4. SEttINGS
4.1.0.4. Links
•
‘Setup Monitoring communication’
takes you to a page to register
your controller with the Heliodyne Monitoring Service. Once you
are registered with the service, this link is hidden. See section 5.
•
‘test remote Monitoring communication’
will perform a test to see
if the controller can contact the Heliodyne remote server.
•
‘Download System Sensor and Energy Data’
opens a new page
which displays all the current saved history data in the controller,
about 1 month’s worth of sensor and energy data.
•
‘relay and variable Speed Output control Panel’
opens a new
page within which one can manually turn on and off relays and
set pump speeds.
•
‘Update Software version’
directs you to a page to begin the
software update process. See Section 6.
CHanGInG ConTRolleR oPeRaTIon seTTInGs
12
4.1.1. OPErAtION Bar
4.1.1.0. Solar relay Box
FUNCTION DESCRIPTION
DEFAULT
SETTINg LIMIT
The minimum Differential (Value of [T1 minus T2], or if T3 is installed
and the average is used [T1 minus the average of T2 & T3] ), to turn
Relay 1 ON from OFF
18°F [CL], 9 [OL]
2°F
≤
V
≤
100°F
Check this box to use the tank average in Differential and High Limit
Operation (with T3 installed)
OFF
ON / OFF
During Relay 1 operation, the maximum Differential the system can
exhibit in order for Relay 1 to turn back OFF
5°F [CL], 4 [OL]
0°F
≤
V < On Diff.
The percentage of Dowfrost HD propylene glycol in the heat transfer
fluid to be used in the energy calculation
50% [CL], 0 [OL]
0%
≤
V
≤
70%
The limit Value T2, or the average of T2 & T3 if installed, at which the
solar relay will turn OFF even with a satisfactory differential. NOT TO BE
RELIED UPON AS A SAFETY LIMIT OR PRIMARY LIMIT CONTROL.
160°F
80°F
≤
V
≤
200°F
Check this box to use the Tank High Limit Function
ON
ON / OFF
High limit hysteresis - The value that the tank temperature must drop by
in order to enable the solar relay to add more solar energy
5°
1°F
≤
V
≤
20°F
The minimum Value T1 must be greater than for the differential function
to begin monitoring the differential
82°F [CL], 80 [OL]
50°F
≤
V
≤
200°F
Uses the cool nighttime collectors to deplete energy from the storage.
Set the minimum T2 Value, or T3 if installed, to cool the tank down to.
120°F
80°F
≤
V
≤
200°F
Check this box to use the Vacation Mode function
OFF
ON / OFF
If the selected system on the SETTINgS > SYSTEM bar is Open Loop,
recirculates warm storage water through the collector loop when this
value is greater than T1.
35°F [OL Only]
33°F
≤
V
≤
80°F
Check this box to use Freeze recirculation when the set system is not
Open Loop
OFF (CL)
ON / OFF
Check this box when operating a Drain Back system to prevent thermal
shock when the Differential is greater than 100°F and the Solar Relay,
Relay 1, is off.
OFF
ON / OFF
FIg. 4.1.0.4
FIg. 4.1.1