Heatcraft H-IM-SCU Installation And Operation Manual Download Page 21

21

© 2015 Heatcraft Refrigeration Products, LLC

Magnum System Alarms

Configuration Alarms

These alarms indicate a problem with the configuration file in the system. The system is not operational and a new configuration must be transmitted to the unit 
through MCS-Connect.

  • INVALID CONFIG - Checksums are incorrect.
  • INVALID CFG VER - The version number of the configuration is invalid.
  • INVALID CFG TYPE – The configuration type does not match the software type.

MCS Local Network Alarms

These alarms indicate problems with the MCS local network:
  • LOST SI COMM #_ / LOST RO COMM #_ - Generated when communications to a Sensor Input or Relay Output board
     is lost. The number of the board will be displayed with the alarm. The system can be accessed but will be in a NO RUN- I/O LOST state.
  • MCS-STAT OFFLINE - The Magnum has lost communications to the MCS-STAT.
  • LOST IO SHUTDOWN - Generated when Magnum is running and there are no communications to one or more of the
    I/O boards. The system can be accessed but will be in a NO RUN- I/O LOST state.
  • LOST I/O RESTART - Generated when the Magnum does an automatic reset once I/O communications are restored.

Key Sensors Alarms

These alarms indicate a problem with a key sensor, it is either shorted or open. The alarm will contain ALARM followed by the
10-character name of the sensor. The following sensors related to the entire system are tested:
  • Leaving temperature: If failed, then Lock Out the system.
  • Returning temperature: If failed, then alarm only no Lock Out.
  • Ambient temperature: If failed, then alarm only no Lock Out.

The following compressor sensors are tested. If they fail, then that compressor only is locked out:
  • Suction pressure and temperature
  • Discharge pressure and temperature
  • Oil pressure and temperature
  • Motor temperature (if an analog input)

Emergency Stop Alarm

  • EMERGENCY STOP - Generated when the emergency stop switch has been turned on. The system can be accessed but is in a Lock Out state.

Setpoint Safety Alarms

The Magnum algorithm incorporates a number of safety checks, based on setpoints, preventing unsafe conditions that could
potentially cause damage to the system. When a safety trips, the circuit will be in a SAFETY TRIPPED state. The circuit will remain
in this state for the time in the ‘Safety Down Time (min)’ cell and then move to the CMP ANTICYCLE or CMP IS OFF state where
the compressor will be allowed to run again if required. If the same safety trip occurs again within the time in the‘Lockout Delay Hrs’ cell since the first trip, the 
circuit will be set to CMP LOCKED OUT state, which requires a manual reset to restart the compressor. If the lockout delay time is set to zero, the Magnum will 
generate a lockout condition the first time that the safety occurs.

Sensor Inputs Used With Magnum

  • Suction Pressure (Analog) Discharge
  • Pressure (Analog) Discharge
  • Temperature (Analog) Motor
  • Temperature (Digital) Motor Amps
  • (Analog)
  • Motor Fault (Digital)
  • Suction Temp (Analog Only) Oil Sump
  • Level (Digital Only)

Setpoint Safeties

For a safety trip to occur, both the Sensor Input and the associated setpoint must be active. If a safety trips, the alarm name will 
consist of the setpoint name plus additional identification such as point number, compressor number, or 30 second history leading
up to the trip if applicable.

NOTE:

  

Most safeties are checked only if the compressor is running, however if the safety is always checked it will be noted.

The following is a list of safeties that are incorporated in the standard algorithm control. These safeties are checked every second. For a system with multiple 
circuits, each one is tested individually. If a safety trip occurs, only that respective compressor will be affected, the others will continue to function normally.

Phase Loss Protection

Phase loss, as indicated by the phase loss monitor, will result in the entire system being Locked Off and a phase loss alarm will be generated. If setpoint #166 
is inactive, the Magnum will wait for 2 seconds before the Lock Out occurs. The alarm will be PHASE LOSS and no restart will be attempted. If setpoint #166 is 
active, the name of the setpoint will be in the message. Refer to section 13 setpoint #166.

Summary of Contents for H-IM-SCU

Page 1: ...actices 5 Refrigeration Pipe Supports 5 Suction Lines 6 Liquid Lines 6 Unit Cooler Piping 6 Line Sizing Tables 7 9 Evacuation and Leak Detection 10 Refrigerant Charging Instructions 10 Field Wiring 10...

Page 2: ...above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLER s factory and no freight shall b...

Page 3: ...mum distance between units is the width of the largest unit If units are placed end to end the minimum distance between units is 4 feet Units in Pits The top of the unit should be level with the top o...

Page 4: ...ntroduced above the liquid in the receiver tank The receiver discharge is regulated by the ORI valve Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 5: ...he system as supplied by Heatcraft Refrigeration Products was thoroughly cleaned and dehydrated at the factory Foreign matter may enter the system by way of the evaporator to condensing unit piping Th...

Page 6: ...runs to provide superheat at the compressor Pipe size example Given 30 F Cooler with one system having 2 evaporators One condensing unit rated at 350 000 BTUH s 20 F SST R404A refrigerant Two evapora...

Page 7: ...0 09 0 13 1 2 R507 404A R407C 6 4 0 58 0 16 0 24 5 8 R507 404A R407C 10 3 0 93 0 25 0 35 7 8 R507 404A R407C 21 2 1 92 0 51 0 72 1 1 8 R507 404A R407C 36 1 3 27 0 86 1 24 1 3 8 R507 404A R407C 55 0 4...

Page 8: ...3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 72000 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 7 8 1 1 8 1 1 8 1...

Page 9: ...8 1 5 8 1 5 8 1 5 8 1 5 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 120000 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 150000 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1...

Page 10: ...er evacuation Do not turn off vacuum pump when connected to an evacuated system before closing shut off valve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is...

Page 11: ...n the condensing unit nameplate If high or low voltage is indicated notify the power company If amperage draw is excessive immediately determine the cause and take corrective action On three phase mot...

Page 12: ...ns to keep the condensing unit s within the control zone d If the supply air temperature is below the control zone and if the Supply Air Temp Rate of Change ROC is not indicating the supply air temper...

Page 13: ...correct the problem and reset the unit using the Lckout RST from the Menu on the MAGNUM s key pad 10 If the compressor relay output is turned on either by computer or manual the compressor safeties a...

Page 14: ...RATURE TEMPERATURE STATUS STATUS Page Up Page Down 09 55 CMP 1 45 54 CMP OFF READY 000 00 42 SST SSH SCT DSH 38 16 9 97 79 2 PG PG HH MM CIRCUIT LEV ENT CURRENT CONTROL STATE TIME IN CURRENT STATE SAT...

Page 15: ...ts menu option shows the first 4 Sensor Inputs Pressing the Page Down button shows the next 4 Relay Outputs ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down button shows the f...

Page 16: ...option shows the first 4 setpoints Selecting the Graphs menu option shows the following Continue pressing the Page Down or Page Up buttons to scroll through all the Alarm screens GRAPHS Selecting the...

Page 17: ...menu Selecting the Lckout RST menu option shows the following Pressing the down arrow shows the rest of the submenu options ACTUAL DISPLAY GETTING STARTED MANUAL REVISION 2 4 Pressing the Page Down bu...

Page 18: ...excess 3 Open valve 4 Check electrical circuit 5 Adjust 6 Clean Low discharge pressure 1 Faulty condenser temperature regulation 2 Suction shutoff valve partially closed 3 Insufficient refrigerant in...

Page 19: ...t option Press enter 1st SI and offset appears i e Suction 1 0 0 Scroll using increase decrease keys to find sensor to calibrated Press enter use the increase decrease keys to change calibration value...

Page 20: ...hat was installed cannot be initialized and therefore cannot be used Replace the Compact Flash card with one that works BATTERY FAILED Generated when Magnum is not getting power from the Battery User...

Page 21: ...lgorithm incorporates a number of safety checks based on setpoints preventing unsafe conditions that could potentially cause damage to the system When a safety trips the circuit will be in a SAFETY TR...

Page 22: ...CHECKED If the discharge temperature analog input rises above the value of the setpoint or the digital input turns ON for the time specified in the Time sec field the compressor will be Locked Out and...

Page 23: ...nections are secure tighten if necessary Check operation calibration of all fan cycle and defrost controls when used Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingl...

Page 24: ...5V GRD GRD 5V S1 5V 5V GRD GRD S1 S1 5V GRD 5V 5V S1 GRD GRD S1 5V 5V S1 GRD GRD S1 5V WHITE BLACK SHIELD TEMP 1 SHIELD BLK TRANSDUCER WHITE DISCHARGE 1 RED GRD M1 ANALOG T1 100 M2 ANALOG T1 500 M3 AN...

Page 25: ..._________________________________________________________________________________ _______________________________________________________________________________________ ______________________________...

Page 26: ...s should be obtained from your local InterLink wholesaler Replacement parts which are covered under the terms of the warranty statement on page 2 of this manual will be reimbursed for total part cost...

Reviews: