9

no or YES

 - Pump Activation every 24 hours

•  If the display shows 

YES 

then the VSP will activate both the Secondary Loop pump and the Injection pump for 5

minutes every 24 hours.  Certain local codes (generally only in Canada) require this.

• If the display shows 

no 

then the VSP will only run the pumps when the system requires it.  This setting will prevent

hot water from being pumped into the Secondary loop when there is no call for heat.

• To change the mode, hold down the center button while pushing either the 

UP

 or 

DOWN

 button to toggle between the

displays of 

YES

 and 

no.

• When the correct mode is selected, release the buttons and wait approximately 5 seconds.
• If any changes were made to the operating modes, the display will flash.  Then the VSP will display the temperature of

the sensor in the Secondary loop.

INITIAL SETTINGS FOR A RESET CONTROL (see 

rSt

 previous page)

• After setting the operating mode, the VSP will display the temperature of the Secondary loop.  This is the default

display.

• To see and/or adjust the other parameters, press then release the center button marked 

PRESS TO READ

.  The VSP will

display a code to indicate which parameter will be displayed next.  After two seconds, the value of the parameter will
be shown.

• For those parameters where the values can be set (shown on chart pg. 10), press the 

UP

 or 

DOWN

 button to change

the value while it is being displayed.  Holding down the 

UP

 or 

DOWN

 button will cause the value to change more

quickly.

• The 

S

ys

t

em

 S

tart

 (

StS

) temperature setting is the outdoor temperature above which the VSP will not give heat.  Start

with the factory default setting of  60°F.

• The 

r

e

S

e

t Ratio

 (

rSt

) determines how quickly the water temperature in the Secondary loop will increase as the outdoor

temperature decreases (see pg. 12).  Lower numbered curves result in lower water temperatures.  The factory default
curve is 7 or (1:1).  This means for every degree the outdoor temperature falls (below the 

System Start

 temperature) the

Secondary loop temperature will be increased one degree.  For baseboard heat, start with 7.  For most radiant tubing
applications, start with 3.

• The 

Off

set

 (

OFF

) value is added or subtracted to the calculated water temperature for the Secondary loop.  It effec-

tively moves the starting point of the reset curves up and down by the number of degrees selected (see pg. 12).  Start
with the factory default setting of 0.

• The 

LO

w

 r

eturn 

(

LOr

) comes factory set to 

OFF

.  This is the correct setting if you are not using the Boiler return water

sensor.  If you do use the Boiler return sensor, then the setting must be set to the boiler manufacturer's specification.

• The 

Hi

gh Supply

 (

Hi

) value must be adjusted to the maximum temperature value specified for the Secondary loop

components.

• The 

S

et

b

ack (Sb) value 

determines how many degrees the Secondary loop temperature will be decreased when the

EXT Input in the Setback mode (see pg. 13) is shorted.  Start with the factory default setting of 20°F.

INITIAL SETTINGS FOR A SET POINT CONTROL (see 

SP

 previous page)

• After setting the operating mode, the VSP will display the temperature of the Secondary loop.  This is the default value

for the VSP display.

• To see and/or adjust the other parameters, press then release the center button marked 

PRESS TO READ

.  The VSP will

display a code to indicate which parameter will be displayed next.  After two seconds, the value of the parameter will
be shown.

• For those parameters where the values can be set (shown on chart pg. 10), press the 

UP

 or 

DOWN

 button to change

the value while it is being displayed.  Holding down the 

UP

 or 

DOWN

 button will cause the value to change more

quickly.

• The 

S

ys

t

em

 S

tart

 (

StS

) temperature setting is the outdoor temperature above which the VSP will not give heat.  Set to

ON

 if the system set point should be held regardless of outside temperature.

• The 

r

e

S

e

t Ratio

 (

rSt

) and 

Off

set

 (

OFF

) values have no effect and do not need to be adjusted.

• The 

LO

w

 r

eturn 

(

LOr

)comes factory set to 

OFF

.  This is the correct setting if you are not using the Boiler return water

sensor.  If you do use the Boiler return sensor, then the setting must be set to the boiler manufacturer's specification.

• The 

S

et 

P

oint

 (

SP

) should be set to the desired temperature for the Secondary loop.

• The 

S

et

b

ack (Sb)

 value determines how many degrees the Secondary loop temperature will be decreased when the

EXT Input in the Setback mode (see pg. 13) is shorted.  Start with the factory default setting of 20°F.

Summary of Contents for VSP

Page 1: ...then automatically regulated based on outdoor temperature The outdoor reset function maintains constant and comfortable ambient building temperatures in all weather conditions The VSP can also be used...

Page 2: ...re than 500 from the VSP controller Both wells are 3 8 ID The wells are designed to be installed in a tee with a 3 4 bull Solder the well into the bull of the tee as shown Slide the sensor into the we...

Page 3: ...nd Secondary loops Pipe Sizing The Injection piping diameter must be at least one pipe size smaller than the smaller of the Primary or Secondary loop piping See Sizing Charts on pages 4 and 5 Primary...

Page 4: ...ve 20 the intersection of the row marked40 Primary Secondary loop temp and the column marked 10 Delta T provides 50 000as the maximum amount of BTUs This is too low Move on to the next chart Checking...

Page 5: ...ature minus Secondary Loop Temperature Maximum Injection BTUs Injection Piping Size 1 1 4 Globe Valve Opening 100 Typical Pump Models Taco 0010 Grundfoss 26 64 Delta T of Secondary Loop 1 760 000 1 44...

Page 6: ...LINE NEU BLUE Pump Motor RED Pump Starter Motor BLACK Must be connected directly to 120VAC motor NO PUMP STARTER Wire Sensor Shields to either COM Screw Outdoor Sensor Setback or Remote Enable If Pump...

Page 7: ...sensor wires have been extended connect the shield to a COM terminal The two wires from the Secondary loop sensor must be connected to the VSP front screws marked SEC and COM The two wires from the O...

Page 8: ...ar application they will be retained in memory and will not need to be reset Note that if you do change an operating mode you will need to reset all other settings An operating mode can only be change...

Page 9: ...Offset OFF value is added or subtracted to the calculated water temperature for the Secondary loop It effec tively moves the starting point of the reset curves up and down by the number of degrees se...

Page 10: ...er manufacturer s specification for minimum boiler return temperature 7 times Reset Operation ONLY This is the highest Secondary loop water temperature the VSP will maintain IMPORTANT The VSP is not a...

Page 11: ...put RED wires will be off The SystemStartis adjustable from 30 F to 70 F TheSystem Start also has two special modes OFF When the System Startis set to OFF neither the Secondary loop pump nor the Injec...

Page 12: ...e Reset Ratio curves see side charts When the OFFset is changed that change is always directly added or subtracted to the calculated water temperature For instance if the calculated Secondary loop wat...

Page 13: ...The High Supply should never be set higher than the maximum value specified by either the Secondary loop component or the flooring manufacturer Adjust the High Supply as shown on the chart pg 10 SET...

Page 14: ...This test should only be performed by a qualified electrician or electrical contractor Place the leads of the voltmeter across the power inputs of the Injection pump At the highest speed the AC Volt...

Page 15: ...OPEN or a resistance greater than 100 000 Check the wires going to the sensor They may have been broken or become discon nected If the wires are fine check the resistance at the sensor itself If the v...

Page 16: ...Sequencing controls Radiant heat controls Digital set point controls Precision tempering valves VARIVALVE air vents 2 3 and 4 way motorized valves Snow melt controls Heat Timer Corporation 20 New Dutc...

Reviews: