Heat-N-Glo RHW-44 Installation & Operating Instructions Manual Download Page 18

RHW-44 WOODBURNING FIREPLACE

3-00

18                                                                                      33147A

Figure 21

Positioning the Hearth Extension

STEP 18 - Installing the Glass Doors.

If desired, or required by local building codes, install
the glass doors using the instructions supplied with
the particular set of doors you have chosen.

STEP 19 - Positioning the Hearth Extension.

Position and secure the hearth extension over the
protective metal strips that have been placed partially
under the firebox front.  These strips should be pro-
truding approximately two inches from under the fire-
place front.  Seal the crack between the hearth
extension and fireplace with a non-combustible
sealant.

STEP 20 - Applying Finishing Materials on the

Hearth Extension.

Apply the non-combustible finishing material of your
choice to the hearth extension.

Do not install com-

bustible materials over the black face of the fire-
place.  This poses a safety hazard and may start
a fire. 

You may only use non-combustible material

over the black face of the fireplace.  Refer to Figure 7
for combustible material information.

Figure 20

Gas Knockout Location

CAUTION:

WHEN USING A GAS LOG SET,
THE FIREPLACE DAMPER MUST
BE SET IN THE FULLY OPEN
POSITION.

THIS ENSURES A

PROPER VENTING OF COMBUS-
TION PRODUCTS.

WARNING!

THIS FIREPLACE WAS NOT TESTED BY THE

FIREPLACE MANUFACTURER FOR USE

WITH AN UNVENTED GAS LOG HEATER.

DO NOT INSTALL AN UNVENTED GAS LOG

HEATER IN THIS FIREPLACE UNLESS IT

HAS BEEN SPECIFICALLY TESTED AND

LISTED BY UNDERWRITERS LABORATO-

RIES INC FOR USE IN THIS SPECIFIC

MODEL FIREPLACE.  UNLESS THE UNVENT-

ED GAS LOG HEATER IS TESTED AND LIST-

ED FOR USE IN THIS FACTORY-BUILT FIRE-

PLACE, A FIRE HAZARD MAY BE CREATED
THAT CAN RESULT IN A STRUCTURE FIRE.

STEP 17 - Provisions for a Gas Log Set or Gas Log

Lighter.

Knockouts are provided on both sides of the fireplace
for the connection of a certified gas log lighter or a dec-
orative gas appliance with a maximum input of 100,000
BTU/hr incorporating an automatic gas shutoff device
and complying with the Standard for Decorative Gas
Appliances for Installation in Vented Fireplaces, ANSI
Z21.60.  The decorative gas appliance should be
installed in accordance with the National Fuel Gas
Code, ANSI Z223.1.  The side refractories are designed
to allow 1/2” iron pipe to pass through.  Use a non-com-
bustible sealant to seal any opening between the gas
pipe and the refractory on the inside.  Repack the insu-
lation removed, to seal around the gas pipe where it
exits the side of the fireplace.  A minimum 1-1/2” air
clearance must be provided to the 1/2” iron pipe.
See Figure 20 for the shaded area.

Summary of Contents for RHW-44

Page 1: ...ion information Framer Please refer to page 9 for framing specifications RHW 44 WOODBURNING FIREPLACE INSTALLATION OPERATING INSTRUCTIONS FOR RESIDENTIAL USE Heat N Glo a Division of Hearth Technologi...

Page 2: ...lly tight the optional combustion air kit may not provide all the air required to support combustion Heat N Glo is not responsible for any smoking or related prob lems that may result from the lack of...

Page 3: ...ITEMS IN THIS SYSTEM UNLESS ALLOWED BY THESE INSTALLATION INSTRUCTIONS WILL VOID THE UNDERWRITERS LABORATORIES LISTING AND MAY VOID THE PRODUCT WARRANTY IT MAY ALSO CREATE A HAZARDOUS INSTALLATION RE...

Page 4: ...Integral Grate included with Fireplace ID4 Insulated Duct Outside Air UD4 Uninsulated Duct Outside Air CAK4 Chimney Air Kit SL306 Chimney Section 6 long SL312 Chimney Section 12 long SL318 Chimney Se...

Page 5: ...3 00 5 33147A OUTSIDE AIR KIT SUPPLIED RHW 44 WOODBURNING FIREPLACE AK14 GR8 STRAIGHT ATTIC HEARTH EXTENSION GLASS DOORS INSULATION SHIELD INTEGRAL GRATE HX3 AS8...

Page 6: ...SL348 48 463 4 CAT A B FS338 0 141 2 FS339 15 183 8 FS340 30 23 CHIMNEY SECTIONS CHIMNEY STABILIZER OFFSETS RETURNS SL3 FIRESTOP SPACERS RF371 6 12 to 12 12 Pitch ROOF FLASHING A Actual length B Effec...

Page 7: ...HIMNEY TERMINAL CAPS VENT SECTIONS RHW 44 WOODBURNING FIREPLACE CT35 CHASE TOP TS345 345P SQUARE TERMINAL CAP TR342 ROUND TELESCOPING TERMINAL CAP TR344 ROUND TERMINAL CAP WITH STORM COLLAR ST375 SQUA...

Page 8: ...LACE MUST NOT BE INSTALLED AGAINST VAPOR BARRIERS OR EXPOSED INSULA TION LOCALIZED OVERHEATING COULD OCCUR AND A FIRE COULD RESULT A B C D 783 4 393 8 171 4 555 8 WITH OR WITHOUT OUTSIDE AIR Figure 2...

Page 9: ...ny material capable of igniting and burning whether flame proofed or not plastered or unplastered Non combustible Material Material which will not ignite and burn Such materials are those consisting e...

Page 10: ...CALCULATE THE REQUIRED THICKNESS FOR THE ALTERNATE MATERIAL USE THE FOLLOWING FORMULA K ALT 43 EXAMPLES OF INSULATION USG MICORE CV230 1 2 0 43 MINIMUM REQUIRED THICKNESS K VALUE x 5 THICKNESS OF ALT...

Page 11: ...ey section s may be used between an offset and return However the distance between two elbows must never exceed 10 feet in total length a Measure how far the chimney needs to be shifted to enable it t...

Page 12: ...losest to but not less than 141 2 is 145 8 using a 30 offset return It is then determined from the table that you would need 33 Dimension B between the offset and return The chimney components that be...

Page 13: ...eate a need for a taller chimney should smoking occur If the horizontal distance from the side of the chim ney to the peak of the roof is more than 10 feet a chimney height reference point is establis...

Page 14: ...metal strips two inches under the front edge of the fireplace The individual pieces must overlap each other by one inch in the middle of the fireplace to provide continuous coverage of the floor See...

Page 15: ...sides of the firestop spacer to the joists using a minimum of three 3 nails per side These firestop spacers are designed to provide the minimum 2 air space required around the chimney In all situation...

Page 16: ...ave straps for securing these parts to joists or rafters See Figure 15 STEP 11 Cutting out the Hole in the Roof Measure to either side of the nail and mark the 14 1 2 x 14 1 2 opening required This is...

Page 17: ...t A mini mum clearance of an 1 2 must be maintained between the fireplace sides and the enclosure as well as the fire place back and the enclosure See Figure 4 for framing details NOTE Use only a non...

Page 18: ...ROPER VENTING OF COMBUS TION PRODUCTS WARNING THIS FIREPLACE WAS NOT TESTED BY THE FIREPLACE MANUFACTURER FOR USE WITH AN UNVENTED GAS LOG HEATER DO NOT INSTALL AN UNVENTED GAS LOG HEATER IN THIS FIRE...

Page 19: ...the chase several factors must be considered a Maintain an 1 2 minimum air space around the firebox b Maintain a 2 air space around the chimney c The chase top must be constructed of a non combustibl...

Page 20: ...ntended to operate as a supple mental heat source for a single room It is not designed to function as a primary heat source for a structure Fireplaces as well as other woodburning appliances have been...

Page 21: ...spillage during start up WARNING DO NOT OPERATE THIS FIREPLACE WITH THE FLUE DAMPER IN THE CLOSED POSI TION COMBUSTION PRODUCTS MUST VENT UP THE CHIMNEY SYSTEM TO PRE VENT CARBON MONOXIDE POISONING AN...

Page 22: ...n damage Flue pipe joints and seams must be con tinuous and mechanically tight In a used chimney additional inspection is needed for creosote build up which is the formation of a flammable sediment Wh...

Page 23: ...escreens must not be used to hold burning material inside the fireplace Only those glass door units specifically tested and listed for use with the specific fireplace model should be used Screens shou...

Page 24: ...ring the first six 6 months after installation HEAT N GLO shall at its option replace or repair the Glass Doors and any electrical components if operation is faulty This does not include Glass panels...

Reviews: