Heatrae Sadia Express 50 Litres Installation, Operation And Maintenance Manual Download Page 16

16

10. Troubleshooting

10.1 Fault finding

Important

  Servicing should only be carried out by competent 

persons in the installation and maintenance of 

water heating systems.

  Any spare parts used MUST be authorised parts.

  Disconnect the electrical supply before removing 

any electrical equipment covers.

  NEVER bypass any thermal controls.

  The Fault Finding Chart (table 5, below) will enable 

operational faults to be identified and their possible 

causes rectified. 

WARNING

DO NOT tamper with any of the safety 

valves or controls supplied with the water 

heater as this will invalidate any warranty. 

Water contained in the water heater may 

be very hot, especially following a thermal 

control failure. Caution must be taken when 

drawing water from the water heater.

Table 5: Fault finding chart

Spare Parts

A full range of spare parts are available for the

appliance range (table 6, page 20). Refer to the 

technical data label on the appliance to identify the 

model installed and ensure the correct part is ordered. 

You will need to quote the serial number, which is 

printed on the data label. 

FAULT

POSSIBLE CAUSES

ACTION

Water not heating

Electrical supply fault.

Check electrical supply.

Thermal cut-out tripped.

Check cut-out, if operated reset and check 

thermostat operation. If necessary replace.

Thermostat fault.

Check thermostat operation, replace if necessary.

Element fault.

Check element for circuit continuity and insulation 

resistance. If faulty replace.

No water flow - 

General

Cold water supply not turned on.

Check mains water supply is on.

Blockage in cold water supply. 

Check for obstructions.

No water flow 

- Cistern Fed 

installations

Blockage in tapset.

Check for obstructions.

Cistern tank empty.

Check water supply to cistern tank is turned on. 

Check operation of cistern float valve.

Water flows 

gradually reduces 

- Cistern Fed 

installations

Cistern not filling as fast as outlet flow rate.

Check water supply to cistern tank is turned on 

and that the inlet flow rate is equal to outlet flow 

rate. Check operation of cistern float valve.

Vent pipe blockage.

Check vent pipe for obstructions, clear as 

necessary.

Summary of Contents for Express 50 Litres

Page 1: ...Express 50 Litres Installation operation and maintenance manual...

Page 2: ...egulations 9 5 2 Installation requirements 9 5 3 Choice of location 9 5 4 Transport 9 6 Installation 10 6 1 General 10 6 2 Water connections 11 6 3 Electrical connections 13 7 Commissioning 13 7 1 Gen...

Page 3: ...t maintenance of the appliance Failure to abide by the instructions for installing the product Installer s liability The installer is responsible for the installation and the commissioning of the appl...

Page 4: ...m bore of 19mm More than one conventional tap can be supplied WARNING Only competent persons having received adequate training are permitted to work on the appliance and the installation Do not tamper...

Page 5: ...lier s model identifier 50L V 3kW Storage volume V in litres 50 Mixed water at 40 C V40 in litres 83 The declared load profile M The water heating energy efficiency class of the model C The water heat...

Page 6: ...nections Item 50L V 3kW B 369mm D 903mm E 100mm F 371mm G 95mm H OUTLET 22mm 3 4 BSP M I INLET 22mm 3 4 BSP M K 865mm L 131mm M 1 2 BSP female B D E F G H I K L M Figure 1 General dimensions Table 3 G...

Page 7: ...TY BLACK WIRE A TERMINAL BLOCK ELEMENT EARTH IMMERSION STUD L N E OUTER CLADDING L N THERMOSTAT ADJUSTMENT SPINDLE FACTORY SET AT 54 C 2 1 B A RESET CUT OUT TO ELEMENT CUT OUT SENSOR THERMOSTAT SENSOR...

Page 8: ...rmostat This appliance is vented which means that the tank where the water is heated is vented to atmosphere and no pressure is built up in the appliance The appliance can be installed in only one way...

Page 9: ...int of most frequent use Avoid siting where extreme cold temperatures will be experienced All exposed pipe work should be insulated Access to associated controls and immersion heaters must be availabl...

Page 10: ...well as which way up the appliance should be mounted The top bracket bolts should be screwed all the way into the hole until they stop and stick out 8mm as shown in figure 4 below The bottom bracket...

Page 11: ...relief device to the vent pipe of this water heater The cold water supply must be from a cold water feed cistern complying with Byelaw 30 The maximum head pressure must not exceed 20 metres Water Reg...

Page 12: ...emoving any covers Never attempt to replace the immersion heater other than with the recommended immersion heater DO NOT bypass the thermal cut out in any circumstances Ensure the two spade terminatio...

Page 13: ...istern fed installation Open the highest hot outlet fed by the appliance Turn on the cold water supply from the cold water cistern Allow the appliance to fill until water discharges from the hot outle...

Page 14: ...ter is not in use for long periods during the winter months do not switch off the electrical supply and set the thermostat to its minimum position N B This will not protect other system pipework The i...

Page 15: ...the pocket on the immersion heater Place a suitable receptacle beneath the immersion heater to collect any water left in the appliance Unscrew immersion heater bolts and remove immersion heater from...

Page 16: ...del installed and ensure the correct part is ordered You will need to quote the serial number which is printed on the data label FAULT POSSIBLE CAUSES ACTION Water not heating Electrical supply fault...

Page 17: ...sed by your negligence Regular maintenance has been carried out by a competent person or a Heatrae Sadia authorised engineer in accordance with the maintenance requirements set out in this manual The...

Page 18: ...y Users in Private Households in the European Union This symbol on the product indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to...

Page 19: ...19...

Page 20: ...20 13 Spare parts Figure 10 Spare parts...

Page 21: ...ATOR LIGHT BBSC not shown 7037724 6 THERMOSTAT THERMAL CUT OUT BBSC FOR KNOB CONTROL 30 50 7037726 7 THERMOSTAT THERMAL CUT OUT ADAPTER 7037738 8 WALL BRACKET VERTICAL NO BOLTS 7037733 9 FIXING BRACKE...

Page 22: ...22...

Page 23: ...23...

Page 24: ...orate responsibility and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account the...

Reviews: