Heat-N-Glo BE-41 Installer'S Manual Download Page 16

18

!

B.  Installing Vent Components

After determining which set of starting collars will be used

(top or rear), follow venting instructions accordingly.

Venting Out the Rear Vent

Remove the installed rear seal cap from the rear starting

collars by cutting the strap at each end. (see Figure 15).

Follow the vent configuration tables accordingly.
Remove the insulation from the 

REAR

 five inch flue, pull

the heat shield out from outside of the firebox.

WARNING: THE TOP HEAT SHIELD (INSIDE

THE FIREBOX) MUST REMAIN ATTACHED IF

THE VENT SYSTEM IS ATTACHED TO THE

REAR STARTING COLLARS. SEE FIGURE 15.

Venting Out the Top Vent

Remove the two screws in the top vent collar seal cap and

remove the top vent collar seal cap and  two pieces of  in-

sulation inside the top two starting collars (See Figure 15).
Remove the heat shield from inside the 

TOP

 five inch flue

from outside of the firebox.
The glass must be taken off again for positioning the logs

when the unit is finally installed in place and finished around

it. Re-install the glass door. Attach vent system to the top

starting collars.

!

   Figure 16.  Attaching the First Vent Component

                     to the Starting Collars

WARNING: A  3/8  INCH  (9.5  MM)  BEAD  OF

STOVE CEMENT MUST BE PLACED AROUND

THE 5 INCH (127 MM) FIREPLACE STARTING COL-

LAR BEFORE ATTACHING THE FIRST VENT COM-

PONENT.  FAILURE  TO  SEAL  THIS  JOINT  MAY

CAUSE THE FIREPLACE TO OPERATE IMPROPERLY.

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

!

1.   Attach the First Vent Component to the

     Starting Collars

To attach the first vent component to the starting collars of

the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the 5 inch (127mm) fireplace starting collar.

• Make sure that the fiberglass rope gasket supplied with

the fireplace seals between the first 8-5/8 inch (219mm)

vent component and the outer fireplace wrap.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior

beads into the fireplace collar or previously installed com-

ponent end with four (4) equally spaced indented sections.

• When the internal beads of each 8-5/8 inch (219mm)

outer pipe line up, rotate the pipe section clockwise about

one-quarter (1/4) turn. The vent pipe is now locked together.

• The first 90° elbow installed in the vent system of a rear

venting fireplace 

MUST BE

 in a vertical position.

WARNING: ENSURE THAT THE FIBERGLASS

ROPE  GASKET  SUPPLIED  WITH  THE

FIREPLACE SEALS BETWEEN THE FIRST VENT

COMPONENT AND THE OUTER FIREPLACE WRAP.

If the installation is for a termination cap attached directly

to the fireplace, skip to the sections, 

Install Firestops

 and

Vent Termination

.

WARNING:  THE REAR VENT COLLAR SEAL

CAP MUST REMAIN ATTACHED TO THE REAR

VENT COLLARS IF THE VENT SYSTEM IS AT-

TACHED TO THE TOP STARTING COLLARS.
WARNING: FAILURE TO REMOVE  INSULATION

IN THE SET OF COLLARS YOU ARE USING

COULD CAUSE A FIRE.
WARNING: YOU MUST LEAVE THE INSULATION

IN PLACE IN THE SET OF COLLARS YOU ARE

NOT USING.

If your vertical vent component is over 10 feet, you may

want to install the vertical baffle (located in the bag containing

the install manual) to improve flame appearance. Center

the vertical baffle on the 5” flue being used, and with self

tapping screws secure the baffle to the inside of the firebox.

Figure 15

Insert screwdriver

or similar object

here to remove cap.

CUT

HERE

Venting Out Rear

Venting Out Top

!

!

!

HEAT

SHIELD

DISCARD

 INSULATION

and

HEAT SHIELD

HEAT

 SHIELD

INSULATION

DISCARD  BOTH

PIECES and

HEAT SHIELD

SEAL 

CAP

SEAL

CAP

Summary of Contents for BE-41

Page 1: ...UTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyforusewiththetype of gas indica...

Page 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Page 3: ...10 Step 3 Installing the Vent System 12 A Vent System Approvals 12 B Installing Vent Components 18 C Vent Termination 21 Step 4 Positioning Leveling and Securing the Fireplace 24 Step 5 The Gas Contr...

Page 4: ...1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas fireplaces are...

Page 5: ...eplace and its components are tested and safe when installed in accordance with this Installers Guide Report to your dealer any parts damaged in shipment particularly the condition of the glass Do not...

Page 6: ...unit is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Whether optional accessories devices such as a fan wall switch or re...

Page 7: ...the face of the fireplace is one inch 25 mm The back of the fireplace may be recessed 21 1 2 inches 546 mm into combustible construction Minimum Clearances from the Vent Pipe to Combustible Materials...

Page 8: ...below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0...

Page 9: ...3 8 INCHES 34 93mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35...

Page 10: ...nting configuration used Terminations Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical...

Page 11: ...Up Vertical Venting NOTE On vertical venting configurations where the vertical component is over 10 feet you may want to install the vertical baffle VERT BAF see Figure 7 STRAIGHT UP VERTICAL VENTING...

Page 12: ...e 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX...

Page 13: ...914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 12 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H...

Page 14: ...914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m...

Page 15: ...m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Page 16: ...inch 127mm fireplace starting collar Make sure that the fiberglass rope gasket supplied with the fireplace seals between the first 8 5 8 inch 219mm vent component and the outer fireplace wrap Lock th...

Page 17: ...e supports to the framing members Figure 17 Adding Venting Components For Vertical Runs The vent system must be supported every eight 8 feet 2 4m above the fireplace flue outlet by wall brackets To in...

Page 18: ...the vent passes To install firestops for vertical runs that pass through ceilings Position a plumb bob directly over the center of the verti cal vent component Mark the ceiling to establish the center...

Page 19: ...OR SIDING SEE THE FOL LOWING DIAGRAM FOR VENT TERMINATION CLEARANCES ROUND CAP TERMINATION PERFORATION CANNOT BE INSIDE THE WALL 7 1 2 191mm MINIMUM TRAPEZOID CAP TERMINATION 7 1 4 184mm WARNING THET...

Page 20: ...or that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm f...

Page 21: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Page 22: ...position level and secure the fireplace Figure 27 Proper Positioning Leveling and Securing of a Fireplace Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The type of g...

Page 23: ...vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the control so that the lines...

Page 24: ...witch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WA...

Page 25: ...NSI or CAN CGAtesting standardsdonot require hearth extensions for gas fireplace appliances Figure 33 Sealant Material HIGH TEMPERATURE SIDE SEAL JOINT 300 F 149 C MIN TOP O O 0 0 FINISH WALL MATERIAL...

Page 26: ...of the tie in the fireplace see Figure 35 WARNING USE WIRE CUT TERS DO NOT ATTEMPT TO CUT THE TIE WITH A KNIFE 3 Grasp the log assembly by the ends Do NOT grasp the log as sembly by the center Remove...

Page 27: ...rward on the refractory see Figure 37 7 Cut shrink wrap and remove from around the log assembly WARNING REMOVE ALL PACKAGING FROM LOGS 8 Install embers See ember placement instructions for details WAR...

Page 28: ...e chemicals used in the paint and logs Step 12 Lighting the Fireplace You ve reviewed all safety warnings you ve checked the fireplace for gas leaks you know the vent system is unobstructed and you ve...

Page 29: ...annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically B...

Reviews: