COMMISSIONING
28
MENU “MANUAL OPERATION”
For commissioning service and test purposes the solar primary system
can be manually operated. For this purpose the switch outputs may be
disconnected or connected.
WARNING: During manual operation there is no automatic regula-
tion of the system. Temperature control is isolated. System tem-
perature could be extremely high.
To avoid inadmissible operating states this mode of operation changes
into “Indication” after approximately 8 hours and the automatic regulation
is activated again.
NOTE:
Exiting this menu will automatically return the system to normal
operation.
MENU “BASIC ADJUSTMENT”
1. Adjustment and changes in this menu must be carried out only by a
competent installer or service engineer.
Incorrect adjustments may
adversely affect the function of controller and solar primary
system.
2. To avoid accidental changes in menu “Basic adjustment”, it is not
editable in normal functioning but has only a display function. To be
able to carry out any changes, this menu must be chosen within the
first minute after switching on the appliance.
The basic adjustment
menu is ‘blocked’ automatically one minute after switching on if
the menu is not accessed.
Indication
Meaning
Value
range
Manual switching on/off switched output A1
(Pump 1)
0=off
1=on
Manual switching on/off switched output A2
(Pump 2/Valve 1)
0=off
1=on
Manual switching on/off of switched output A3
(cooling, thermostat or temperature difference
controller function)
0=off
1=on
Pump type selection
0
Normal 230V pump
1
1=HE pump with non-inverse PWM
Alternatively: DC control
2
2=HE pump with inverse PWM
Alternatively: DC control
Energy yield measurement (glycol type selection)
0
Anro
6
Tyfocor L5.5
1
Ilexan E, Glythermin
7
Dowcal 10
2
Antifrogen L
8
Dowcal 20
3
Antifrogen N
9
Dowcal N
4
Ilexan E
10
Tyfocor LS
5
Ilexan P
Display
Meaning
Value range
Factory
setting
Line Value
*0
0
System diagram
0-4
0
1
1
Primary storage tank selection
1-2
1
2
240
Multiple storage tank systems
Contoller response time in seconds
30-480
240
*3
0
Colector protection function
0=Off
1=On
2=Drain back
0=Off
4
120ºC Collector protection temperature
110-150ºC
120ºC
5
180
Fill time for drain-back function
(if activated)
15-360s
180s
*6
0
Recooling function
(only if collector protection is on)
0=Off
1=On
0=Off
7
40ºC
Recooling temperature for
storage tank
30-90ºC
40ºC
*8
0
Energy yield measurement
DFG=Flow transmitter
VFS=Grundfos sensor
0=Off
1=Flow transmitter
2=VFS
0=Off
9
1,0
If low transmitter is on (8-1):
Litres/pulse
0,5-25l/pulse
0.5l increments
1,0
10
20
If VFS on (8-2): VFS type 1-20
or 2-40
20=1-20
40=2-40
20
11
0
Energy yield measurement
Set glycol type
0-10
0
12
50
Energy yield measurement
Glycol proportion
0-100%
5% increments
50
13
0
Tube collector function,
time-controlled
0=Off
1=On
0=Off
*14
0
Anti-freeze protection function
0=Off
1=On
0
15
6
Anti-freeze protection function
Reference sensor selection
1-6
6
16
3
Anti-freeze protection function
Start temperature
-20ºC - +7ºC
3
*17
0
Independent controller function
0=Off
1=Cooling
2=Heating
3=Temp. difference
controller
0
18
5
Independent controller
Reference sensor
1-6
5
19
0
Pump type A1
0-2
0
20
0
Pump type A2
0-2
0