background image

FUEL SUPPLY (CONTINUED)

• For proper propane tank sizing see page 9.
• Visually inspect the hose assembly and ensure that it is protected from traffic, building 

materials, and contact with hot surfaces.  If it is evident that there is excessive abrasion or wear,
or the hose is cut, replace it immediately.

• Purge air from line and wait 10 minutes for gas to dissipate.
• After installation, check the hose assembly for gas leaks by applying a water and soap solution 

to each connection.

• Fuel hose must be UL approved.
• The installation of this heater to a natural gas supply must confirm with all applicable local 

codes or, in the absence of local codes, with the 

National Fuel Gas Code ANSI Z223.1/NFPA 54.

For vapor propane, refer to standard for 

Storage and Handling of Liquified Petroleum Gases 

ANSI/NFPA 58.

ELECTRICAL

• Electric cable extensions must be connected based on the unit capacity and cable length.

• We highly recommend a dedicated line, 20 amp minimum.

• Confirm voltage at heater connection (105V min.) to ensure proper operation.

EXHAUST FLUE PIPE

• The unit is to be connected to a flue pipe with adequate draft, to ensure the proper start and 

operation of the unit.  Refer to page 11.

• The flue pipe and its installation must comply with the regulations and instructions given by 

the local authorities.

• A flue pipe must be used at all times.  You must increase flue pipe diameter if its is 

longer than 26”

DISCHARGE DUCTING (Warm Air)

• Minimum clearance from combustible materials is 4 inches.
• Use steel ducting or fabric ducting capable of withstanding maximum temperature of 225ºF.
• Maximum length of duct: 75’ (straight).
• Duct diameter: 20”.
• Make sure that the duct is safely and properly fastened to the outlet.
• Avoid sharp bends and corners to ensure maximum air flow and avoid back pressure/heat 

accumulation in heater.

• Do not exceed 3/4” w.c. of back pressure.
• FAILURE TO COMPLY WITH THESE RECOMMENDATIONS COULD RESULT IN SHUTDOWN

OF THE HEATER.

Rec Duct PN WD2025 (20’Dia. x 25’ Long)

5

Summary of Contents for VF600

Page 1: ...or future reference 342 N Co Rd 400 East Valparaiso IN 46383 888 432 8924 Fax 219 462 7985 www heatwagon com Revision 11 16 CAUTION Do not use this heater in a space where gasoline or other liquids having flammable vapors are stored Construction Heater VG600 VF600 ...

Page 2: ...WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE QUESTIONS ABOUT LOCAL REGULATIONS Other standards govern the use of fuel gases and heat producing products in specific applica tions Your local authority can advise you about these CAUTION DO NOT USE THIS HEATER IN A SPACE WHERE GASOLINE OR OTHER LIQ UIDS HAVING FLAMMABLE VAPORS ARE STORED OR USED CONSTRUCTION HEATER GENERAL HAZARD WARNING Failure ...

Page 3: ...nd serial number Components are guaranteed to the extent of the component manufacturer s warranty LIMITATIONS Warranty claims for service parts wear parts such as spark plugs igniters and flame rods will not be allowed Diagnostic parts such as voltage meters and pressure gauges are not warrantable Evidence of improper fuel usage fuel pressures outside of manufacturer s specification poor fuel qual...

Page 4: ...unit from power supply and turn off the gas supply when maintenance or service is being performed IF NOT OPERATED WITHIN GUIDELINES OF THESE OPERATING INSTRUCTIONS MANUFACTURER WILL NOT BE HELD RESPONSIBLE AND WARRANTY WILL BECOME VOID 3 SPECIFICATIONS Model No VG600 Fuels Vapor Propane or Natural Gas Capacity 600 000 BTU HR Blower 5400 CFM 3 4 SP Electrical Rating 120 Volts 15 Amps Fuel Consumpti...

Page 5: ...ssure to the heater does not exceed 1 2 psi inlet pressure Excessive pressures over 1 2 psi 14 W C will damage controls and void warranty This heater is shipped as either natural gas or vapor propane Check for proper burner orifice in burner Vapor Propane 2 0 Natural Gas 3 7 Be certain to use adequate hose or pipe size to ensure proper volume and pressure See Chart Below 4 VAPOR PROPANE QUICK REFE...

Page 6: ...nd cable length We highly recommend a dedicated line 20 amp minimum Confirm voltage at heater connection 105V min to ensure proper operation EXHAUST FLUE PIPE The unit is to be connected to a flue pipe with adequate draft to ensure the proper start and operation of the unit Refer to page 11 The flue pipe and its installation must comply with the regulations and instructions given by the local auth...

Page 7: ...ices including the safety limit controls The room thermostat and burner sensor control the running sequences of the burner and the fan sensor controls the fan function Overheat limit reset controls and shuts off the heater burner in the case of overheating The unit can also be used for ventilation purposes only if needed 1 Turn the control switch on the control box to position 2 VENTILATION 2 The ...

Page 8: ...h are harmful or environmentally unfriendly when cleaning the unit Do not use water jet when cleaning the unit Pressurized air may be used for maintenance Be careful not to damage the fan blower wheel with too much pressure 30 psi Check whether the unit is free from mechanical damage replace faulty parts as necessary Check fan blower wheel of the fan at regular intervals and clean it with a small ...

Page 9: ...exchanger Clean combustion chamber and exchanger tube with brush Vacuum all loose ash and soot Close all cleaning flanges carefully to avoid damage to gasket material Disassembling of burner 1 Disassemble two tightening nuts on the combustion chamber flange and remove burner from mounting flange Take care not to damage the flange gasket 2 Pull out the burner Take care not to damage the burner head...

Page 10: ...9 REFERENCE CHARTS ...

Page 11: ...10 Propane Orifice Kit PN BIE 3000886 Natural Gas Orifice PN BIE 3006703 ...

Page 12: ...6 610 840 8 0 415 660 970 1320 2 322 515 745 1020 8 303 490 720 1000 16 281 458 685 950 10 0 450 720 1060 1450 2 355 560 850 1130 10 330 525 795 1080 20 300 486 735 1030 15 0 525 840 1240 1720 2 414 675 985 1350 15 373 610 905 1250 30 328 553 845 1180 20 0 575 930 1350 1900 2 470 755 1100 1520 10 443 710 1045 1460 20 410 665 990 1390 30 380 626 945 1270 30 0 650 1060 1550 2170 2 535 865 1310 1800 ...

Page 13: ...WIRING CHART 12 ...

Page 14: ...13 PARTS BREAKDOWN ...

Page 15: ... 2 2077 180 TIRE NOT SHOWN 25 1 2077 170 SUPPORT LEG 26 1 2077 203 DUCT ADAPTER 27 1 2077 221 BOTTOM PLATE BLOWER 28 2 2077 222 BRACKET TOP BLOWER 29 2 2077 223 MOUNTING STRIPS SIDE 30 1 2077 226 AIR INLET LEFT PANEL 31 1 2077 227 MOTOR MOUNT PLATE 32 1 38243420M AIR FAN HW 33 1 HM1050 MOTOR HW 34 1 LD4P CLUTCH PULLEY 35 1 AK74 FAN SHEAVE HW 36 2 A42 V BELT HW 37 4 M10 x 1 25 din zn HEX NUT 38 2 M...

Page 16: ...15 SPARE PARTS BREAKDOWN VG900 VG600 VG700 ...

Page 17: ...16 SPARE PARTS LIST Gas Pipe Train Not Shown C5852400 Maxitrol Regulator RV61 C5850607 ASCO Solenoid C5850017 Dungs Valve ...

Page 18: ...17 RIELLO BURNER WIRING either 120V or 240V control systems ...

Page 19: ...18 RIELLO BURNER COMBUSTION HEAD ...

Page 20: ...19 RIELLO BURNER AIR GATE ...

Page 21: ...20 RIELLO BURNER COMBUSTION CHAMBER ...

Page 22: ...21 RIELLO BURNER START UP ...

Page 23: ...22 RIELLO BURNER DIAGNOSTICS ...

Page 24: ...23 RIELLO BURNER TROUBLESHOOTING ...

Page 25: ...VF600 OIL FIRED BURNER ELECTRODE SETTING 24 ...

Page 26: ...VF600 OIL FIRED BURNER AIR ADJUSTMENT 25 ...

Page 27: ...VF600 OIL FIRED BURNER PARTS BREAKDOWN 26 ...

Page 28: ...342 N Co Rd 400 East Valparaiso IN 46383 219 464 8818 Fax 219 462 7985 www heatwagon com ...

Reviews: