COMMUNICATIONS
HeatNet Control REV 1.38-1
Page 58
Figure 39
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
30133
Boiler03CyclesLow16
be combined (concatenated) into a
single 32 bit counter as:
Boiler##CyclesHigh16:Boiler##Cyc
lesLow16
Example
Boiler01Cycles =
(Boiler01CyclesHigh16 * 65536) +
Boiler01CyclesLow16
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
30134
Boiler04CyclesHigh16
30135
Boiler04CyclesLow16
30136
Boiler05CyclesHigh16
30137
Boiler05CyclesLow16
30138
Boiler06CyclesHigh16
30139
Boiler06CyclesLow16
30140
Boiler07CyclesHigh16
30141
Boiler07CyclesLow16
30142
Boiler08CyclesHigh16
30143
Boiler08CyclesLow16
30144
Boiler09CyclesHigh16
30145
Boiler09CyclesLow16
30146
Boiler10CyclesHigh16
30147
Boiler10CyclesLow16
30148
Boiler11CyclesHigh16
30149
Boiler11CyclesLow16
30150
Boiler12CyclesHigh16
30151
Boiler12CyclesLow16
30152
Boiler13CyclesHigh16
30153
Boiler13CyclesLow16
30154
Boiler14CyclesHigh16
30155
Boiler14CyclesLow16
30156
Boiler15CyclesHigh16
30157
Boiler15CyclesLow16
30158
Boiler16CyclesHigh16
30159
Boiler16CyclesLow16
Figure 40
MODBUS — BoilerStatus Flags
Bit
Description
Valid Values/Range
0
Pilot Valve
0 = closed, 1 = open
1
Blower Running
0 = off, 1 = running
2
Ignition Alarm
0 = ok, 1 = alarm
3
Valve Alarm
0 = ok, 1 = alarm
4
High Limit
0 = ok, 1 = tripped
5
Air Prove Switch
0 = open, 1 = closed
6
RESERVED (FACTORY)
7
Software Operator
0 = off, 1 = on
8
Header Sensor not Detected
0 = detected, 1 = not detected
9
Supply Sensor not Detected
0 = detected, 1 = not detected
10
Return Sensor not Detected
0 = detected, 1 = not detected
11
Outside Sensor not Detected
0 = detected, 1 = not detected
12
System Pump
0 = off, 1 = on
13
Combustion Air Damper
0 = off, 1 = on
14
Master Boiler
0 = member, 1 = master
15
Boiler Detected (at this address)
0 = not detected, 1 = detected