Heatcraft H-IM-SCU Installation And Operation Manual Download Page 4

4

© 2015 Heatcraft Refrigeration Products, LLC

Figure 4. Pad Mount for Mobile or Deep Sump Application

Condensing Unit Rigging and Mounting

Rigging holes are provided on all units. Caution should be exercised when moving 
these units. To prevent damage to the unit housing during rigging, cables or chains 
used must be held apart by spacer bars. The mounting platform or base should be 
level and located so as to permit free access of supply air. 

Ground Mounting

Concrete slab raised six inches above ground level provides a suitable base. Raising 
the base above ground level provides some protection from ground water and wind 
blown matter. Before tightening mounting bolts, recheck level of unit. The unit should 
in all cases be located with a clear space in all directions that is at a minimum, equal 
to the height of the unit above the mounting surface. A condensing unit mounted in 
a corner formed by two walls, may result in discharge air recirculation with resulting 
loss of capacity.

Roof Mounting

Due to the weight of the units, a structural analysis by a qualified engineer may be 
required before mounting. Roof mounted units should be installed level on steel 
channels or an I-beam frame capable of supporting the weight of the unit. Vibration 
absorbing pads or springs should be installed between the condensing unit legs or 
frame and the roof mounting assembly.

Access

Sufficient access must provided to ensure future service of all major components is pos-
sible.  The screw compressor, as well as some of the compressors removable components 
are heavy enough to require additional lifting equipment for service.  Care must be taken 
during condensing unit placement to accommodate the use of service equipment for 
maintenance or repair. 

Pad Mounted Compressor

All units use pad mounted compressors. Check the compressor mounting bolts to 
insure they have not vibrated loose during shipment. See Figure 4.

Head Pressure Control

Head pressure control is managed by the microprocessor controller.  Fan manage-
ment is constantly monitored and adjusted by the controller to maintain the target 
head pressure.

a. Dual Valve System

The system employs an ORI (open on rise of inlet pressure) valve and an ORD 
(open on rise of differential pressure) valve. The high pressure discharge gas is 
introduced above the liquid in the receiver tank. The receiver discharge is regulated 
by the ORI valve.

Operation and Adjustment

Condensing units with dual valves require sufficient charge to partially flood the 
condenser during low ambient conditions.

Valve adjustment should be made with gauges connected to the discharge port of 
the compressor. Adjustments should be made during mild or low ambient conditions. 
Turning the valve stem “clockwise” on the ORI valve will increase the discharge 
pressure, while turning the valve stem “counterclockwise” will decrease the discharge 
pressure.

If adjustments are made during warm ambient conditions, it may not be possible to 
adjust the regulator valve as low as desired. Readjustment may be necessary once 
cooler conditions prevail.

The discharge pressure of the ORI valve must be adjusted to regulate the unit for 
proper operating conditions. Adjust the ORI valve shown on the following diagram to 
maintain a discharge pressure of 160 to 180 PSIG.“flooding” of the condenser with 
liquid refrigerant reduces the available condensing surface, holding the condensing 
pressure at the valve setting.

b. Ambient Fan Cycle Control

This is an automatic winter control method which will maintain a condensing pressure 
within reasonable limits by cycling fan motors in response to outside air temperature. 
The thermostat(s) should be field adjusted to shut off the fan when the condensing 
temperature is reduced to approximately 90

˚

F. Table 1 lists approximate settings for 

several system T.D.’s. These settings are approximate as they do not take into account 
variations in load.

Rubber

Oil Type

BITZER Compact Screws are available in both standard CSH models for medium and 
high temperature condensing applications. These compressors offer excellent part and 
full load efficiencies. 

A key aspect to utilizing these compressors to their fullest potential is specifying 
the correct oil for your refrigerant. CSH screws may use BSE 170 oil in a variety of 
refrigerants (R134a, R407C, R404A and R507A). 

Table 2. Refrigeration Oils

ISO 170 (880 SUS) POE oil
OIL CHANGE

As received, the POE lubricant will be clear or straw colored. After use, it may acquire 
a darker color. This does not indicate a problem as the darker color merely reflects the 
activity of the lubricant's protective additive.

BYPASS

REGULATOR

CHECK

VALVE

DRAIN

REGULATOR

STD. LIQUID

LINE OUTLET

RECEIVER

DIP TUBE

COMPRESSOR

AIR COOLED

CONDENSER

DISCHARGE

LINE

Washer

Compressor for
Mounting Foot

Summary of Contents for H-IM-SCU

Page 1: ...actices 5 Refrigeration Pipe Supports 5 Suction Lines 6 Liquid Lines 6 Unit Cooler Piping 6 Line Sizing Tables 7 9 Evacuation and Leak Detection 10 Refrigerant Charging Instructions 10 Field Wiring 10...

Page 2: ...above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLER s factory and no freight shall b...

Page 3: ...mum distance between units is the width of the largest unit If units are placed end to end the minimum distance between units is 4 feet Units in Pits The top of the unit should be level with the top o...

Page 4: ...ntroduced above the liquid in the receiver tank The receiver discharge is regulated by the ORI valve Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 5: ...he system as supplied by Heatcraft Refrigeration Products was thoroughly cleaned and dehydrated at the factory Foreign matter may enter the system by way of the evaporator to condensing unit piping Th...

Page 6: ...runs to provide superheat at the compressor Pipe size example Given 30 F Cooler with one system having 2 evaporators One condensing unit rated at 350 000 BTUH s 20 F SST R404A refrigerant Two evapora...

Page 7: ...0 09 0 13 1 2 R507 404A R407C 6 4 0 58 0 16 0 24 5 8 R507 404A R407C 10 3 0 93 0 25 0 35 7 8 R507 404A R407C 21 2 1 92 0 51 0 72 1 1 8 R507 404A R407C 36 1 3 27 0 86 1 24 1 3 8 R507 404A R407C 55 0 4...

Page 8: ...3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 72000 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1...

Page 9: ...8 1 5 8 1 5 8 1 5 8 1 5 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 120000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 150000 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1...

Page 10: ...er evacuation Do not turn off vacuum pump when connected to an evacuated system before closing shut off valve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is...

Page 11: ...n the condensing unit nameplate If high or low voltage is indicated notify the power company If amperage draw is excessive immediately determine the cause and take corrective action On three phase mot...

Page 12: ...ns to keep the condensing unit s within the control zone d If the supply air temperature is below the control zone and if the Supply Air Temp Rate of Change ROC is not indicating the supply air temper...

Page 13: ...correct the problem and reset the unit using the Lckout RST from the Menu on the MAGNUM s key pad 10 If the compressor relay output is turned on either by computer or manual the compressor safeties a...

Page 14: ...RATURE TEMPERATURE STATUS STATUS Page Up Page Down 09 55 CMP 1 45 54 CMP OFF READY 000 00 42 SST SSH SCT DSH 38 16 9 97 79 2 PG PG HH MM CIRCUIT LEV ENT CURRENT CONTROL STATE TIME IN CURRENT STATE SAT...

Page 15: ...ts menu option shows the first 4 Sensor Inputs Pressing the Page Down button shows the next 4 Relay Outputs ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down button shows the f...

Page 16: ...option shows the first 4 setpoints Selecting the Graphs menu option shows the following Continue pressing the Page Down or Page Up buttons to scroll through all the Alarm screens GRAPHS Selecting the...

Page 17: ...menu Selecting the Lckout RST menu option shows the following Pressing the down arrow shows the rest of the submenu options ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down bu...

Page 18: ...excess 3 Open valve 4 Check electrical circuit 5 Adjust 6 Clean Low discharge pressure 1 Faulty condenser temperature regulation 2 Suction shutoff valve partially closed 3 Insufficient refrigerant in...

Page 19: ...t option Press enter 1st SI and offset appears i e Suction 1 0 0 Scroll using increase decrease keys to find sensor to calibrated Press enter use the increase decrease keys to change calibration value...

Page 20: ...hat was installed cannot be initialized and therefore cannot be used Replace the Compact Flash card with one that works BATTERY FAILED Generated when Magnum is not getting power from the Battery User...

Page 21: ...lgorithm incorporates a number of safety checks based on setpoints preventing unsafe conditions that could potentially cause damage to the system When a safety trips the circuit will be in a SAFETY TR...

Page 22: ...CHECKED If the discharge temperature analog input rises above the value of the setpoint or the digital input turns ON for the time specified in the Time sec field the compressor will be Locked Out and...

Page 23: ...nections are secure tighten if necessary Check operation calibration of all fan cycle and defrost controls when used Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingl...

Page 24: ...5V GRD GRD 5V S1 5V 5V GRD GRD S1 S1 5V GRD 5V 5V S1 GRD GRD S1 5V 5V S1 GRD GRD S1 5V WHITE BLACK SHIELD TEMP 1 SHIELD BLK TRANSDUCER WHITE DISCHARGE 1 RED GRD M1 ANALOG T1 100 M2 ANALOG T1 500 M3 AN...

Page 25: ..._________________________________________________________________________________ _______________________________________________________________________________________ ______________________________...

Page 26: ...s should be obtained from your local InterLink wholesaler Replacement parts which are covered under the terms of the warranty statement on page 2 of this manual will be reimbursed for total part cost...

Reviews: