background image

6

Mineral Oils 

 

The BR and Scroll compressors use Sontex 200, a “white oil”. 

This oil is not suitable for low temperature applications nor is 

it available through the normal refrigeration wholesalers. For 

field “top-off” the use of 3GS or equivalent, or Zerol 200TD 

is permissible, as long as at least 50% of the total oil charge 

remains Sontex 200. 

 

Suniso 3GS, Texaco WF32 and Calumet R015 (yellow oils) are 

available through normal refrigeration wholesalers. These oils 

are compatible if mixed and can be used on both high and low 

temperature systems. 

 

Polyol Ester Lubricants

The Mobil EAL ARCTIC 22 CC is the preferred Polyol ester due to 

unique additives included in this lubricant. ICI Emkarate RL 32S is 

an acceptable Polyol ester lubricant approved for use when Mobil 

is not available. These POEʼs 

must

 be used if HFC refrigerants are 

used in the system. They are also acceptable for use with any

of the traditional refrigerants or interim blends and are 

compatible with mineral oils. They can therefore be mixed 

with mineral oils when used in systems with CFC or HCFC 

refrigerants. These lubricants are compatible with one another 

and can be mixed. 

 

Alkyl Benzenes

Zerol 200TD is an alkyl benzene (AB) lubricant. Copeland 

recommends this lubricant for use as a mixture with mineral oil 

(MO) when using the interim blends such as R-401A, R-401B 

and R-402A (MP39, MP66 and HP80). A minimum of 50% AB is 

required in these mixtures to assure proper oil return.
Shell MS 2212 is a 70/30 mixture of AB/MO. If this lubricant is 

used in a retrofit situation virtually all of the existing MO must be 

drained prior to refilling with the MS 2212 to assure a minimum 

50% AB content.

Table 3. Refrigeration Oils

Refrigeration Oils*

With the changes that have taken place in our industry due to 

the CFC issue, we have reevaluated our lubricants to ensure 

compatibility with the new HFC refrigerants and HCFC interim 

blends offered by several chemical producers. As a secondary 

criteria, it is also desirable that any new lubricant be compatible 

with the traditional refrigerants such as CFC-12, HCFC-22 or 

R502. This “backward compatibility” has been achieved with the 

introduction of the Polyol ester lubricants.
Table 3 below summarizes which oils/lubricants are approved 

for use in Copeland compressors:

Polyol Ester Lubricants

Hygroscopicity

Ester lubricants (POE) have the characteristic of quickly 

absorbing moisture from the ambient surroundings. This is 

shown graphically in Figure 3 where it can be seen that such 

lubricants absorb moisture faster and in greater quantity than 

conventional mineral oils. Since moisture levels greater than 

100 ppm will results in system corrosion and ultimate failure, it 

is imperative that compressors, components, containers and the 

entire system be kept sealed as much as possible. Lubricants 

will be packaged in specially designed, sealed containers. 

After opening, all the lubricant in a container should be used at 

once since it will readily absorb moisture if left exposed to the 

ambient. Any unused lubricant should be properly disposed of. 

Similarly, work on systems and compressors must be carried 

out with the open time as short as possible. Leaving the system 

or compressor open during breaks or overnight 

MUST BE 

AVOIDED!

Color

As received, the POE lubricant will be clear or straw colored. 

After use, it may acquire a darker color. This does not indicate 

a problem as the darker color merely reflects the activity of the 

lubricantʼ s protective additive.

Oil Level

During Copelandʼ s testing of Polyol ester oil, it was found that 

this lubricant exhibits a greater tendency to introduce oil into the 

cylinder during flooded start conditions. If allowed to continue, 

this condition will cause mechanical failure of the compressor.
A crankcase heater is required with condensing units and it 

must be turned on several hours before start-up.
Oil level must not exceed 1/4 sight glass.

Mineral Oil

Figure 3.

 

 

 

Interims 

HFCʼs

 

 

Traditional Refrigerants R401A, R401B, R402A 

HFC-134a,

 

Refrigeration Oils 

HCFC-22 

(MP-39, MP-66, HP-80) 

R404A, R507

 POEʼs

 

Mobil EAL ARCTIC 22 CC 

P

 

ICI (Virginia KMP) EMKARATE RL 32CF 

P

 

Suniso 3GS 

PM

 Mineral

 

Texaco WF32 

PM 

NOT

 

Oils

 

Calumet RO15 (Witco) 

PM 

ACCEPTABLE

 

Sontex 200-LT (White Oil) 

(BR & Scroll Only)

 

Witco LP-200 

P

 

 

A/B

 

Zerol 200TD 

AM 

PM 

NOT

 

Soltex Type AB-200 

 

PM 

ACCEPTABLE

 P = Preferred Lubricant Choice A = Acceptable Alternative M = Mixture of Mineral Oil and Alkyl Benzene (AB) with minimum 50% AB.

* (Reprinted with permission from Copeland)

Summary of Contents for H-IM-FL1A

Page 1: ...riers Sight Glasses 5 Refrigerant Oils 6 Phase Loss Monitor 7 Recommended Refrigerant Piping Practices 7 Refrigeration Pipe Supports 7 Suction Lines 8 Suction Line Risers 8 Liquid Lines 8 Evacuation and Leak Detection 11 Refrigerant Charging Instructions 12 Field Wiring 12 Check Out and Start Up 12 Operational Check Out 13 System Balancing Compressor Superheat 13 System Troubleshooting Guide 14 Pr...

Page 2: ...turerʼs recommendations or if the serial number has been altered defaced or removed MOTOR COMPRESSORS Motor compressors furnished by SELLER are subject to the standard warranty terms set forth above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLERʼs factory and no freight shall be allow...

Page 3: ...d Location Requirements for Air Cooled Condensing Units and Remote Condensers Units in Pits The top of the unit should be level with the top of the pit and side distance increased to 2W If the top of the unit is not level with the top of pit discharge cones or stacks must be used to raise discharge air to the top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free a...

Page 4: ...ess Provide adequate space at the compressor end of the unit for servicing Provide adequate space on the connection side to permit service of components Spring Mounted Compressor Compressors are secured rigidly to make sure there is no transit damage Before operating the unit it is necessary to follow these steps a Remove the upper nuts and washers b Discard the shipping spacers c Install the neop...

Page 5: ... drier The sight glass is designed to give a visual indication of moisture content in the system Generally it requires no field service However in cases of extreme acid formation in a system after a compressor burnout the acid may damage the sensing element or etch the glass This would require that the sight glass be replaced along with the liquid line drier after any compressor motor burnout CAUTI...

Page 6: ...introduction of the Polyol ester lubricants Table 3 below summarizes which oils lubricants are approved for use in Copeland compressors Polyol Ester Lubricants Hygroscopicity Ester lubricants POE have the characteristic of quickly absorbing moisture from the ambient surroundings This is shown graphically in Figure 3 where it can be seen that such lubricants absorb moisture faster and in greater qu...

Page 7: ... the base of each suction riser of four 4 feet or more to enhance oil return to the compressor e For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximity of the expansion valve bulb f When brazing refrigerant lines an inert gas should be passed through the line at low pressure to prevent scaling and oxidation inside the tubing ...

Page 8: ...superheat at the compressor Figure 6 Suction P Traps Slope 1 4 per 10 ft toward compressor Suction Lines NOTE If the suction line must rise to a point higher than the suction connection on the evaporator a suction line trap at the outlet of the evaporator must be provided Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1 4 inch per 10 feet for go...

Page 9: ...Tee Straight Through 1 2 2 3 4 4 5 7 8 10 12 14 16 Table 4 Pressure Loss of Liquid Refrigerants in Liquid Line Risers Expressed in Pressure Drop PSIG and Subcooling Loss F Liquid Line Rise in Feet 10ʼ 15ʼ 20ʼ 25ʼ 30ʼ 40ʼ 50ʼ 75ʼ 100ʼ Refrigerant PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F R22 4 8 1 6 7 3 2 3 9 7 3 1 12 1 3 8 14 5 4 7 19 4 6 2 24 2 8 0 36 3 12 1 48 4 16 5 R134a 4...

Page 10: ... 1 3 27 26 39 63 86 1 24 134a 64 2 2 57 14 26 40 61 1 91 1 3 8 22 63 5 3 50 27 42 64 93 1 33 R507 404A 55 0 4 98 40 58 95 1 32 1 87 134a 90 9 3 65 20 37 57 87 1 30 1 5 8 22 90 0 4 96 37 59 90 1 33 1 88 R507 404A 78 0 7 07 56 82 1 35 1 86 2 64 134a 158 6 34 34 64 98 1 51 2 24 2 1 8 22 156 8 61 65 1 03 1 57 2 30 3 26 R507 404A 134 12 25 98 1 43 2 35 3 23 4 58 134a 244 9 78 52 99 1 51 2 32 3 47 2 5 8...

Page 11: ...CFCʼs There is a view that even small quantities of chlorine may act as a catalyst encouraging copper plating and or corrosion and should therefore be avoided WARNING HFC 134a has been shown to be combus tible at pressure as low as 5 5 psig at 350 F when mixed with air at concen trations more than 60 air by volume At lower temperature higher pressures are required to support combustion Therefore a...

Page 12: ...ng until system has sufficient refrigerant for proper operation Do not overcharge Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant i Do not leave unit unattended until the system has reached normal operating conditions and the oil charge has been properly adjusted to maintain the oil level at the center of the sight glass CAUTION Extreme car...

Page 13: ...ve at the evaporator should be adjusted Operational Check Out After the system has been charged and has operated for at least two hours at normal operating conditions without any indication of malfunction it should be allowed to operate overnight on automatic controls Then a thorough recheck of the entire system operation should be made as follows a Check compressor discharge and suction pressures...

Page 14: ... system 3 Check for leaks Repair and add charge 4 Low suction pressure 4 See corrective steps for low suction pressure 5 Variable head pressure valve 5 Check valve setting High suction pressure 1 Excessive load 1 Reduce load or add additional equipment 2 Expansion valve overfeeding 2 Check remote bulb Regulate superheat Low suction pressure 1 Lack of refrigerant 1 Check for leaks Repair and add ch...

Page 15: ... and components Verify that all electrical and ground connections are secure tighten as required Check condition of compressor and heater contactors Look for discoloration and pitting Replace as required Check operation and calibration of all timers relays pressure controls and safety controls Clean electrical cabinet Look for signs of moisture dirt debris insects and wildlife Take corrective acti...

Page 16: ...ATE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 2...

Page 17: ...TE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 25...

Page 18: ...18 Control Circuit Wiring Diagram for BACU51 and BACU59 ...

Page 19: ...19 Submittal ...

Page 20: ...20 Submittal ...

Page 21: ...t Serial ________________________________________ Compressor Model ____________________ Compressor Model _________________ Compressor Serial ____________________ Compressor Serial __________________ Electrical _________________ Volts __________________ Phase _______ Voltage at Compressor L1__________ L2 ___________ L3 ___________ Amperage at Compressor L1__________ L2 ___________ L3 ___________ Se...

Page 22: ...22 Notes ...

Page 23: ...23 Notes ...

Page 24: ...PLACE BOULEVARD STONE MOUNTAIN GA 30087 USA 770 465 5600 FAX 770 465 5990 WWW HEATCRAFTRPD COM Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice Visit us online at www heatcraftrpd com ...

Reviews: