Heatilator • I60 US-CAN • 4013-202 Rev F • 11/07
13
Risk of Smoke Spillage
Outside air inlet must be located to prevent blockage
from:
•
Leaves
•
Snow/ice
•
Other
debris
Blockage may cause combustion air starvation.
CAUTION
4
4
Installation of Fireplace
Fire Risk
Asphyxiation Risk
Do not draw outside combustion air from:
• Wall,
fl
oor or ceiling cavity.
• Enclosed space such as an attic or
garage.
• Close proximity to exhaust vents or
chimneys.
Fumes or odor may result.
WARNING
A. Install the Outside Air Kit
This
fi
replace will operate correctly only if adequate ventila-
tion is provided to allow proper draft to the
fi
replace system.
See Section 2.
The outside air kit is supplied (as an optional feature) with
this
fi
replace and its use is highly recommended to minimize
the effects of negative pressure within the structure. We
recommend you utilize the shortest duct run to optimize the
performance of the outside air kit. Cold air
fl
ow can be mini-
mized by putting a small dip in the duct creating a cold air
trap. This trap can also help prevent heat build-up and ex-
hausting out the intake due to the stack effect. The outside
air kit inlet should be positioned in a manner that will not al-
low snow, leaves, etc. to block the inlet. In some installations
the air duct may need to be run vertically. In such an instal-
lation, a 3 ft (.914 m) height difference must be maintained
from the top of the uppermost chimney section to the outside
combustion air inlet. See Figure 4.2.
See Figure 4.3 for proper placement of outside air inlet.
The outside air kit is installed on the left hand side of the
fi
replace. See Figure 4.4 for handle location/operation.
Sharp Edges
• Wear protective gloves and safety glasses
during installation.
CAUTION
Outside Air
Shield
Outside Air
Plate
Assembly
2 Wire Ties
Flexible Duct
(not supplied)
Figure 4.1 Outside Air Installation