Heatcraft H-IM-SCU Installation And Operation Manual Download Page 10

10

© 2015 Heatcraft Refrigeration Products, LLC

Evacuation and Leak Detection

Due to the smaller molecule size of HFC’s, they will tend to leak more readily than 
CFC’s. Consequently, it is of the utmost importance that proper system evacuation and 
leak detection procedures be employed.

Manufacturer recommendation is a minimum of 500 micron evacuation. In addition, 
a vacuum decay test is strongly recommended to assure there is not a large 
pressure differential between the system and vacuum pump. Good evacuation 
processes include frequent vacuum pump oil changes and large diameter, short hose 
connections to both high and low sides of the system preferably using bronze braided 
hose. Leak detection can be carried out in the conventional manner. If HCFC or CFC 
tracer gas is used, care must be taken to completely remove all traces of the gas prior 
to introducing HFC’s.

Electronic leak detectors are now available that will sense HFC’s. This is considered 
preferable since it removes the possibility of chlorine remaining in the system after 
leak testing with HCFC’s and/or CFC’s. There is a view that even small quantities of 
chlorine may act as a catalyst encouraging copper plating and/or corrosion and should 
therefore be avoided.

Leak Testing

After all lines are connected, the entire system must be leak tested. The complete 
system should be pressurized to not more than 150 psig with refrigerant and 
dry nitrogen (or dry CO

2

). The use of an electronic type leak detector is highly 

recommended because of its greater sensitivity to small leaks. As a further check 
it is recommended that this pressure be held for a minimum of 12 hours and then 
rechecked. For a satisfactory installation, the system must be leak tight. 

Line Insulation

After the final leak test, refrigerant lines exposed to high ambient conditions should 
be insulated to reduce heat pickup and prevent the formation of flash gas in the liquid 
lines. Suction lines must always be insulated with 3/4" wall Armstrong “Armaflex” or 
equal. When required, Liquid lines should be insulated with 1/2 inch wall insulation or 
better. The insulation located in outdoor environments should be protected from UV 
exposure to prevent deterioration of insulating value.

Evacuation

A good, deep vacuum pump should be connected to both the low and high side 
evacuation valves with copper tube or high vacuum hoses (1/4" ID minimum). If the 
compressor has service valves, they should remain closed. A deep vacuum gauge 
capable of registering pressure in microns should be attached to the system for 
pressure readings. 

A shut off valve between the gauge connection and vacuum pump should be provided 
to allow the system pressure to be checked after evacuation. Do not turn off vacuum 
pump when connected to an evacuated system before closing shut off valve. 
The vacuum pump should be operated until a pressure of 1,500 microns absolute 
pressure is reached — at which time the vacuum should be broken with the 
refrigerant to be used in the system through a drier until the system pressure rises 
above “0” psig. 

Repeat this operation a second time. 

Open the compressor service valves and evacuate the entire system to 500 microns 
absolute pressure. Raise the pressure to 2 psig with the refrigerant and remove the 
vacuum pump.

Refrigerant Charging Instructions

1.  Install a liquid line drier in the refrigerant supply line between the  

 

service gauge and the liquid service port of the receiver. 

2.  This extra drier will insure that all refrigerant supplied to the  

 

 

system is clean and dry.

3.  When initially charging a system that is in a vacuum, liquid  

 

 

refrigerant can be added directly into the receiver tank.

4.  Check equipment catalog for refrigerant capacity. System  

 

 

refrigerant capacity is 90% of receiver capacity. Do not add more  

 

refrigerant than the data tag indicates, unless the line run exceeds  

 

25ft. Then, add additional refrigerant as per the chart on page 30.  

 

Weigh the refrigerant drum before charging so an accurate record  

 

can be kept of the weight of refrigerant put in the system.

5.  Start the system and finish charging until the sight glass indicates  

 

a full charge and the proper amount has been weighed in. If the    
refrigerant must be added to the system through the   

 

 

suction side of the compressor, charge in vapor form only. Liquid   

 

charging must be done in the high side only or with    

 

 

liquid metering devices to protect the compressor.

NOTE:

 

R-407c should be introduced into the system as a liquid.

Field Wiring

The field wiring should enter the areas as provided on the unit. The wiring diagram for 
each unit is located on the inside of the electrical panel door. All field wiring should 
be done in a professional manner and in accordance with all governing codes. Before 
operating unit, double check all wiring connections, including the factory terminals.

Factory connections can vibrate loose during shipment.

1.  The serial data tag on the unit is marked with the electrical characteristic  

 

for wiring the unit.

2.  Consult the wiring diagram in the unit cooler and in the condensing unit  

 

for proper connections. 

3.  Wire type should be of copper conductor only and of the proper    

 

size to handle the connected load.

4.  The unit must be grounded.

CAUTION:

 

Do not use the refrigeration compressor to evacuate the 

system. Do not start the compressor while it is in a vacuum. 

WARNING:

 

All wiring must be done in accordance with applicable

codes and local ordinances.

NOTE: 

Refrigerant used during evacuation cannot be vented. Reclaim all used 

refrigerant. EPA regulations are constantly being updated. Ensure your procedure 
follows correct regulations. 

Summary of Contents for H-IM-SCU

Page 1: ...actices 5 Refrigeration Pipe Supports 5 Suction Lines 6 Liquid Lines 6 Unit Cooler Piping 6 Line Sizing Tables 7 9 Evacuation and Leak Detection 10 Refrigerant Charging Instructions 10 Field Wiring 10...

Page 2: ...above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLER s factory and no freight shall b...

Page 3: ...mum distance between units is the width of the largest unit If units are placed end to end the minimum distance between units is 4 feet Units in Pits The top of the unit should be level with the top o...

Page 4: ...ntroduced above the liquid in the receiver tank The receiver discharge is regulated by the ORI valve Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 5: ...he system as supplied by Heatcraft Refrigeration Products was thoroughly cleaned and dehydrated at the factory Foreign matter may enter the system by way of the evaporator to condensing unit piping Th...

Page 6: ...runs to provide superheat at the compressor Pipe size example Given 30 F Cooler with one system having 2 evaporators One condensing unit rated at 350 000 BTUH s 20 F SST R404A refrigerant Two evapora...

Page 7: ...0 09 0 13 1 2 R507 404A R407C 6 4 0 58 0 16 0 24 5 8 R507 404A R407C 10 3 0 93 0 25 0 35 7 8 R507 404A R407C 21 2 1 92 0 51 0 72 1 1 8 R507 404A R407C 36 1 3 27 0 86 1 24 1 3 8 R507 404A R407C 55 0 4...

Page 8: ...3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 72000 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1...

Page 9: ...8 1 5 8 1 5 8 1 5 8 1 5 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 120000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 150000 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1...

Page 10: ...er evacuation Do not turn off vacuum pump when connected to an evacuated system before closing shut off valve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is...

Page 11: ...n the condensing unit nameplate If high or low voltage is indicated notify the power company If amperage draw is excessive immediately determine the cause and take corrective action On three phase mot...

Page 12: ...ns to keep the condensing unit s within the control zone d If the supply air temperature is below the control zone and if the Supply Air Temp Rate of Change ROC is not indicating the supply air temper...

Page 13: ...correct the problem and reset the unit using the Lckout RST from the Menu on the MAGNUM s key pad 10 If the compressor relay output is turned on either by computer or manual the compressor safeties a...

Page 14: ...RATURE TEMPERATURE STATUS STATUS Page Up Page Down 09 55 CMP 1 45 54 CMP OFF READY 000 00 42 SST SSH SCT DSH 38 16 9 97 79 2 PG PG HH MM CIRCUIT LEV ENT CURRENT CONTROL STATE TIME IN CURRENT STATE SAT...

Page 15: ...ts menu option shows the first 4 Sensor Inputs Pressing the Page Down button shows the next 4 Relay Outputs ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down button shows the f...

Page 16: ...option shows the first 4 setpoints Selecting the Graphs menu option shows the following Continue pressing the Page Down or Page Up buttons to scroll through all the Alarm screens GRAPHS Selecting the...

Page 17: ...menu Selecting the Lckout RST menu option shows the following Pressing the down arrow shows the rest of the submenu options ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down bu...

Page 18: ...excess 3 Open valve 4 Check electrical circuit 5 Adjust 6 Clean Low discharge pressure 1 Faulty condenser temperature regulation 2 Suction shutoff valve partially closed 3 Insufficient refrigerant in...

Page 19: ...t option Press enter 1st SI and offset appears i e Suction 1 0 0 Scroll using increase decrease keys to find sensor to calibrated Press enter use the increase decrease keys to change calibration value...

Page 20: ...hat was installed cannot be initialized and therefore cannot be used Replace the Compact Flash card with one that works BATTERY FAILED Generated when Magnum is not getting power from the Battery User...

Page 21: ...lgorithm incorporates a number of safety checks based on setpoints preventing unsafe conditions that could potentially cause damage to the system When a safety trips the circuit will be in a SAFETY TR...

Page 22: ...CHECKED If the discharge temperature analog input rises above the value of the setpoint or the digital input turns ON for the time specified in the Time sec field the compressor will be Locked Out and...

Page 23: ...nections are secure tighten if necessary Check operation calibration of all fan cycle and defrost controls when used Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingl...

Page 24: ...5V GRD GRD 5V S1 5V 5V GRD GRD S1 S1 5V GRD 5V 5V S1 GRD GRD S1 5V 5V S1 GRD GRD S1 5V WHITE BLACK SHIELD TEMP 1 SHIELD BLK TRANSDUCER WHITE DISCHARGE 1 RED GRD M1 ANALOG T1 100 M2 ANALOG T1 500 M3 AN...

Page 25: ..._________________________________________________________________________________ _______________________________________________________________________________________ ______________________________...

Page 26: ...s should be obtained from your local InterLink wholesaler Replacement parts which are covered under the terms of the warranty statement on page 2 of this manual will be reimbursed for total part cost...

Reviews: