heat-timer VSP Installation & Operating Instructions Manual Download Page 12

12

RESET RATIO

Set Point Operation:

r

e

S

e

t

 ratio

 (

rSt

) has no effect.

Reset Operation:

The 

r

e

S

e

t

 ratio

 (

rSt

) determines how the Secondary loop

water temperature will vary with outside temperature.  With
any ratio, the colder it is outside, the hotter the tempera-
ture of the Secondary loop.  At a 1:1 reset ratio (Curve 7) a
1 degree drop in outdoor temperature will increase the
Secondary loop temperature by 1 degree; at the 3:1 ratio
(Curve 3) an outdoor temperature drop of 3 degrees will
increase the Secondary loop temperature by 1 degree.

The ratios are adjustable from 8:1 (Curve 1) for the least
amount of heat to 1:4 (Curve 12) for the most amount of
heat (see side chart).  With most baseboard heating
applications, a 1:1 (Curve 7) setting is a good place to start.
Radiant heat applications usually require a lower curve.

Adjust the 

r

e

S

e

t

 ratio

 in cold weather.  If the ambient

space temperatures are too cold in cold weather, increase
the curve number by one.  If the space temperatures are
too warm in cold weather, decrease the curve number by
one.  After making a change to the ratio, wait 24 hours to
evaluate the impact of the change.  See chart pg. 10 to
adjust the 

r

e

S

e

t

 ratio

OFFSET

Set Point Operation:

OFF

set

 (

OFF

) has no effect.

Reset Operation:

The 

OFF

set

 (

OFF

) allows you to adjust the starting points

of the Reset Ratio curves (see side charts).  When the

OFF

set

 is changed, that change is always directly added

or subtracted to the calculated water temperature.  For
instance, if the calculated Secondary loop water tempera-
ture were 130°F and the 

OFF

set

 were changed from 0° to

10° (an increase of 10°), then the calculated water tempera-
ture would immediately change to 140°F.

Adjust the

OFF

set

 

in mild weather.  If the ambient space

temperatures are warm in mild weather, decrease the

OFF

set

.  If the space temperatures are cold in the mild

weather, increase the 

OFF

set

.  The rule of thumb for

baseboard radiation is to change the 

OFF

set

 by 4° for

every degree you wish to change the space temperatures.
For radiant heat applications, change the 

OFF

set

 by 1° or

2° for every degree you wish to change the space tempera-
ture.  See chart on 10 to adjust the 

OFF

set.

Outdoor T emperature

W

a

te

T

e

m

p

e

ra

tu

re

70

40

50

60

130

120

110

100

11

2

7

Outdoor T emperature

W

a

te

T

e

m

p

e

ra

tu

re

70

40

50

60

110

100

90

80

11

2

7

Outdoor T emperature

W

a

te

T

e

m

p

e

ra

tu

re

70

40

50

60

150

140

130

120

11

2

7

0° Offset

The ratios begin

at 100° Water
Temperature.

-20° Offset

The ratios begin

at 80° Water

Temperature.

+20° Offset

The ratios begin

at 120° Water
Temperature.

Offset Examples

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

W

a

te

T

e

m

p

e

ra

tu

re

 (

in

 °

F

)

100

120

110

130

140

150

160

180

170

190

200

210

220

12 11

10

9

8

7

6

4

3
2

5

1

1:4 1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1
4:1

8:1

Reset Ratio Curves

Ratios represent Outdoor:Water

Summary of Contents for VSP

Page 1: ...then automatically regulated based on outdoor temperature The outdoor reset function maintains constant and comfortable ambient building temperatures in all weather conditions The VSP can also be used...

Page 2: ...re than 500 from the VSP controller Both wells are 3 8 ID The wells are designed to be installed in a tee with a 3 4 bull Solder the well into the bull of the tee as shown Slide the sensor into the we...

Page 3: ...nd Secondary loops Pipe Sizing The Injection piping diameter must be at least one pipe size smaller than the smaller of the Primary or Secondary loop piping See Sizing Charts on pages 4 and 5 Primary...

Page 4: ...ve 20 the intersection of the row marked40 Primary Secondary loop temp and the column marked 10 Delta T provides 50 000as the maximum amount of BTUs This is too low Move on to the next chart Checking...

Page 5: ...ature minus Secondary Loop Temperature Maximum Injection BTUs Injection Piping Size 1 1 4 Globe Valve Opening 100 Typical Pump Models Taco 0010 Grundfoss 26 64 Delta T of Secondary Loop 1 760 000 1 44...

Page 6: ...LINE NEU BLUE Pump Motor RED Pump Starter Motor BLACK Must be connected directly to 120VAC motor NO PUMP STARTER Wire Sensor Shields to either COM Screw Outdoor Sensor Setback or Remote Enable If Pump...

Page 7: ...sensor wires have been extended connect the shield to a COM terminal The two wires from the Secondary loop sensor must be connected to the VSP front screws marked SEC and COM The two wires from the O...

Page 8: ...ar application they will be retained in memory and will not need to be reset Note that if you do change an operating mode you will need to reset all other settings An operating mode can only be change...

Page 9: ...Offset OFF value is added or subtracted to the calculated water temperature for the Secondary loop It effec tively moves the starting point of the reset curves up and down by the number of degrees se...

Page 10: ...er manufacturer s specification for minimum boiler return temperature 7 times Reset Operation ONLY This is the highest Secondary loop water temperature the VSP will maintain IMPORTANT The VSP is not a...

Page 11: ...put RED wires will be off The SystemStartis adjustable from 30 F to 70 F TheSystem Start also has two special modes OFF When the System Startis set to OFF neither the Secondary loop pump nor the Injec...

Page 12: ...e Reset Ratio curves see side charts When the OFFset is changed that change is always directly added or subtracted to the calculated water temperature For instance if the calculated Secondary loop wat...

Page 13: ...The High Supply should never be set higher than the maximum value specified by either the Secondary loop component or the flooring manufacturer Adjust the High Supply as shown on the chart pg 10 SET...

Page 14: ...This test should only be performed by a qualified electrician or electrical contractor Place the leads of the voltmeter across the power inputs of the Injection pump At the highest speed the AC Volt...

Page 15: ...OPEN or a resistance greater than 100 000 Check the wires going to the sensor They may have been broken or become discon nected If the wires are fine check the resistance at the sensor itself If the v...

Page 16: ...Sequencing controls Radiant heat controls Digital set point controls Precision tempering valves VARIVALVE air vents 2 3 and 4 way motorized valves Snow melt controls Heat Timer Corporation 20 New Dutc...