Heatilator IB75 Installation & Operating Instructions Manual Download Page 8

8

35048 Rev L

03/04

IB75 B-VENT GAS APPLIANCE

4.Chase/Termination Installation

Figure 8 and Table 1 specify minimum vent heights for

various pitched roofs.

These vent heights are necessary for safety and do

not  ensure  draft-free  operation.  Trees,  buildings,

adjoining roof lines, adverse conditions, etc. may create

a need for a taller vent should down drafting occur.

Figure 8

Vent Height for Vertical Termination

Roof Pitch

H (Min.) Ft.

Flat to 6/12 ................................................ 1.0

6/12 to 7/12 ............................................... 1.25

Over 7/12 to 8/12 ...................................... 1.5

Over 8/12 to 9/12 ...................................... 2.0

Over 9/12 to 10/12 .................................... 2.5

Over 10/12 to 11/12 .................................. 3.25

Over 11/12 to 12/12 .................................. 4.0

Over 12/12 to 14/12 .................................. 5.0

Over 14/12 to 16/12 .................................. 6.0

Over 16/12 to 18/12 .................................. 7.0

Over 18/12 to 20/12 .................................. 7.5

Over 20/12 to 21/12 .................................. 8.0

Table 1 - Vent Height

Note:

 

To ensure proper operation, verify all venting

and the termination are unobstructed.

6.Check the Vent System

Test the venting system periodically to assure proper

operation. This can be done with a match while the

appliance is operating.

Hold a lighted match at the top edge of the appliance

opening.  If  the  flames  and  smoke  remain  upright,

ventilation is acceptable. If the flames and smoke are

drawn  into  the  appliance,  this  means  ventilation  is

good. If the flames and smoke are forced away from

the appliance, this may indicate a ventilation blockage

or down draft resulting in gas spillage into your home.

If this occurs, turn off the appliance and do not burn it

until  it  has  been  inspected  by  a  qualified  service

person.

If you have installed optional doors, close the doors

and conduct the test following the same instructions

above. See Figure 9.

Figure 9 - Testing Ventilation

5.Automatic Damper

This  appliance  comes  with  a  thermally  activated

automatic damper device. When at room temperature,

the damper will have slight spring pressure keeping it

in  a  closed  position.  When  placed  in  a  heat  source

(i.e. when the appliance is turned on), the damper will

open as the thermally activated spring heats. Check

that  the  damper  blade  moves  freely  and  does  not

scrape  or  bind  on  any  of  the  damper  components.

While the appliance is in operation, visually check that

the  damper  opens.  It  will  take  approximately  four

minutes  for  the  spring  to  reach  normal  operating

temperature  and  the  damper  to  reach  a  fully  open

position.

Summary of Contents for IB75

Page 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas Do not try to light any appliance Do not touch any electrical...

Page 2: ...be required due to excessive lint from carpeting bedding materials etc It is imperative that the control compartment burners and circulating air passageways of the appliance be kept clean 4 This is a...

Page 3: ...ign and construction stage of the home If you desire to put an appliance in your basement we recommend that you consider a direct vent gas appliance Basements always have a significant negative air pr...

Page 4: ...leak check solution Note Minimum and maximum clearances must be main tained at all times Illustrations throughout these instruc tions reflect typical installations and are for design pur poses only Ac...

Page 5: ...cated in a room The IB75 may be installed directly on the floor or raised on a hearth These appliances are certified for installation in a bedroom or bed sitting room in the U S and Canada provided th...

Page 6: ...ncombustible material as necessary Secure the appliance by bending out the nailing flanges on each side of the appliance and nail to framing The nailing flanges have been positioned 1 2 in back from t...

Page 7: ...nt system Do not pack air spaces with insulation or other material Figure 6 Venting off the Top of the Appliance Figure 5 Vertical Termination Vent Lengths 3 Firestop Spacer Vent Installation Frame an...

Page 8: ...opening If the flames and smoke remain upright ventilation is acceptable If the flames and smoke are drawn into the appliance this means ventilation is good If the flames and smoke are forced away fro...

Page 9: ...educed When installing this appliance at an elevation above 4500 feet in Canada check with local authorities 2 Connect the Gas Line Open the control access panel as shown in Figure 10 This appliance i...

Page 10: ...m m 8 7 1 n i 0 7 0 G N e z i S e c i f i r O t n o r F m m 2 4 1 n i 6 5 0 r a e R m m 8 2 3 n i 9 2 1 WARNING This valve has been preset at the factory Altering settings may result in a fire hazard...

Page 11: ...lt AC transformer which requires the installation of the supplied JK9 Junction Box Kit It is highly recommended that the JK9 be installed at this time to avoid reconstruction The battery pack requires...

Page 12: ...nd high temperatures General Electric RTV103 Black or equivalent Rutland Inc Appliance Mortar 63 or equivalent A high temperature sealant 1 8 in wide minimum bead must be used to close off gaps betwee...

Page 13: ...vermiculite sprinkle it evenly over the area covered by the lava rock See Figures 15 16 It is not necessary to use the entire bag of lava rock or vermiculite Save the remaining amount for future use...

Page 14: ...or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Imm...

Page 15: ...ative that control compartments burners and circulating air passageways of the appliance be kept clean WARNING Keep the area near the appliance clear and free from combustible materials gasoline and o...

Page 16: ...6 4 n i h t i w d e n a e l c e b d l u o h s s r o o d s s a l G A s s e c o r p g n i r u t c a f u n a m e h t m o r f s l i o y b t f e l s t i s o p e d e v o m e r o t y r a s s e c e n e b y a...

Page 17: ...rect Operation of Doors WARNING Gas appliances equipped with doors should be operated only with doors fully open or doors fully closed If doors are left partially open gas and flame may be drawn out o...

Page 18: ...ss after initial 4 6 hours burning time This is to remove any film that develops from oils and log burn After initial cleaning clean as needed b Handle glass panel with care to avoid striking or scrat...

Page 19: ...e 24 Pull up on the assembly to remove it from the firebox and set it aside being careful not to damage any of the logs See Figure 25 4 To remove the back log remove three screws and carefully lift th...

Page 20: ...ENT GAS APPLIANCE N REPLACEMENT PARTS Replacement parts are available from your distributor dealer Gas Log Assembly Visit our Website at www heatilator com for a dealer distributor near you Valve Asse...

Page 21: ...6 1 6 7 7 4 3 t e k c a r B e v l a V 1 7 1 9 9 7 4 3 9 2 1 e c i f i r O 1 8 1 4 0 8 4 3 e t a l P e v l a V 1 9 1 7 0 0 3 0 0 4 t e k c a r B t o l i P 1 0 2 A 0 9 5 3 9 5 s s e n r a H e r i W 1 1...

Page 22: ...Control RCT MLT HTL Multi Function Remote Control SMART STAT HTL Remote Control with Thermostat Control SMART BATT HTL Battery operated Remote Control with Thermostat Control DCKVP Natural to Propane...

Page 23: ...0 Glass Cleaning 18 Condensation 2 16 Film 2 16 Glass Doors 17 H High Altitude Installation 9 High Limit Safety Switch 18 High Surface Temperatures 15 I Inspection 15 Insulation 7 Intermittent Pilot I...

Page 24: ...quate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than those spe...

Reviews: