13 Installation settings
• To adjust the operational parameters:
• Press for more than 7 seconds on the button
to
access the confi guration menu. The screen displays "0".
• Holding in the button
until 35 is displayed, accesses the
service parameters.
• Press 4 times on the button
The screen displays "96".
This is the installer's password.
Code Installation Parameters
Unit
Description
Factory
setting
Modifi able
parameter
d.00 Maximum heating power
kW
Choose a value 24 > 8 to 18 and 28 > 9 to 24.
-
yes
d.01 Pump over-run time - heating
min
Choose a value between 2 and 60
5
yes
d.02 Blocking time for burner in heating mode (anti-cycle
time)
min
To prevent the burner frequently switching on and
off. The reactivation of the burner is electronically
blocked for a period that is determined each
time the burner stops. The burner blocking
time can be adapted to the usage conditions
for the heating.Installation and depends
on the temperature that is set for heating:
-at 80°C, the period is fi xed (2 minutes)
-at 10°C ,the period is adjustable: choose a value
between 2 and 60 minutes.
20
yes
d.18 Pump function
enum
Mode:
0 = With the burner
1 = Continuous with ambient temperature
2 = Continuous
1
yes
d.20 Maximum temperature setting for domestic hot water
°C
The recommended maximum temperature setting
for DHW is 60°C. Choose a value suitable for
your needs.
60
yes
d.34 Speed of fan
rpm
100 = Domestic Hot Water.
0 = Central Heating.
-
no
d.35 3 way valve position
%step Fan speed is displayed between 0 and 99.
Multiply the display value by 100.
-
-
d.36 Domestic hot water fl ow
l/min. Display domestic hot water fl ow.
-
no
d.40 Heating fl ow temperature
°C
Display the heating fl ow temperature.
-
no
d.41 Heating return temperature
°C
Display the heating return temperature.
-
no
d.67 Time remaining before the end of the anti-cycle in
heating mode.
min.
Display the time remaining before the end of the
anti-cycle
-
no
d.71 Maximum temperature setting for heating outlet
°C
Select a value between 50°C and 80°C.
75
yes
d.85 Minimum power setting for heating mode
kW
Minimum power setting
kW
yes
d.94 Reset the fault codes
true/
false
true/false
yes
Code Service Parameters
Unit Description
Factory
setting
Modifi able
parameter
d.08 Current state of the 230V room thermostat
-
230V room thermostat :
0 = open (no heating),
1 = closed (heating mode).
-
no
d.09 Flow temperature set point from external eBus control
°C
External eBus set value.
-
no
d.10 Heating pump status
-
0 = off
1 = on
-
no
d.16 Current state of the 24V room thermostat
°C
0 = open (no heating),
1 = closed (heating mode)
-
no
d.17 Flow or Return temperature monitoring
°C
Temperature regulation on fl ow (radiator) or return
(under-fl oor heating) temperature sensor.
0
yes
• Press on
to validate.
The screen displays a fl ashing
and alternating "d." and "00".
• Press on button
or
to access the parameter to modify.
• Press on button
to modify the value of the parameter
and select with the
or
keys.
• The parameter is changed after the screen fl ashes 3 times.
• To exit to display menu, press the
button for 3
seconds.