15
SST = Saturated Suction Temperature
All coils have single refrigerant distributors unless noted as below:
MBH = BTU per Hour in Thousands
^ These selections require two circuits.
Sens. = Sensible Capacity
^^ These selections require three circuits.
Face Area in square feet
* These selections require four circuits.
** To estimate performance of coils at other than 10 FPI or at other air speeds or with other refrigerant or air temperatures see page 21,
or call your representative. With your representative, you can have specific computer selected coils rated for your job conditions.
CFM
Coil
MBH - 4 ROWS
MBH - 6 ROWS
Unit
Std
Face 35°F. SST 40°F. SST 45°F. SST 35°F. SST 40°F. SST 45°F. SST
Size
Air
Area
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
03
1500
3.00
61
42
48
36
36
31
74
49
61
43
48
37
06
2845
5.69
110
77
85
66
62
57
143
94
116
82
88
70
08
3750
7.50
152
106
127
93
98
82
187
123
151
107
117
92
10
4690
9.38
189
132
153
116
122
102
236
155
194
136
149
117
12
5844
11.69
242
167
192
143
142
123
291
193
243
170
189
147
14
6875
13.75
288
197
233
173
175
148
334
221
281
198
224
173
18
8750
17.50
367
251
296
221
223
188
442
291
360
251
285
220
20
9625
19.25
394
270
329
245
256
213
486
320
402
281
312
240
26
12750
25.50
531
366
419
313
332
278
641
425
535
374
415
323
34
17000
34.00
708^
488
559^
418
442
371
855
567
713^
498
553
430
41
20188
40.38
840^
580
664^
496
525
441
1016
673
846^
592
657
511
50
24750
49.50
1037^
706
826^
615
634^
532
1242*
820
1036^
726
811^
622
65
32292
64.58
1364^
927
1105^
814
832^
704
1641* 1081
1339*
938
1059^
813
75
37458
74.92
1582^ 1075 1282^
944
966^
817
1904* 1254
1553*
1088 1229^
943
Table 4
Supermarket
Air Conditioning
1/2" tube, entering air at 75°F. DB and 63°F. WB**
1/2" tube, direct expansion, cooling capacities
10 FPI**, large coils, 500 FPM**
CFM
Coil
MBH - 4 ROWS
MBH - 6 ROWS
Unit
Std
Face 35°F. SST 40°F. SST 45°F. SST 35°F. SST 40°F. SST 45°F. SST
Size
Air
Area
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
03
1565
3.13
57
39
44
34
32
29
72
48
60
42
46
36
06
2880
5.76
108
73
88
65
69
56
133
88
111
78
86
67
08
3905
7.81
145
99
121
88
92
76
182
119
151
106
117
91
10
4885
9.77
184
125
149
110
117
97
228
150
187
132
147
115
12
6200
12.40
234
159
192
139
147
121
292
191
238
168
186
144
14
7290
14.58
276
187
227
164
174
145
341
224
284
199
218
171
18
8855
17.71
335
227
276
199
211
176
414^
273
345
241
267
208
20
10025
20.05
378
254
314
227
240
196
472
312
391
272
302
233
26
13280
26.56
505
342
413
298
320
261
628^
411
513^
361
402
311
34
16825
33.65
640^
434
523^
378
405
330
796^
520
649^
457
510^
394
41
20365
40.73
775^
525
633^
457
490
403
963^^
630
786^^
553
617^
477
50
25313
50.63
962^
645
793^
573
603^
500
1199*
787
984*
984
764^
593
65
32290
64.58
1312^
820
1011^
736
778^
640
1520*
992
1265*
880
978*
758
75
37675
75.35
1415*
957
1180*
859
908*
747
1773* 1158
1476*
1027 1141*
885
Table 5
Supermarket
Air Conditioning
5/8" tube, entering air at 75°F. DB and 63°F. WB**
5/8 "tube, direct expansion, cooling capacities
10 FPI**, large coils, 500 FPM**
Air Handler Perfromance- Direct Expansion