background image

11

Installation Instructions and Owner’s Manual

Unvented Natural Gas Vent Free Room Heaters

connecting the gas supply, the control knob should be 
depressed for about 30 seconds. This will allow air to bleed 
from the gas system.
6. With control knob pressed in, push down and release 

the ignition button. This will light pilot. If needed keep 
pressing igniter button until pilot lights. 

7. Keep control knob pressed in for (30) seconds after 

lighting pilot. After 30 seconds, release control knob.

• 

 If pilot does not stay lit, refer to Troubleshooting, pages 

12-13. Also, contact a qualified service person or gas 

supplier for repairs. 

• 

 If control knob does not pop up when released, contact 

a qualified service person or gas supplier for repairs.

8. When the pilot is lit, turn the control knob 

counterclockwise 

 to heating level. The main burner 

should light.

9. To select the desired heat level, turn the temperature 

setting knob to desired comfort setting from 1 to 5. 

CAUTION:

 Do not try to adjust heating level by using 

equipment shutoff valve. 

TO TURN OFF GAS TO APPLIANCE

SHUTTING OFF HEATER:

1.  Turn off equipment shutoff valve. 

2.  Turn control knob clockwise 

 to the OFF 

position.

SHUTTING OFF BURNER ONLY (PILOT STAYS LIT)

1.  Turn control knob clockwise 

 to the PILOT/IGN 

position.

THERMOSTAT CONTROL OPERATION

FOR HSSVFRD20NGBT / HSSVFRD30NGBT: 

The thermostatic control used simply turns on and off the 
burner.

FOR HSSVFBF20NGBT / HSSVFBF30NGBT: 

The thermostatic control used modulates the flame size as 
the temperature gets closer to set point, then it turns off 
the burner upon reaching temperature. 
The burner will cycle back on when room temperature 
drops below the set temperature. The control knob can 
be set to any heat level between 1 and 5. Selecting the HI 
setting will cause the burner to remain on.

INSPECTING BURNER

Check pilot flame pattern and burner flame pattern often.

PILOT FLAME PATTERN

Figure 17 show a correct pilot flame pattern and also shows 

an incorrect pilot flame pattern. The incorrect pilot flame 
pattern is not touching thermocouple. This will cause the 
thermocouple to cool. When the thermocouple cools, the 
heater will shut down. If pilot flame pattern is incorrect, as 

shown in Figure 17:

• 

Turn heater off (see To Turn OFF Gas to Appliance, 
page 10)

 

• 

See Troubleshooting, pages 12-13.

Figure 17

Correct pilot position.

Incorrect pilot position.

Summary of Contents for HSSVFBF20NGBT

Page 1: ...llation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisi...

Page 2: ...lts should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room wi...

Page 3: ...ximum 14 Inches of Water 14 Inches of Water 14 Inches of Water 14 Inches of Water Inlet Gas Pressure Minimum 7 Inches of Water 7 Inches of Water 7 Inches of Water 7 Inches of Water Electrical Rating B...

Page 4: ...ose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kW of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is no...

Page 5: ...space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adj...

Page 6: ...ble alternative to test gauge connection Purchase a CSA AGA certified equipment shutoff valve from your dealer LOCATING HEATER This heater is designed to be mounted on the wall The heater can also be...

Page 7: ...wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in fig ure 7 If you can provide greater clearances from the floor and joining wall...

Page 8: ...ING AWAY FROM WALL Installing Support Feet See figure 11 1 Lay heater onto table on its back with bottom edge overhanging table edge 2 Securely attach feet to bottom of heater using 2 self tapping scr...

Page 9: ...ppliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psi 3 5 kPa 2 Cap off open en...

Page 10: ...ettle on the floor WHAT TO DO IF YOU SMELL GAS Shut off gas supply Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call you gas s...

Page 11: ...HEATER 1 Turn off equipment shutoff valve 2 Turn control knob clockwise to the OFF position SHUTTING OFF BURNER ONLY PILOT STAYS LIT 1 Turn control knob clockwise to the PILOT IGN position THERMOSTAT...

Page 12: ...lean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot assembly c...

Page 13: ...13 Installation Instructions and Owner s Manual Unvented Natural Gas Vent Free Room Heaters PAGE LEFT INTENTIONALLY BLANK...

Page 14: ...d by any metal or tubing Keep igniter cable dry Broken igniter cable Replace igniter cable Bad Piezo igniter Replace control valve Low Battery Replace battery When igniter button is pressed in there i...

Page 15: ...irty or partially clogged burner orifice Clean burner orifice see Cleaning and Maintenance on page 1 1 or replace burner orifice White powder residue forming within burner box or on adjacent walls or...

Page 16: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Page 17: ...Valve 1 12 80019 Igniter Module 1 ITEM P N PART DESCRIPTION QTY 13 80010 Thermostat Valve Mounting Bracket 1 14 8001 1 Igniter Module Mounting Bracket 1 15 80058 Floor Mounting Feet Beige 1 80214 Floo...

Page 18: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Page 19: ...1 ITEM P N PART DESCRIPTION QTY 14 70640 Thermostat Valve 1 15 80014 Igniter Wire 1 16 80019 Igniter Module 1 17 8001 1 Igniter Module Mounting Bracket 1 18 80010 Thermostat Valve Mounting Bracket 1...

Page 20: ...MITED WARRANTY Enerco Group Inc EGI warrants Heatstar Vent free heaters to be free from defects in material and workmanship for a period of five years from the date of manufacture During the first two...

Reviews: