Mechanical Specification
General
Provide a air handler of sound materials construction and design. Frame mem-
bers, structural bases and all casings parts are fabricated from mill galvanized
steel. The table on page 39 specifies the metal gauge of each component. Ex-
terior panels are to be a minimum of 16 gauge galvanized steel. Access doors
in the fan section provide complete access to motor(s), belts, drive(s) and fan.
Removable casing panels in the coil section permit removal of coil from either
side. Fan housings extend from the fan section panel for duct connections.
Air Conditioning Models - VCS, HCS, HCL
Provide a air conditioning air handler to meet cooling and condensate require-
ments. The air handler shall have standard insulation in both the fan and cool-
ing coil sections with a drain pan as described below.
Cooling Coil Sections
Provide a air handler with a readily accessible and drainable coil section. Coil
sections have removable panels on each side. Drain pan is of double wall con-
struction with insulation sandwiched between the metal pans. Two (2) 1-1/4"
FPT drain connections are supplied. These drain connections are furnished on
each side of the drain pan on all sizes. Drain pans are #16 gauge galvanized
steel. Provide standard insulation for the cooling coil section as described
below.
Insulation
Provide the air handler with adequate insulation for air conditioning require-
ments. Standard Insulation is 1"-3/4# (1 inch thick, 3/4 lbs per cubic foot)
fiberglass. Insulation is mat faced to prevent erosion. It meets the NFPA 90
Standard for flame spread and smoke generation.
Heating And Ventilating Models - HD
Provide a air handler to meet heating or ventilating (but no cooling) duty
requirements. The standard heating unit includes 1 or 2 row heating sections.
Furnish deeper coil sections for 3, 4, or 6 row coils. Do not insulate the fan or
coil sections on these units.
Fans
Provide a air handler with fan section that meets air flow requirements. All
units have been certified as complying with ARI Standard 430. All units have a
single fan design (either forward curved or airfoil). The fans are statically and
dynamically balanced in fan section before the unit leaves the factory. Fans and
shafts operate well below the first critical speed. Fan bearings are ball bearing
type selected for 200,000 hour average life. Low pressure LF fans - Sizes 03
through 12 have lifetime lubricated, rubber mounted, cartridge bearings. Unit
sizes 14 through 75 have extended lube lines to the outside casing of the air
handler on drive side.
Coils
Provide water heating, water cooling, steam heating, and direct expansion coils
with ARI certification. All coils shall be of cartridge type, coils removable
from either side of casing. Direct expansion coils are to be aluminum ripple
corrugated plate fins on the staggered copper tubes. Fins shall have belled
collars and shall be bonded to tubes by mechanical expansion. Maximum
working pressure shall be 250 psig at 300°F. Coil shall be submerged in water
for testing. Direct expansion coils shall be provided with pressure-type brass
distributors with solder-type connections. All coils shall have a minimum of___
distributors, charged with dry air. Tubing for coils shall be copper with 1/2 or
5/8 inch outside diameters. Coils shall have suction and discharge connections
on the same end. Heatcraft coil performance data is certified as complying with
ARI Standard 410.
Filter Sections
Flat - Provide the air handler with an accessible flat filter section. Flat filter
sections for 2 and 4 inch filters are available on all sizes. Access doors are
furnished on both sides.
High Capacity - Provide the air handler with an accessible high capacity filter
section. High capacity filter sections are for 2 inch filters. High capacity filter
sections have one large door on each side.
High Efficiency - Provide the air handler with a high or a medium efficiency
filter section. Units are constructed of 16 gauge galvanized steel. Fully gasket-
ed doors are standard on each side of housing and units are fitted with positive
pressure trip lock latches that assures a tight seal. Both 2 inch prefilter and one
inch final filter tracks are extruded aluminum combined with reinforced nylon
pile seal to create a corrosion resistant seal.
Economizer Section
Provide the air handler with an economizer with inlets options at the back,
bottom, and top of the section. Economizer damper casing and blades shall be
not less than 16 U.S. gauge galvanized steel. Each blade shall be die-formed,
multi-break and not exceed 49 inches in length. Blades are to be mounted to
a single square one half inch rod, to prevent linkage slip, extending the full
length of the damper casing.
Face and Bypass Section
Dampers are opposed blade type. Shafts rotate in porous bronze bearings.
Access Section
Access sections have two hinged and latched doors, for all unit sizes. Access
sections are not insulated as standard.
Visit our website at www.heatcraftrpd.com for technical literature online.