a)  Defrost Termination Requirements        a)  

除霜终止要求

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Each column represents a 3-hour period 
during the day. An X indicates the hour that a 
defrost should commence. “Heavy Load” 
represents the nominal ‘working period’ of 
each day. 

每列代表了每天时段中的

3

个小时。

X

显示了

除霜应该开始的时间。

"

重负荷

"

显示的是通常

意义上每天的“工作时段”。

 

 

 

温度终止—温度终止的设定主要根据除霜的频
率和结霜的状况,另外还取决于温度传感器

/

温度开关的位置。如果使用的是电子除霜控制
器,对于每个安装环境下的冷风机,其温度终
止的设定点必须单独确定,设定点应不低于

 

12

 

切断。温度传感器的位置应根据各个不

同的安装环境进行优化摆放。将传感器放置于
盘管上时通常需要更高的设置点,一般为

 20

 

或者更高。

 

 
 
 
 
 
 
 

压力终止—可采用多种方式用于除霜。不论采
用何种方式,必须注意翅片表面的温度总是比
制冷剂饱和压力对应的温度要低,应此,必须
考虑在设定压力控制时,制冷剂的温度设定要
高点。请参看下面的表。西克制冷不推荐通过
压力来控制风机延时,因为在采用热力膨胀阀
的系统中,当风机停止时,除霜结束后系统迅
速进入低压状态。对风机延时控制上,建议对
采用压力中止的除霜方式基础上采用时钟。

 

 
 
 
 
 
 

 
 

电加热丝热保护—西克生产的冷风机标准产品
中不带电加热丝热保护装置。客户负责安装合
适的该保护装置以防止在控制器和传感器失灵
的情况下,由于过高的温度和压力引起的冷风
机及周围环境的过热。

 

 

Defrost time for average loads should be 
approx. 20 - 25 minutes including drainage.  
Time will vary with varying degrees of ice 
build up. 
 
Time Termination – should be set to ensure 
complete defrost at the heaviest load 
condition. Typically allow 25 - 30 minutes 
with safety reset at 35 minutes. 

对于正常负荷的系统来说,平均的除霜时间大
约为

20-25

分钟(包括滴水时间)。这个除霜

时间将随着结霜的程度有所变化。

 

 

时间终止—时间终止是为了能够保证在最重负
荷的情况下仍然能够除尽盘管上的霜。通常的
时间设定为

25 - 30

分钟,安全关断时间为

35

分钟。

Summary of Contents for BOHN

Page 1: ...nd Clearance pg 3 Installation Instructions pg 4 a Lifting of Unit pg 4 b Unpacking of Unit pg 4 c Mounting the Unit pg 4 d Condensate Drain Line pg 5 e Refrigerant Distributor and Nozzle pg 5 f TX Va...

Page 2: ...Defrost Guidelines pg 7 a Defrost Termination Requirements pg 7 b Control Setting Guidelines pg 8 Routine Maintenance of Unit pg 8 General Decommissioning Guide pg 9 Material Safety Data Sheets M S D...

Page 3: ...l if it is inhaled and or makes contact with exposed skin Refrigerants used in this equipment are controlled substances and must be used and recovered responsibly It is against the law to deliberately...

Page 4: ...refrigerants For other refrigerants please refer to sales data sheet for capacity variations Low temperature range evaporators Kirby KHDF series are designed at 24 C SST and 6 KTD to suit room temper...

Page 5: ...1 C is preferred placement C D S2 S1 S2 S2 S1 S2 D is an alternative for the same reason as B D B Where one side of wall mounting will not accommodate all required units or air throw distance must be...

Page 6: ...ly with HACCP and or relevant regulations for food safety the area above the evaporator must be sealed or exposed in such a way to facilitate hand cleaning without the use of tools So depending on the...

Page 7: ...igerated room HACCP PVC 1 300mm U U To obtain the best performance of the evaporator the distributor body shall be mounted vertically to ensure refrigerant liquid being distributed evenly to all the c...

Page 8: ...e shall be taken during installation of the piping to prevent entrance of foreign matter or moisture by minimising the time that the piping is uncapped The interconnecting refrigeration pipe size is n...

Page 9: ...eets for all the information regarding voltage and current for fan motors and element heaters During field wiring fan motors shall be wired up in star connection After electrical installation units sh...

Page 10: ...rier will ensure all refrigerant supplied to the refrigeration system is clean and dry The sight glass is a useful device to ensure sufficient refrigerant is supplied to the refrigeration system Refri...

Page 11: ...avy Load represents the nominal working period of each day 3 X 12 20 Defrost time for average loads should be approx 20 25 minutes including drainage Time will vary with varying degrees of ice build u...

Page 12: ...iven as a guide During the commissioning this data should be used as a reference initially It is then necessary to fine tune the control settings to achieve the satisfactory defrost results The above...

Page 13: ...re designed to have low service maintenance requirements Based on normal operation conditions and working environment a service maintenance schedule shall be established after the successful completio...

Page 14: ...rost completely Look for abnormal accumulation of ice patterns and adjust the defrost cycles accordingly Check the superheat and adjust TX valve accordingly All power must be disconnected before clean...

Page 15: ...in a potential personal injury hazard Cut and solder seal the refrigeration liquid line and suction line pipe connections Remove the evaporator from its mounting place Adequate support must be provid...

Page 16: ...to providing safe products and protecting the environment by complying with all applicable national laws and regulations governing environmental protection New and used refrigerants cannot be vented...

Page 17: ...ED ALLOW 1000 MM MIN FOR AIRFLOW REMOVABLE OPENING ACCESS DOOR AIRFLOW LABEL CEILING MOUNTED ALLOW 600 MM MIN FOR AIRFLOW FOOT MOUNTED ALLOW 1000 MM MIN FOR AIRFLOW ALLOW 520 MM MIN FOR ACCESS PANEL O...

Page 18: ...2 IF PRESENT 3 Ph FAN MOTOR 3 IF PRESENT FUSE OR CIRCUIT BREAKER 415 V 3 Ph 50 Hz ISOLATION SWITCH BLACK BROWN BLUE G Y W2 U1 U2 V1 V2 W1 W2 U1 U2 V1 V2 W1 3 Ph FAN MOTOR 1 3 Ph FAN MOTOR 2 IF PRESEN...

Page 19: ...tion by customer L1 COIL HEATER 1 WAGO TERMINALS 1 N BLACK COIL HEATER 2 2 BLACK COIL HEATER 3 3 BLACK TRAY HEATER BLACK 4 L2 L3 COIL HEATER 4 BLACK 5 6 7 BLACK BLACK BLACK BLACK BLACK IF PRESENT 8 E...

Page 20: ...20070206 20 of 20...

Reviews: