UH8-RF V2 – Installation Manual

Description
The UH8-RF V2 is an 8 Zone central wiring centre for use with 

Heatmiser RF thermostats.
The UH8-RF V2 can be used to control any actuator or valve, which

requires a 230v AC signal to open. For mid position valves and those

requiring a closing signal, a changeover relay is required. The 

UH8-RF V2 also offers the ability to operate a boiler or other heat

source through a volt free output with changeover contacts, giving

you both a heat on signal and a heat off signal.
Additional outputs designed for use with hot water or underfloor

heating systems, are also included as standard. These are the pump

and valve outputs which would normally operate a manifold pump

or a manifold valve.
Any output which is not needed can be ignored.
When wiring directly to the heat source is not possible, a radio link is

provided to remotely enable a separate receiver, the RF-Switch.
Test switches are included for the installation engineer and further

options include creepage protection and pump delay.
Operation
Using the toggle switches, each channel used on this system can be 

configured for either a radiator zone or underfloor 

heating zone.
When the thermostat sends a signal for heating, the UH8-RF V2 will

provide a 230v AC output on the paired zone and also bring on the

boiler/other heat source output. At the same time the UH8-RF V2 can

send a radio signal to the RF-Switch. If the zone is configured as

an underfloor heating zone, the UH8-RF V2 will also start the pump and

valve outputs.

If an enable signal is received from a hot water time clock on the

system, only the H/W output will become active. This is a timed output,

which is normally fed to a cylinder thermostat, then to a valve, but

could also be used for towel rails. In either case the valve auxiliary

switch would operate the boiler/other heat source.
Other functions
Creepage
During hot weather the heating is not normally needed as often, this

means that valves and pumps that are not being used can seize and

refuse to operate. To prevent this, it is good practice to operate the

valve or pump once a day, the creepage function does this for you.
Once enabled the UH8-RF V2 will operate each valve or pump for 1

minute, if the outputs have not been operated by a thermostat,

within the preceding 24 hours. This function does not operate the

boiler output.
Pump Delay
Some valves or actuators can take more than a minute to open, if the

boiler and pump operate before the valve is open it can force a boiler

to go to lockout and stop operating. This function delays the operation

of the pump and boiler to give the actuators and valves time to open.

Summary of Contents for UH8-RF V2

Page 1: ...Model UH8 RF V2...

Page 2: ...ting the UH8 RF V2 will provide a 230v AC output on the paired zone and also bring on the boiler other heat source output At the same time the UH8 RF V2 can send a radio signal to the RF Switch If the...

Page 3: ...On the back of the UH8 RF V2 position the clip in the middle and slide down Points A and B locate in the corresponding holes and lock into place Locate the UH8 RF V2 onto the DIN rail from the top Pu...

Page 4: ...se the common and normally open connections Zones 1 8 Zones outputs are clearly marked L live out to actuator or valve N neutral to actuator or valve There are two connections live L and neutral N bot...

Page 5: ...on when the zone output is on 2 Light flashes when the zone is in pairing mode Button functions 1 Single press to manually turn output On Off 2 Hold down for 5 seconds to start pairing mode Indicator...

Page 6: ...pump and heat output ZONE 1 ZONE 2 ZONE 3 1 2 3 1 2 3 1 2 3 MAINS SUPPLY 3 AMP UFH PUMP MANIFOLD LIMIT STAT 1 L L N N ZONE 4 ZONE 4 1 2 3 230 VOLT PUMP N I S N I A M BOILER ENABLE N N ZONE L L N N ZON...

Page 7: ...ote Boiler enable Boost Repeater Extension Antenna EA1 Extension Antenna included EA1 DEW POINT RT1 SL Dew Point Sensor Flow Sensor L L N N ZONE 8 L L N N ZONE 7 L L NE 6 NO C NC NO C NC 1 2 DEW POINT...

Page 8: ...itch allows To enable creepage protection put switch 3 to the ON position Creepage Protection Dip Switch 3 Position 1 Zone output only When a thermostat is in demand the UH8 RF will activate the Zone...

Page 9: ...Model UH8 RF V2 System Configuration PLEASE COMPLETE DURING INSTALLATION UH8 RF V2 Title In Use ZoneType ZoneTitle Under Floor Radiator Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 HotWate...

Page 10: ...Notes Wiring Centre 10...

Page 11: ...Wiring Centre 10 Notes Model UH8 RF V2 11...

Page 12: ...9090 Or view technical specifications directly on our website www heatmiser com Twitter heatmiseruk Facebook facebook com thermostats Slimline RF neoAir RF Switch RF Switch V2 Heatmiser UK Ltd Units 1...

Reviews: