78
Flue plugged.
Clean Flue.
Refer to
“top rectangular Flue.”
Water temperature not
being held in the 140 to
180 degree range
Consult Dealer.
Contact your
Local Dealer
.
thermometer
(temp gauge)
exceeds
212 degrees
Fahrenheit.
Furnace is not
boiling.
Low water level
Add water.
(Let Furnace cool first)
Refer to
“Water Level Maintenance.”
charcoal build-up
in rear of firebox.
Excessive ashes.
Remove ashes.
Refer to
“ash Management and ash
removal.”
Failure to rake ashes
periodically.
Rake ashes.
Refer to
“ash Management and ash
removal.”
Blower continues
to operate
and display
shows a higher
than setting
temperature.
Water level is low.
Add water.
Refer to
“Filling the Furnace initially
with Water.”
Defective Electronic
Controller.
Replace Electronic
Controller.
Refer to
“electrical (electronic
controller)”
Defective temperature
probe.
Replace temperature
probe.
Refer to
“electrical (temperature
Probe)”
too much smoke
comes out
firebox door while
loading.
Opening firebox door
when there is fuel still
inside.
Do not add so much
fuel all at one time.
Refer to
“Loading Wood into the
heatMOr™.”
PrOBLeM
cause
sOLutiOn
PrOceDure