5
FRAMING SHOULD BE
CONSTRUCTED OF 2 X 4
LUMBER OR HEAVIER.
Model
A
B
C
D
Grand-50
57 1/2 47 3/4
25 5/8 86 5/8
NOTE: DIMENSIONS SHOWN IN INCHES
Figure 3. Framing Dimensions
THE FRAMING HEADERS MAY REST ON
THE FIREPLACE STAND-OFFS.
12”X12” VENT
FRAMING HOLE.
*
Minimum Clearances from the Vent Pipe to
Combustible Materials
For Vertical
For Horizontal Sections
Sections
At Wall Firestops
Top
Bottom
Sides
Top
Bottom
Sides
3 inches*
1 inch
1 inch
1 inch
2-1/2 inches 1/2 inch
1 inch
(75 mm) (25 mm) (25 mm)
(25 mm)
(63.7 mm) (13 mm) (25 mm)
For minimum clearances, see the direct vent
termination clearance diagrams on pages 19 and 21 in
this section.
Additional clearance and/or installation of a heat
shield is required above the first 90° elbow. See page
13 of the Installers Guide.
Step 2
Framing the
Fireplace
Fireplace framing can be built before or after the
fireplace is set in place. Framing should be positioned
to accommodate wall coverings and fireplace facing
material. The diagram below shows framing reference
dimensions.
MEASURE FIREPLACE DIMENSIONS, AND
VERIFY FRAMING METHODS AND WALL
COVERING DETAILS, BEFORE FRAMING
CONSTRUCTION BEGINS.
CAUTION