19
HEATILATOR ECO-CHOICE
E. Through The Wall
Horizontal termination cap must be a minimum of 6 inches.
(152mm) from the wall. Approved for mobile home instal-
lations. Must use 3 or 4 inch (76-102mm) “L” or “PL” listed
pellet venting or Listed double wall pipe and an authorized
Outside Air Kit in mobile homes.
In Canada, where passage through a wall or partition of
combustible construction is desired, the installation shall
conform to CAN/CSA-B365
Figure 19.1
NOTICE:
Please note that while the minimum clearance
for the termination cap is 6 inches (152mm) there is the
possibly of soot build-up around the termination area. If
this occurs we suggest to move the termination further
away from the house to prevent it. The suggested mini-
mum is 12 inches.
Straight Out
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
Wall
Thimble
Horizontal
Termination
Cap
2 in.
(51mm)
Minimum
6 in.
(152mm)
Minimum
From Glass
45 Degree
Wall
Thimble
Illustration shows venting going in both directions.
Choose which one is best for your installation.
2 in. (51mm)
Minimum
2 in.
(51mm)
Minimum
6 in (152mm) Minimum
6 in (152mm)
Minimum
DO NOT DOWNWARD VENT.
The following will occur:
• The appliance will not vent properly
• Smoke spillage in the house
•
Excessive
sooting
CAUTION
Figure 19.2