11. Maintenance |
27
11. Maintenance
To be able to guarantee the
impeccable function of the smoke
alarm incl. radio module, an on-site
inspection including functional test
is to be carried out, at least once per
year (12 ± 3 months), in accordance
with the national directives
and regulations (in Germany in
accordance with DIN 14676-1). Please
refer to the chapter "Maintenance"
in the operating manual of the
smoke alarm.
For radio smoke alarms, we also
recommend carrying out a line test.
For better traceability, we
recommend documenting the
maintenance work.
11.1 Line test
The line test checks whether all
smoke alarms in a line with the same
ID are within range and functional.
Performing a line test
f
Remove a radio smoke alarm
form the base.
f
Press the test button briefly.
Ö
All smoke alarms in this
line that can be reached by
radio signal signal this for
15 minutes by a reduced triple
acoustic signal and green
flashing of the LED every
8 seconds.
f
Press the test button on all
signalling radio smoke alarms
within these 15 minutes in
succession.
Ö
Every smoke alarm confirms
its availability by a positive