COMMISSIONING
31
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line Value
17
1
Variable selection:
cooling function,
thermostat function or
temperature difference
controller function
0 = Off
1 = Cooling
2 = Heating
3 = Temperature
difference controller
0
18
5
Selects the sensor
for the independent
controller (source)
1-6
5
“Programming” menu
Display
Meaning
Value
range
Factory
setting
max 40ºC
Switch-on temperature for
cooling function
20-90ºC
40ºC
dT 10 K
Hysteresis for cooling function
1-30K
10K
min 00:00:00
1 (2,3)
Time frame 1 (2,3): Start
0:00-23:59
0:00
max 23:59:00
1 (2,3)
Time frame 1 (2,3): Stop
0:00-23:59
23:59
• Heating
If the temperature measured drops below the target value, then output
A3 is activated until the temperature measured reaches the target value
+ hysteresis.
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line Value
17
2
Variable selection:
cooling function,
thermostat function or
temperature difference
controller function
0 = Off
1 = Cooling
2 = Heating
3 = Temperature
difference controller
0
18
5
Selects the sensor
for the independent
controller (source)
1-6
5
“Programming” menu
Display
Meaning
Value
range
Factory
setting
min 40ºC
Switch-on temperature for
heating function
20-90ºC
40ºC
dT 10 K
Hysteresis for heating function
1-30K
10K
min 00:00:00
1 (2,3)
Time frame 1 (2,3): Start
0:00-23:59
0:00
max 23:59:00
1 (2,3)
Time frame 1 (2,3): Stop
0:00-23:59
23:59
• Temperature difference
For independent temperature difference controllers, minimum (e.g. solid
fuel boiler) and maximum temperature limits possible.
If the difference between both measurement points exceeds the hystere-
sis set, then A3 is activated.
In addition, one may also define a maximum temperature for the energy
consumer and a minimum temperature for the energy source.
“Basic Setup” menu
Display
Meaning
Value range
Factory
setting
Line Value
17
3
Variable selection:
cooling function,
thermostat function or
temperature difference
controller function
0 = Off
1 = Cooling
2 = Heating
3 = Temperature
difference controller
0
18
5
Selects the sensor
for the independent
controller (source)
Temperature sensor
heat consumer is
preset to S6
1-5
5
“Programming” menu
Display
Meaning
Value
range
Factory
setting
max
65ºC
Maximum temperature for
heat consumer in ºC
15-
95ºC
65ºC
min
15ºC
Minimum temperature for
heat consumer in ºC
0-95ºC
15ºC
dT max
7 K
Hysteresis dT max in K
3-40K
7K
dT min
3 K
Hysteresis dT min in K
2-35K
3K
min 00:00:00
1 (2,3)
Time frame 1 (2,3): Start for
independent controller
0:00-
23:59
0:00
max 23:59:00
1 (2,3)
Time frame 1 (2,3): Stop for
indenendent controller
0:00-
23:59
23:59
(0:00 for 2 & 3)
1. TUBE COLLECTOR OR START FUNCTION
If the function is active, then the solar circuit pump is started using a
time frame, independently of the actual collector temperature. In this
way, the medium is transported to the measuring point for the collector
temperature.
“Basic Setup” menu
Display
Meaning
Value
range
Factory
setting
Line Value
13
1
Special function for time-controlled
circulation when using tube collectors
0 = Off
1 = On
0
“Programming” menu
Display
Meaning
Value
range
Factory
setting
min 6:00
4
Time frame 4: Start for tube
collector function
0:00-23:59
6:00
max 20:00
4
Time frame 4: Stop for tube
collector function
0:00-23:59
20:00