heat-timer VSP Installation & Operating Instructions Manual Download Page 7

7

CONTROL INSTALLATION

MOUNTING THE CONTROL

• The VSP is designed to mount on a 1900 (4”x4”) electrical box.
• If the VSP is to be panel mounted, or if additional room is needed for wiring, an extension kit is available (HT #908520).
• Locate the VSP in a convenient location near the variable speed pump.  The VSP can not be mounted more than 500'

from any sensor location.

• Mount the VSP away from excessive heat or cold.  Ambient operating temperature is from 20 to 120°F.
• After completing all the wiring connections (see opposite page) use the two screws provided to mount the VSP to the

1900 box.

INSTALLING THE SENSORS

• All three sensors are interchangeable.
• The sensor wires can be extended up to 500' from the controller by splicing with shielded two conductor 18 gauge

wire..  Do not connect the shield at the sensor end.  Do not run wires in conduit with line voltage.

• The Secondary loop sensor should be inserted in the well as described on pg. 2.
• The Boiler return water sensor, if used, should be inserted in the well as described on pg. 2.
• The Outdoor sensor should be mounted in the shade on the north side of the building (never in direct sunlight).  Keep

the sensor approximately 10' above ground level and away from doors, windows, exhaust fans, or other heat sources.

WIRING THE SENSORS

• The sensor wires have no polarity.  Either wire from a sensor can be connected to the appropriately marked VSP screw

terminal (see pg. 11) or the sensor common marked 

COM

.

• Either or both screw terminals marked 

COM

 can be used as the sensor common.  They are interchangeable.

• If the sensor wires have been extended, connect the shield to a 

COM

 terminal.

• The two wires from the Secondary loop sensor must be connected to the VSP front screws marked 

SEC

 and 

COM

.

• The two wires from the Outdoor sensor must be connected to the VSP front screws marked 

OUT

 and 

COM

.

• The two wires from the Boiler return water sensor, if used, must be connected to the VSP front screws marked 

RTN

 and

COM

.  (If not using this sensor, see the 

NOTE

 in Low Return pg. 13).

WIRING THE VSP POWER

• Attach 120VAC line voltage to the two Blue wires extending from the back of the VSP.
• Use wire nuts, or wrap the connections with electrical tape.
• Class 1 voltages must enter the 1900 box through a different opening from any Class 2 wiring.

WIRING THE INJECTION PUMP

• The Red wires provide a solid state switching output to the Injection pump.
• The Injection pump motor must be a fractional horsepower permanent split capacitor type motor.
• The output is designed for AC power only.  The maximum rating for the injection pump output is 3A 1/4HP.
• The Red wires must be directly in series with the pump power (see pg. 6).  The signal can not be wired through any

pilot duty relays or pump starters.

• Safety limit switches or HOA switches must be wired in series with the pump power.
• Use wire nuts, or wrap the connections with electrical tape.
• Class 1 voltages must enter the 1900 box through a different opening from any Class 2 wiring.

Warning:

  This Heat-Timer

 control is strictly an operating control;  it should never be used as a

primary limit or safety control.  All equipment must have its own certified limit and safety controls
required by local codes.  The installer must verify proper operation and correct any safety problems
prior to the installation of this Heat-Timer control.

Summary of Contents for VSP

Page 1: ...then automatically regulated based on outdoor temperature The outdoor reset function maintains constant and comfortable ambient building temperatures in all weather conditions The VSP can also be used...

Page 2: ...re than 500 from the VSP controller Both wells are 3 8 ID The wells are designed to be installed in a tee with a 3 4 bull Solder the well into the bull of the tee as shown Slide the sensor into the we...

Page 3: ...nd Secondary loops Pipe Sizing The Injection piping diameter must be at least one pipe size smaller than the smaller of the Primary or Secondary loop piping See Sizing Charts on pages 4 and 5 Primary...

Page 4: ...ve 20 the intersection of the row marked40 Primary Secondary loop temp and the column marked 10 Delta T provides 50 000as the maximum amount of BTUs This is too low Move on to the next chart Checking...

Page 5: ...ature minus Secondary Loop Temperature Maximum Injection BTUs Injection Piping Size 1 1 4 Globe Valve Opening 100 Typical Pump Models Taco 0010 Grundfoss 26 64 Delta T of Secondary Loop 1 760 000 1 44...

Page 6: ...LINE NEU BLUE Pump Motor RED Pump Starter Motor BLACK Must be connected directly to 120VAC motor NO PUMP STARTER Wire Sensor Shields to either COM Screw Outdoor Sensor Setback or Remote Enable If Pump...

Page 7: ...sensor wires have been extended connect the shield to a COM terminal The two wires from the Secondary loop sensor must be connected to the VSP front screws marked SEC and COM The two wires from the O...

Page 8: ...ar application they will be retained in memory and will not need to be reset Note that if you do change an operating mode you will need to reset all other settings An operating mode can only be change...

Page 9: ...Offset OFF value is added or subtracted to the calculated water temperature for the Secondary loop It effec tively moves the starting point of the reset curves up and down by the number of degrees se...

Page 10: ...er manufacturer s specification for minimum boiler return temperature 7 times Reset Operation ONLY This is the highest Secondary loop water temperature the VSP will maintain IMPORTANT The VSP is not a...

Page 11: ...put RED wires will be off The SystemStartis adjustable from 30 F to 70 F TheSystem Start also has two special modes OFF When the System Startis set to OFF neither the Secondary loop pump nor the Injec...

Page 12: ...e Reset Ratio curves see side charts When the OFFset is changed that change is always directly added or subtracted to the calculated water temperature For instance if the calculated Secondary loop wat...

Page 13: ...The High Supply should never be set higher than the maximum value specified by either the Secondary loop component or the flooring manufacturer Adjust the High Supply as shown on the chart pg 10 SET...

Page 14: ...This test should only be performed by a qualified electrician or electrical contractor Place the leads of the voltmeter across the power inputs of the Injection pump At the highest speed the AC Volt...

Page 15: ...OPEN or a resistance greater than 100 000 Check the wires going to the sensor They may have been broken or become discon nected If the wires are fine check the resistance at the sensor itself If the v...