7
Start-Up Operation
Single System With 1 Evaporator
• Check all wiring connections to be sure they are
correct and tight.
• On the condensing unit
-
Check the adjustable low pressure switch
setting on freezer units. Refer to H-IM-CU
(Available on website). On some condensing
units, the low pressure switch has a fixed
setting and cannot be adjusted.
• Turn power on
• On the evaporator
-
Use the “
PROGRAM REVIEW
” button to scroll
through settings.
-
Check “
rEF
” (Refrigerant Type). Factory defaults
are: Air Defrost R-404A, Electric Defrost R-404A.
Change to the refrigerant being used.
-
Check
“
bot
”
(Box Temperature). Factory
defaults are: air defrost 35°F and electric defrost
–10°F. Change to the desired temperature.
-
Review and change other settings if necessary
-
See procedures on page 10 for how to change
settings.
Start-Up Operation
Single System With Multiple Evaporators
• Check all wiring connections to be sure they are
correct and tight.
• On the condensing unit
-
Check the low pressure switch setting on
freezer units. Refer to H-IM-CU (Available on
website). On some condensing units, the low
pressure switch has a fixed setting and cannot
be adjusted.
• Turn power on.
• On the MASTER evaporator
-
DO NOT REMOVE the room sensor.
-
Use the “
PROGRAM REVIEW
” button
to scroll through settings.
-
Check “
rEF
” (Refrigerant Type). Factory defaults
are: air defrost R-404A, electric defrost R-404A.
Change to the refrigerant being used.
-
Check
“
bot
”
(Box Temperature). Factory
defaults are: air defrost 35°F and electric defrost
–10°F. Change to the desired temperature.
-
Review and change other setting if necessary.
-
See procedures on page 10 on how to change
settings.
• On the SLAVE evaporators.
- Each SLAVE Evaporator must be changed to
identify it as a SLAVE. Use the “
PROGRAM
REVIEW
” button to scroll until
“
SLA
”
appears,
then use the “SELECT” knob to select
“YES”
then press
“ENTER.”
-
DO NOT NEED TO REMOVE the Room
Sensor on any evaporator.
M
= Master Evaporator
S
= Slave Evaporator
M
S
S
S