d) 

Condensate Drain Line                            d)   

排水管

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

e) 

Refrigerant Distributor and Nozzle          e

)制冷剂分液器及节流环

 

 
 
 
 
 
 
 
 
 
 
 
 

f) 

TX Valve, Sensor Bulb and External Equalisation Line 

f

)热力膨胀阀

感温包及外平衡管

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 

Ensure that the installation complies with 
HACCP and/or relevant regulations for food 
safety, and the end user’s preferences when 
choosing copper, stainless steel or PVC 
material for condensate drain lines. For low 
temperature applications, proper insulation 
and heating cable shall be provided to 
prevent the drainpipe from freezing. Provide 
a minimum 300mm per meter pitch to 
condensate drain lines for proper drainage. 
Drain lines should be at least as large as the 
evaporator drain connection. All condensate 
drain lines must be trapped to prevent 
outdoor air and odours entering the 
refrigerated room, and must never be 
connected directly to the sewer system. All 
traps must be located in a warm ambient to 
prevent water from freezing. It is 
recommended that the drain line be kept to a 
minimum length within the refrigerated room. 

请确认排水管的安装符合食品的

HACCP

及相

应的安全规范,材料可选择铜管,不锈钢管或

PVC

管,根据客户而定。对低温应用工况,

需提供保温及加热丝以防止排水管结冰。推荐

1

300mm

的坡度正确安装排水管。排水

管的尺寸至少和冷风机的积水盘接头一样。所
有的凝结水排水管必须要安装

U

型弯以防止

外界空气及异味进入冷库,绝对禁止直接和排
污系统相连。所有

U

型弯置于温暖的环境以

防止结冰。建议排水管在冷库内的长度要尽可
能短。

 

To obtain the best performance of the 
evaporator, the distributor body shall be 
mounted vertically to ensure refrigerant liquid 
being distributed evenly to all the circuits. 
 
For each unit through the whole range of 
BOHN Heavy Duty Evaporators, a carefully 
selected Sporlan-type orifice will be factory-
fitted in the distributor based on your request 
of refrigerant type before delivering the 
completed unit to your preferred site. 

为保证冷风机达到最佳的制冷效果,分液器必
须竖直安装,确保制冷剂均匀地分配到各个制
冷回路中。

 

 
 

对于

BOHN 

工业型冷风机中每一个型号,在

发往客户指定的地点前,根据客户所采用的制
冷剂,我司已在工厂安装了和分液器配套的

Sporlan

孔板。

 

For best performance, the TX valve should 
be installed as close to the distributor as 
possible. 
 
Locate the TX valve sensor bulb on the 
horizontal section of suction line and close to 
the suction header. For a satisfactory TX 
valve operation, good thermal contact 
between the sensor bulb and the suction line 
is essential. Follow TX valve manufacturers 
recommendations when positioning TX valve 
and sensor bulb. Incorrect installation may 
result in poor evaporator performance. 
 
The external equalisation line should be used 
to link the TX valve external equalisation port 
and the suction line, near the suction header. 
A ¼” tube brazed to the suction line is 
supplied for that purpose. 

为了达到最佳的制冷效果,热力膨胀阀应尽可
能安装在离分液器近的位置。

 

 
 

将热力膨胀阀的感温包放置在吸气管的水平位
置,并且离吸气集管比较近的位置。为了达到
良好的运行效果,必须保证感温包和吸气管之
间达到良好的热接触。热力膨胀阀及感温包的
放置请遵循生产厂家的指示。不正确的安装会
导致制冷效果变差。

 

 
 
 

外平衡管用于连接热力膨胀阀的外平衡口和吸
气集管附近的吸气管。连接到吸气管的

1/4

寸铜管就是所说的外平衡管。

 

Summary of Contents for BOHN

Page 1: ...nd Clearance pg 3 Installation Instructions pg 4 a Lifting of Unit pg 4 b Unpacking of Unit pg 4 c Mounting the Unit pg 4 d Condensate Drain Line pg 5 e Refrigerant Distributor and Nozzle pg 5 f TX Va...

Page 2: ...Defrost Guidelines pg 7 a Defrost Termination Requirements pg 7 b Control Setting Guidelines pg 8 Routine Maintenance of Unit pg 8 General Decommissioning Guide pg 9 Material Safety Data Sheets M S D...

Page 3: ...l if it is inhaled and or makes contact with exposed skin Refrigerants used in this equipment are controlled substances and must be used and recovered responsibly It is against the law to deliberately...

Page 4: ...refrigerants For other refrigerants please refer to sales data sheet for capacity variations Low temperature range evaporators Kirby KHDF series are designed at 24 C SST and 6 KTD to suit room temper...

Page 5: ...1 C is preferred placement C D S2 S1 S2 S2 S1 S2 D is an alternative for the same reason as B D B Where one side of wall mounting will not accommodate all required units or air throw distance must be...

Page 6: ...ly with HACCP and or relevant regulations for food safety the area above the evaporator must be sealed or exposed in such a way to facilitate hand cleaning without the use of tools So depending on the...

Page 7: ...igerated room HACCP PVC 1 300mm U U To obtain the best performance of the evaporator the distributor body shall be mounted vertically to ensure refrigerant liquid being distributed evenly to all the c...

Page 8: ...e shall be taken during installation of the piping to prevent entrance of foreign matter or moisture by minimising the time that the piping is uncapped The interconnecting refrigeration pipe size is n...

Page 9: ...eets for all the information regarding voltage and current for fan motors and element heaters During field wiring fan motors shall be wired up in star connection After electrical installation units sh...

Page 10: ...rier will ensure all refrigerant supplied to the refrigeration system is clean and dry The sight glass is a useful device to ensure sufficient refrigerant is supplied to the refrigeration system Refri...

Page 11: ...avy Load represents the nominal working period of each day 3 X 12 20 Defrost time for average loads should be approx 20 25 minutes including drainage Time will vary with varying degrees of ice build u...

Page 12: ...iven as a guide During the commissioning this data should be used as a reference initially It is then necessary to fine tune the control settings to achieve the satisfactory defrost results The above...

Page 13: ...re designed to have low service maintenance requirements Based on normal operation conditions and working environment a service maintenance schedule shall be established after the successful completio...

Page 14: ...rost completely Look for abnormal accumulation of ice patterns and adjust the defrost cycles accordingly Check the superheat and adjust TX valve accordingly All power must be disconnected before clean...

Page 15: ...in a potential personal injury hazard Cut and solder seal the refrigeration liquid line and suction line pipe connections Remove the evaporator from its mounting place Adequate support must be provid...

Page 16: ...to providing safe products and protecting the environment by complying with all applicable national laws and regulations governing environmental protection New and used refrigerants cannot be vented...

Page 17: ...ED ALLOW 1000 MM MIN FOR AIRFLOW REMOVABLE OPENING ACCESS DOOR AIRFLOW LABEL CEILING MOUNTED ALLOW 600 MM MIN FOR AIRFLOW FOOT MOUNTED ALLOW 1000 MM MIN FOR AIRFLOW ALLOW 520 MM MIN FOR ACCESS PANEL O...

Page 18: ...2 IF PRESENT 3 Ph FAN MOTOR 3 IF PRESENT FUSE OR CIRCUIT BREAKER 415 V 3 Ph 50 Hz ISOLATION SWITCH BLACK BROWN BLUE G Y W2 U1 U2 V1 V2 W1 W2 U1 U2 V1 V2 W1 3 Ph FAN MOTOR 1 3 Ph FAN MOTOR 2 IF PRESEN...

Page 19: ...tion by customer L1 COIL HEATER 1 WAGO TERMINALS 1 N BLACK COIL HEATER 2 2 BLACK COIL HEATER 3 3 BLACK TRAY HEATER BLACK 4 L2 L3 COIL HEATER 4 BLACK 5 6 7 BLACK BLACK BLACK BLACK BLACK IF PRESENT 8 E...

Page 20: ...20070206 20 of 20...

Reviews: