INSTALLATION INSTRUCTIONS

Fan Coils: FEM4X, FEM4P, REM4X, FXM4X

14

496 01 5503 02

Specifications  are subject to change without notice.

FEM / REM

 

AIRFLOW PERFORMANCE TABLES

Table 1 

 Airflow Performance (CFM)

MODEL & SIZE

BLOWER SPEED

TOTAL STATIC (inches water column)

0.10

0.20

0.30

0.40

0.50

0.60

1800

Tap 5

767

739

702

669

620

565

Tap 4

614

569

534

486

436

398

Tap 3

701

660

616

581

537

499

Tap 2

614

569

534

486

436

398

Tap 1

410

350

304

261

228

203

FEM4P2400

Tap 5

969

936

892

835

763

676

Tap 4

826

795

766

743

706

660

Tap 3

826

795

766

743

706

660

Tap 2

701

660

616

581

537

499

Tap 1

617

592

552

507

472

420

FEM4X2400

REM4X2400

Tap 5

965

920

870

823

780

740

Tap 4

820

783

740

680

630

575

Tap 3

820

783

740

680

630

575

Tap 2

720

655

610

555

485

450

Tap 1

716

600

540

495

430

328

3000

Tap 5

1108

1090

1065

1034

1009

974

Tap 4

1026

1000

969

938

899

865

Tap 3

1026

1000

969

938

899

865

Tap 2

909

873

842

799

762

724

Tap 1

825

795

757

722

674

634

3600

Tap 5

1301

1276

1245

1218

1176

1121

Tap 4

1227

1191

1169

1143

1105

1074

Tap 3

1227

1191

1169

1143

1105

1074

Tap 2

1087

1062

1030

1001

966

930

Tap 1

1026

1000

969

938

899

865

4200

Tap 5

1560

1544

1507

1464

1424

1358

Tap 4

1419

1397

1358

1320

1279

1239

Tap 3

1419

1397

1358

1320

1279

1239

Tap 2

1249

1220

1184

1142

1093

1052

Tap 1

1242

1205

1158

1110

1069

1026

4800

Tap 5

1743

1712

1679

1642

1610

1574

Tap 4

1669

1634

1599

1564

1531

1499

Tap 3

1669

1634

1599

1564

1531

1499

Tap 2

1452

1413

1377

1339

1308

1271

Tap 1

1300

1256

1221

1182

1142

1101

6000

Tap 5

1897

1867

1836

1808

1774

1736

Tap 4

1817

1785

1757

1724

1693

1655

Tap 3

1817

1785

1757

1724

1693

1655

Tap 2

1657

1621

1589

1557

1518

1474

Tap 1

1443

1412

1377

1332

1286

1243

 - Airflow outside 450 cfm/ton.

NOTES:

1. Airflow based upon dry coil at 230v with factory

approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes

4200 through 6000). For FEM4X, FEM4P, and REM4X models, airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a

constant torque motor. The torque doesn’t drop off at the speeds the motor operates.

2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:

Return static pressure must be less than 0.40 in. wc.

Horizontal applications of 4200 

 6000 sizes must have supply static greater than 0.20 in. wc.

3. Airflow above 400 cfm/ton on 4800 

 6000 size could result in condensate blowing off coil or splashing out of drain pan.

Summary of Contents for FEM4P

Page 1: ...in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or picture...

Page 2: ...ly duct work NOTE If the door gasket is damaged or missing the unit may not meet the ASHRAE 193 standard for cabinet air leakage Contact your supplier and order kit 1191140 Nuisance sweating may occur...

Page 3: ...REM36 17 432mm FXM30 19 483mm B MODULAR UNITS FEM4X6000B REM4X6000B and FXM4X4800 6000 fan coils are two piece modular units This allows for modular units to be disassembled and components moved sepa...

Page 4: ...kaged with accessory kit See Product Specification literature for kit part numbers During the conversion process remove the plastic cap covering the vertical drains only and discard Remove the plug fr...

Page 5: ...fitting panel refer to Figure 5 2 Remove coil mounting screw securing coil assembly to right side casing flange 3 Remove coil assembly 4 Lay fan coil unit on its right side and reinstall coil assembly...

Page 6: ...ghs C and install on opposite tube sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly 8 Slide coil assembly into casing Be sure coil bracket on each corne...

Page 7: ...NST WALL 1 8 3mm INCH THICK ANGLE MOUNTING BRACKET TYPICAL BOTH SIDES SECURE FAN COIL TO STRUCTURE UNIT AWAY FROM WALL PIPE STRAP SECURE UNIT TO FLOOR ANGLE BRACKET OR PIPE STRAP 4 102mm MAX 4 102mm M...

Page 8: ...rmed until the main disconnect switch remote to the unit is turned off A LINE VOLTAGE CONNECTIONS Fan Coils installed without electric heat require the use of a factory authorized Power Plug Kit acces...

Page 9: ...uninterrupted or unbroken ground in order to minimize potential for personal injury or death if an electrical fault should occur The ground may consist of electrical wire or metal conduit when instal...

Page 10: ...it bottoms 3 Braze connection using silver bearing or non silver bearing brazing materials Do not use solder materials which melt below 800_F 427_C Consult local code requirements 4 Evacuate coil and...

Page 11: ...equired Consult outdoor unit pre sale literature for start assist kit part number Figure 15 Refrigerant Flow Control Device TEFLON SEAL BRASS HEX NUT STRAINER PISTON RETAINER BRASS HEX BODY DISTRIBUTO...

Page 12: ...w running traps are inadequate and DO NOT allow proper condensate drainage refer to Figure 17 Figure 16 Recommended Condensate Trap 2 MIN 51mm 2 MIN 51mm UNIT Figure 17 Insufficient Condensate Trap DO...

Page 13: ...r motor is de energized and stops E ELECTRIC HEAT OR EMERGENCY HEAT MODE Thermostat closes R to W W energizes electric heat relay s which completes circuit to heater element s W also energizes the ind...

Page 14: ...4200 Tap 5 1560 1544 1507 1464 1424 1358 Tap 4 1419 1397 1358 1320 1279 1239 Tap 3 1419 1397 1358 1320 1279 1239 Tap 2 1249 1220 1184 1142 1093 1052 Tap 1 1242 1205 1158 1110 1069 1026 4800 Tap 5 1743...

Page 15: ...1294 1245 Tap 2 1257 1226 1191 1141 1090 1033 Tap 1 1237 1206 1160 1121 1070 1013 FXM4X4800 Tap 5 1757 1725 1693 1653 1614 1576 Tap 4 1664 1626 1593 1552 1517 1477 Tap 3 1664 1626 1593 1552 1517 1477...

Page 16: ...049 0 059 FXM4X24 0 016 0 027 0 038 0 049 0 059 30 0 049 0 059 0 070 0 080 36 0 070 0 080 0 090 0 099 FXM4X36 0 055 0 064 0 073 0 081 42 0 049 0 056 0 063 0 070 48 0 063 0 070 0 076 0 083 0 090 FXM4X...

Page 17: ...ere POE oils may cause damage to certain plastics and roofing materials Vacuum pumps will not remove moisture from oil A liquid line filter drier is required on every unit Do not use liquid line filte...