background image

®

Heat

Link

19

www.heatlink.com

SSPxx000x – SS Manifold Pump Panels

Installation, Operation, and Maintenance

SSP Panel

T

SSP Panel

T

Fill And Purge

The following steps are recommended in order to fill the panel 

with water and purge entrained air once piping is completed, 

and before activation of the panel.

Note: 

Additional purging steps may be required for the rest of 

the hydronic system.

Note: 

Isolation and drain valves are not included with the 

panel, but are necessary to properly fill and purge the 

panel, and to isolate the panel for service.

Step 1 

Ensure the panel is not powered.

Step 2 

Fully close valves 

A

B

, and 

C

. Fully close all supply 

E

 and all return 

F

 manifold valves.

 

Fully open valve 

D

.

Step 3 

Attach a purge hose (not included) to 

D

. Pressurize 

the main supply line. Open valve 

B

.

Step 4 

Open the first return manifold valve 

F

. Open the first 

supply manifold valve 

E

. Watch the hose in the pail 

until you observe a steady stream of water (no air or 

spitting). Close the first return manifold valve 

F

.

Step 5 

Repeat Step 4 for each loop until all loops are filled 

with water, and air is purged from pipes. 

Step 6 

Purging is complete when there is no more air and/or 

spitting. Close valve 

D

 then valve 

B

.

Step 7 

Remove hose from drain valve 

D

.

Step 8 

Check for leaks at connections. If any leaks are found 

use a back-up wrench and carefully tighten until leak 

stops. Do not overtighten.

The discharged system fluid from the fill and purge 

process is not for consumption or washing.

E

F

F

E

A

A

B

B

C

C

D

D

SSTL Series bottom feed

SSTL Series top feed

Summary of Contents for SSPLR106T

Page 1: ...e Manual Heat Link L6SSPxx000x MECHANICAL ROOM IN A BOX SSPLR106T SSPSS106B 120 140 160 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION 115 VOLTS ONLY 120 140 160 180 200 100 80...

Page 2: ...acking 5 Panel Components 6 7 Specifications 8 Panel Component Specifications 9 14 Manifold Balancing 11 Recessed Housing Mounting 15 16 Surface Mount Housing Mounting 17 Piping Hookup 18 Fill and Pur...

Page 3: ...tion of the panel and your safety Please pay attention to these symbols Disclaimer HeatLink Group Inc shall not be responsible for errors in its brochures or printed materials HeatLink Group Inc reser...

Page 4: ...ion of factors such as BTU loads outdoor design temperature indoor design temperature room set point temperature s differential fluid temperatures head loss flow rates and transfer capacities of the h...

Page 5: ...by removing the strapping Step 3 Remove the cardboard spacers from the carton then remove the panel from the carton Lift the panel by the enclosure not the cover Step 4 Remove the cover from the pane...

Page 6: ...0 76930 76930 6 Isolation Ball Valve 7 120V ac terminal strip 8 24V ac 40VA Transformer 9 StatLink Base Module 40226 40226 40226 10 Enclosure Recessed or Surface Mount Recessed or Surface Mount Recess...

Page 7: ...nce 11 15 120 140 16 0 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION 115 VOLTS ONLY 106030C 120 140 16 0 180 200 100 80 60 40 C F 0 20 100 40 80 60 LIVE GROUND NEUTRAL CAUTION...

Page 8: ...system controller 110 V ac max current 3A Auxiliary terminal Yes Piping 1 piping Piping connections 1 FNPT Enclosure Galvanized steel visible parts are satin coated steel Recessed Surface Mount 4 6 lo...

Page 9: ...e 40226 The StatLink base module connects room thermostats to their corresponding actuators Each zone has an LED which indicates if it is calling for heat A timer thermostat 46643 or 46673 can send a...

Page 10: ...m Head feet 1st Speed 2nd Speed 3rd Speed Circulator The circulators moves the heated fluid through the hydronic system when there is a call for heat from the thermostat Factory set to 3rd speed Speci...

Page 11: ...ll return valves are open remove black cap 3 Use the return valve to adjust flow to desired setting flow meter 4 Valves adjusted first may need to be re adjusted once all other loops have been set Rem...

Page 12: ...01 0 05 0 15 Pressure Drop in ft H 2 O kPa 10 30 30 90 0 03 1 0 5 0 25 Stainless Steel Manifold of turns from closed position 0 75 1 5 2 3 5 Working loop flow ranges from 0 1 to 1 25 US gpm 0 38 to 4...

Page 13: ...e Stainless Steel Manifold of turns from closed position 1 3 78 0 1 0 38 5 18 9 0 5 1 89 0 01 0 04 0 05 0 19 Mass Flow Rate in US gpm L min 1 3 5 15 0 1 0 3 0 5 1 5 0 01 0 05 0 15 Pressure Drop in ft...

Page 14: ...ing water is used for hydronic systems Specifications Adjustment Range 0 05 0 5 bar 1 67 16 73 ft H2 O 106030C SSASLEM Optional Installed StatLink 4 Zone Expansion Module 40234 The StatLink 4 zone exp...

Page 15: ...e knockouts Recessed Enclosure Mounting Step 1 Use a screwdriver or similar thin tool through the hole to bend the mounting tabs out 90 degrees from the enclosure 42 1 2 7 8 O D 7 8 O D 2 14 13 16 27...

Page 16: ...me This panel is heavy 2 3 person lift required Step 5 Complete the supporting frame by adding a top plate Be sure to drill corresponding holes in the top plate if any knockouts were removed Step 6 Se...

Page 17: ...aw a straight line on the wall and mark the stud locations If the housing cannot be secured directly to the studs or suitable backing boards plywood may need to be installed behind the housing to prop...

Page 18: ...Lubricate the inside of the manifold port with silicone o ring lubricant 79952 sold separately 2 Cut the PEX tubing at a 90 angle 3 Place the Nut and Split Ring Ferrule onto the PEX tubing Note For th...

Page 19: ...lves Fully open valve D Step 3 Attach a purge hose not included to D Pressurize the main supply line Open valve B Step 4 Open the first return manifold valve F Open the first supply manifold valve E W...

Page 20: ...g 2 Wire Thermostat battery only or non electric 3 Wire Thermostat HeatLink thermostats 4 Wire Thermostat with dry contact signal W R C 1 2 1 1 2 2 24 V Signal W R C 1 2 1 1 2 2 24 V 24 V Signal W R C...

Page 21: ...When the thermostat calls for heat its internal 24V contacts close the StatLink Base Module dry contacts 2 close and the pump 3 turns on If actuator s 4 are connected to the thermostat s zone the act...

Page 22: ...heat Use a stethoscope or similar device to verify The StatLink module or circulator may be defective A qualified electrician should verify 24V power is supplied to the thermostats and actuator The 2...

Page 23: ...es regulations and authorities have final jurisdiction Rough in wiring see Wiring detail see SSP Panel T Heat Source e g Boiler or Heat Exchanger SCH SSP M010 2013 10 08 Generic SSP Series Radiant Hea...

Page 24: ...etc for heat source as per local codes Use isolation ball valves for all circuits and components Local codes regulations and authorities have final jurisdiction Rough in wiring see Wiring detail see S...

Page 25: ...355 HeatLink Mixing Reset Control 2 1 Com 3 No Power Cls Opn 6 IN 7 Com 8 MIX 9 Com 10 OUT 11 Pwr C 12 Pwr R 13 Sys Pump 17 Boiler 18 Mix Sensor Supply Outdoor Sensor Boiler Contacts 4 Timer 5 15 Dem...

Page 26: ...h particular control chosen In all cases manufacturer equipment schematics will take precedence over HeatLink electrical schematics Local codes regulations and authorities have final jurisdiction Appl...

Page 27: ...Heat Link 27 www heatlink com SSPxx000x SS Manifold Pump Panels Installation Operation and Maintenance...

Page 28: ...al Phone 852 25693213 Fax 852 25359271 Ireland Distributed by Jamoni Ltd Phone 057 932 4062 Fax 057 932 4063 Freephone 1800 311338 M xico Distributed by Distribuidora Caisa S A de C V Phone 52 55 3300...

Reviews: