electrical pre-heater is cooling sufficiently. Check the
triggering of the safety temperature limiter.
9 - Preheater 1 fault
Unit ventilates
Pre-heater overheated
Check whether the air can freely flow through the unit and
the electrical pre-heater is cooling sufficiently. Check the
triggering of the safety temperature limiter.
12 - CO2 sensor fault
Unit ventilates
Air quality sensor malfun-
ction
Check whether the CO2 sensor is correctly connected. If
necessary, check the functioning of the CO2 sensor (output
signal value).
16 - Supply air - Faulty
outside air temp. sensor
(T-EXT1)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
17 - Supply air - Faulty tem-
perature sensor behind the
heat exchanger (T-EXT2)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
18 - Supply air - Faulty
temperature sensor in the
supply air duct (T-EXT3)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
19 - Supply air - Fault with
temperature sensor behind
the second heater battery
(T-EXT4)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
20 - Extract air - Faulty
temperature sensor in the
extract air duct (T-INT0)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
20 - Extract air - Faulty
temperature sensor in the
extract air duct (T-INT1)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
22 - Extract air - Faulty frost
protection temperature
sensor in heat exchanger
(T-INT2)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
23 - Faulty temperature
sensor for the hot water
heater battery water return
(T_WATER_IN)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
24 - Faulty temperature
sensor for the water return
(T_WATER_OUT)
Unit does not operate
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
25 - Faulty room tempera-
ture sensor (T_Room)
Unit ventilates
Temperature sensor fault
Check whether the sensor is correctly connected to the
electronics. If necessary, carry out function test on sensor
using resistance measurement (the resistance value at +20°C
is around 10kW)
26 - Fault with pressure
sensor of extract air filter
Unit ventilates
Pressure sensor fault
Check whether the measuring device is damaged or
contaminated. Check the pressure hoses for consistency. If
necessary, replace the pressure sensor module.
EN