Heat-N-Glo RHW-44 Installation & Operating Instructions Manual Download Page 15

RHW-44 WOODBURNING FIREPLACE

3-00

15                                                                                       33147A

Figure 12

Connecting Chimney Sections

Figure 13

Installing the Firestop Spacer

STEP 7 - Installing an AS8 Insulation Shield.

An AS8 insulation shield should be installed when there
is a possibility of insulation coming into contact with the
factory-built chimney system.  The AS8 is installed by
positioning it over the vertical chimney section where it
penetrates an FS338 firestop spacer.  The FS338 will
support the AS8.  See Figure 14.  When the factory-built
chimney penetrates an insulated ceiling at either 15 or
30 degrees from vertical, an insulation dam should be
constructed from plywood or sheet metal.  A minimum
2" air space must be provided between the insulation
dam and the factory-built chimney system.

STEP 5 - Preparing the Ceiling for Firestop

Spacers.

Mark and cut out an opening in the ceiling for the par-
ticular firestop spacer being utilized (14-1/2" x 14-1/2"
for an FS338, or 14-1/4" x 18-3/4" for an FS339, or
14-1/2” x 23” for an FS340).  Frame the opening with
the same dimension lumber used in the ceiling joists.

STEP 6 - Installing the Firestop Spacers.

Install the firestop spacer FS338 (Straight), FS339 (if
a 15° offset is located in the ceiling joist area), or
FS340 (if a 30° offset is located in the ceiling joist
area).  Nail the four sides of the firestop spacer to the
joists using a minimum of three [3] nails per side.

These firestop spacers are designed to provide the
minimum 2” air space required around the chimney.
In all situations, the firestop spacers are to be nailed

NOTE:  The
inner flue is
placed to the
inside of the
flue section
below it.  The
outer casing is
placed outside
the outer casing
of the chimney
section below it.
See Figure 12.

STEP 4 - Assembling Chimney Sections.

Attach either a straight chimney section or an offset
to the top of the fireplace depending on your installa-
tion requirement.  Chimney sections are locked
together by pushing downward until the top section
meets the stop bead on the lower section.  When
using offsets/returns, it is highly recommended that
the offset and return sections be secured in place
with screws to ensure proper orientation.
See Figure 11.

CAUTION:

INNER FLUE AND OUTER LINER SEC-
TIONS CANNOT BE DISASSEMBLED
ONCE LOCKED TOGETHER.

PLAN

AHEAD TO INSURE THE PROPER INSTAL-
LATION HEIGHT IS ACHIEVED WITH THE
SELECTED CHIMNEY COMPONENTS.

Figure 11

Connecting Chimney Sections

to the ceiling joists from the bottom or fireplace side,

EXCEPT

when the space above is an insulated ceiling

or attic space.  In this situation, the firestop spacer
must be nailed from the top side to prevent loose insu-
lation from falling into the required two inch air space
around the chimney.  See Figure 13. 

Firestop spacers must be used whenever the chimney
penetrates a ceiling/floor area.

Summary of Contents for RHW-44

Page 1: ...ion information Framer Please refer to page 9 for framing specifications RHW 44 WOODBURNING FIREPLACE INSTALLATION OPERATING INSTRUCTIONS FOR RESIDENTIAL USE Heat N Glo a Division of Hearth Technologi...

Page 2: ...lly tight the optional combustion air kit may not provide all the air required to support combustion Heat N Glo is not responsible for any smoking or related prob lems that may result from the lack of...

Page 3: ...ITEMS IN THIS SYSTEM UNLESS ALLOWED BY THESE INSTALLATION INSTRUCTIONS WILL VOID THE UNDERWRITERS LABORATORIES LISTING AND MAY VOID THE PRODUCT WARRANTY IT MAY ALSO CREATE A HAZARDOUS INSTALLATION RE...

Page 4: ...Integral Grate included with Fireplace ID4 Insulated Duct Outside Air UD4 Uninsulated Duct Outside Air CAK4 Chimney Air Kit SL306 Chimney Section 6 long SL312 Chimney Section 12 long SL318 Chimney Se...

Page 5: ...3 00 5 33147A OUTSIDE AIR KIT SUPPLIED RHW 44 WOODBURNING FIREPLACE AK14 GR8 STRAIGHT ATTIC HEARTH EXTENSION GLASS DOORS INSULATION SHIELD INTEGRAL GRATE HX3 AS8...

Page 6: ...SL348 48 463 4 CAT A B FS338 0 141 2 FS339 15 183 8 FS340 30 23 CHIMNEY SECTIONS CHIMNEY STABILIZER OFFSETS RETURNS SL3 FIRESTOP SPACERS RF371 6 12 to 12 12 Pitch ROOF FLASHING A Actual length B Effec...

Page 7: ...HIMNEY TERMINAL CAPS VENT SECTIONS RHW 44 WOODBURNING FIREPLACE CT35 CHASE TOP TS345 345P SQUARE TERMINAL CAP TR342 ROUND TELESCOPING TERMINAL CAP TR344 ROUND TERMINAL CAP WITH STORM COLLAR ST375 SQUA...

Page 8: ...LACE MUST NOT BE INSTALLED AGAINST VAPOR BARRIERS OR EXPOSED INSULA TION LOCALIZED OVERHEATING COULD OCCUR AND A FIRE COULD RESULT A B C D 783 4 393 8 171 4 555 8 WITH OR WITHOUT OUTSIDE AIR Figure 2...

Page 9: ...ny material capable of igniting and burning whether flame proofed or not plastered or unplastered Non combustible Material Material which will not ignite and burn Such materials are those consisting e...

Page 10: ...CALCULATE THE REQUIRED THICKNESS FOR THE ALTERNATE MATERIAL USE THE FOLLOWING FORMULA K ALT 43 EXAMPLES OF INSULATION USG MICORE CV230 1 2 0 43 MINIMUM REQUIRED THICKNESS K VALUE x 5 THICKNESS OF ALT...

Page 11: ...ey section s may be used between an offset and return However the distance between two elbows must never exceed 10 feet in total length a Measure how far the chimney needs to be shifted to enable it t...

Page 12: ...losest to but not less than 141 2 is 145 8 using a 30 offset return It is then determined from the table that you would need 33 Dimension B between the offset and return The chimney components that be...

Page 13: ...eate a need for a taller chimney should smoking occur If the horizontal distance from the side of the chim ney to the peak of the roof is more than 10 feet a chimney height reference point is establis...

Page 14: ...metal strips two inches under the front edge of the fireplace The individual pieces must overlap each other by one inch in the middle of the fireplace to provide continuous coverage of the floor See...

Page 15: ...sides of the firestop spacer to the joists using a minimum of three 3 nails per side These firestop spacers are designed to provide the minimum 2 air space required around the chimney In all situation...

Page 16: ...ave straps for securing these parts to joists or rafters See Figure 15 STEP 11 Cutting out the Hole in the Roof Measure to either side of the nail and mark the 14 1 2 x 14 1 2 opening required This is...

Page 17: ...t A mini mum clearance of an 1 2 must be maintained between the fireplace sides and the enclosure as well as the fire place back and the enclosure See Figure 4 for framing details NOTE Use only a non...

Page 18: ...ROPER VENTING OF COMBUS TION PRODUCTS WARNING THIS FIREPLACE WAS NOT TESTED BY THE FIREPLACE MANUFACTURER FOR USE WITH AN UNVENTED GAS LOG HEATER DO NOT INSTALL AN UNVENTED GAS LOG HEATER IN THIS FIRE...

Page 19: ...the chase several factors must be considered a Maintain an 1 2 minimum air space around the firebox b Maintain a 2 air space around the chimney c The chase top must be constructed of a non combustibl...

Page 20: ...ntended to operate as a supple mental heat source for a single room It is not designed to function as a primary heat source for a structure Fireplaces as well as other woodburning appliances have been...

Page 21: ...spillage during start up WARNING DO NOT OPERATE THIS FIREPLACE WITH THE FLUE DAMPER IN THE CLOSED POSI TION COMBUSTION PRODUCTS MUST VENT UP THE CHIMNEY SYSTEM TO PRE VENT CARBON MONOXIDE POISONING AN...

Page 22: ...n damage Flue pipe joints and seams must be con tinuous and mechanically tight In a used chimney additional inspection is needed for creosote build up which is the formation of a flammable sediment Wh...

Page 23: ...escreens must not be used to hold burning material inside the fireplace Only those glass door units specifically tested and listed for use with the specific fireplace model should be used Screens shou...

Page 24: ...ring the first six 6 months after installation HEAT N GLO shall at its option replace or repair the Glass Doors and any electrical components if operation is faulty This does not include Glass panels...

Reviews: