8. Radio commissioning |
17
8. Radio commissioning
Radio commissioning is carried out
for each line, i.e. each line must be
commissioned separately. If 2 A.0
lines are to be operated in parallel,
2 radio commissioning operations
must be carried out in succession.
This ensures that the lines emit
alarms separately and independently.
Requirements
A radio smoke alarm of the line
is ready at hand, but not yet
screwed into the base.
All other radio smoke alarms of
this line are completely assembled
and signal their readiness for
commissioning by means of the
running light ( green-orange-red )
on the test button every
8 seconds.
Performing radio commissioning
After the start of commission-
ing, all users of this line
must be confirmed within
15 minutes by pressing the test
button.
f
Press and hold the red operating
button on the ready but not yet
mounted smoke alarm for at least
5 seconds until the radio module
LED lights up permanently.
f
Release the red operating button.
Ö
The radio module LED con-
tinues to flash for a short
time.
f
Screw the smoke alarm into the
base.
Ö
All smoke alarms of this
line within range will signal
the receipt of the signal for
i
Summary of Contents for Standard X