Heat Controller HBH Series Engineering Design Manual Download Page 8

Engineering Design Guide 

HBH SERIES 

Heat Controller, Inc.

8

Performance Data
HBH072

Performance capacities shown in thousands of Btuh

2,400 CFM Nominal Airfl ow Heating & Cooling

WATER/BRINE

Cooling - EAT 80/67°F

Heating - EAT 70°F

EWT

°F

Flow 
GPM

PD

PSI

PD 

FT

TC

SC

kW

HR

EER

HC

kW

HE

LAT

COP

20

20.0

6.8

15.8

Operation not recommended

49.5

5.0

32.5

87.1

2.9

30

10.0

1.2

2.7

82.3

56.8

3.6

94.5

23.0

54.7

5.0

37.5

89.0

3.2

15.0

3.3

7.7

81.1

55.8

3.4

92.8

23.6

56.8

5.1

39.6

89.9

3.3

20.0

6.2

14.3

80.2

55.1

3.4

91.7

23.8

58.0

5.1

40.7

90.3

3.4

40

10.0

1.0

2.2

82.4

57.4

3.9

95.6

21.2

63.2

5.1

45.6

92.3

3.6

15.0

3.0

7.0

82.6

57.1

3.7

95.1

22.4

66.1

5.2

48.4

93.4

3.7

20.0

5.6

13.0

82.4

56.8

3.6

94.6

22.9

67.7

5.2

50.0

94.1

3.8

50

10.0

0.9

2.0

80.7

57.2

4.2

95.1

19.0

72.3

5.3

54.4

95.8

4.0

15.0

2.8

6.5

81.9

57.4

4.0

95.6

20.5

76.0

5.3

57.8

97.2

4.2

20.0

5.3

12.2

82.3

57.4

3.9

95.6

21.1

78.0

5.4

59.7

98.0

4.3

60

10.0

0.5

1.2

77.7

56.3

4.7

93.6

16.7

81.8

5.4

63.3

99.5

4.4

15.0

2.2

5.1

79.7

56.9

4.4

94.7

18.2

86.0

5.5

67.2

101.1

4.6

20.0

4.4

10.1

80.6

57.2

4.3

95.1

18.9

88.3

5.5

69.4

102.0

4.7

70

10.0

0.5

1.1

73.9

54.9

5.2

91.4

14.3

91.1

5.6

72.0

103.1

4.8

15.0

2.1

4.8

76.3

55.8

4.8

92.8

15.8

95.6

5.7

76.3

104.8

4.9

20.0

4.2

9.6

77.5

56.2

4.7

93.5

16.5

98.0

5.7

78.5

105.7

5.0

80

10.0

0.4

0.9

69.4

53.1

5.7

88.9

12.2

99.8

5.8

80.2

106.4

5.1

15.0

1.9

4.5

72.2

54.2

5.4

90.5

13.4

104.4

5.9

84.4

108.2

5.2

20.0

3.9

9.1

73.5

54.7

5.2

91.2

14.1

106.7

5.9

86.5

109.1

5.3

85

10.0

0.4

0.8

67.1

52.1

6.0

87.7

11.2

103.7

5.8

83.8

107.9

5.2

15.0

1.9

4.4

69.8

53.3

5.7

89.2

12.4

108.0

5.9

87.8

109.6

5.3

20.0

3.9

8.9

71.2

53.8

5.5

89.9

13.0

110.1

6.0

89.7

110.4

5.4

90

10.0

0.3

0.8

64.8

51.2

6.4

86.4

10.2

107.6

5.9

87.4

109.4

5.3

15.0

1.8

4.3

67.5

52.3

6.0

87.9

11.3

111.7

6.0

91.1

111.0

5.4

20.0

3.8

8.8

68.9

52.9

5.8

88.6

11.9

113.5

6.0

92.8

111.7

5.5

100

10.0

0.3

0.7

60.1

49.2

7.1

84.2

8.5

Operation not recommended

15.0

1.8

4.1

62.7

50.3

6.6

85.4

9.4

20.0

3.7

8.5

64.1

50.9

6.4

86.1

10.0

110

10.0

0.2

0.6

55.8

47.5

7.9

82.7

7.1

15.0

1.7

3.9

58.1

48.4

7.4

83.4

7.8

20.0

3.6

8.3

59.4

48.9

7.2

83.9

8.3

120

10.0

0.2

0.5

52.2

46.3

8.8

82.2

5.9

15.0

1.6

3.7

54.1

46.9

8.3

82.3

6.5

20.0

3.5

8.0

55.1

47.3

8.0

82.5

6.9

Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.  
AHRI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.  
Table does not refl ect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.  
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.

Summary of Contents for HBH Series

Page 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ENGINEERING DESIGN GUIDE Commercial Horizontal Packaged Water Source Heat Pump HBH Series 6 10 Tons...

Page 2: ...Data HBH120 10 Performance Data Correction Tables 11 Antifreeze Correction Table 12 Blower Performance Data HBH072 Standard Unit 13 Blower Performance Data HBH096 Standard Unit 14 15 Blower Performanc...

Page 3: ...or desuperheater capacity Mbtuh FPT female pipe thread KW total power unit input kilowatts LAT leaving air temperature F LC latent cooling capacity BTUH LWT leaving water temperature F MBTUH 1000 BTU...

Page 4: ...d assess the selection If the units selected are not within 10 of the load calculations then review what effect changing the GPM water temperature and or air flow and air temperature would have on the...

Page 5: ...n horizontal units Cabinetry Compact design galvanized steel construction FPT water connections high and low voltage knockouts filter and filter brackets All horizontal units have field convertible di...

Page 6: ...for AHRI is 3 0 turns open Note 3 All HBH120 ratings 4000CFM 1888 l s w 30GPM 1 89 l s Sheave setting for AHRI is 3 0 turns open Note 4 Cooling capacities based upon 80 6 F DB 66 2 F WB entering air t...

Page 7: ...cutout due to the activation of the Low Temperature Protection JW3 should never be clipped for standard range equipment or systems without antifreeze Example At 50 F EWT Entering Water Temperature an...

Page 8: ...0 3 9 9 1 73 5 54 7 5 2 91 2 14 1 106 7 5 9 86 5 109 1 5 3 85 10 0 0 4 0 8 67 1 52 1 6 0 87 7 11 2 103 7 5 8 83 8 107 9 5 2 15 0 1 9 4 4 69 8 53 3 5 7 89 2 12 4 108 0 5 9 87 8 109 6 5 3 20 0 3 9 8 9 7...

Page 9: ...108 4 5 1 24 0 6 3 14 5 99 7 73 1 6 9 123 2 14 5 143 5 8 09 115 9 109 4 5 2 85 12 0 1 1 2 7 92 3 70 0 8 0 119 6 11 6 138 3 7 98 111 1 107 9 5 1 18 0 3 4 7 7 95 7 71 4 7 5 121 3 12 8 145 3 8 13 117 5 1...

Page 10: ...4 8 30 0 9 4 21 7 126 9 91 0 8 8 157 1 14 4 186 9 11 2 148 6 111 2 4 9 85 15 0 2 0 4 6 116 4 86 5 10 2 151 2 11 5 179 5 11 0 141 9 109 5 4 8 22 5 5 1 11 9 121 1 88 5 9 6 153 8 12 7 189 4 11 3 151 0 1...

Page 11: ...ier Entering DB F Power Heat of Rejection 60 65 70 75 80 80 6 85 90 95 50 0 7335 0 8825 0 9782 0 7834 55 0 8063 0 6757 0 8842 1 1119 0 9836 0 8424 60 0 8830 0 6734 0 8817 1 0918 0 9900 0 9301 65 0 977...

Page 12: ...989 0 997 1 070 15 0 986 0 986 1 009 0 968 0 990 1 210 25 0 978 0 978 1 014 0 947 0 983 1 360 Methanol 5 0 995 0 995 1 002 0 989 0 997 1 070 15 0 990 0 990 1 007 0 968 0 990 1 160 25 0 982 0 982 1 012...

Page 13: ...5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 780 815 850 885 920 950 985...

Page 14: ...920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20 1 26 1 32 1 38 1 44 Sheave Mtr B B...

Page 15: ...1 1 47 1 53 1 59 1 68 1 75 1 83 1 90 1 96 2 02 2 08 Sheave Mtr A A A A A A A A A A C C C C E E RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200 Turns Open 6 5 4 5 4 3 5 3 2...

Page 16: ...31 1 37 1 43 1 49 1 55 1 62 1 68 1 75 1 81 1 88 1 95 Sheave Mtr B B B B A A A A A A A A A A A C RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5...

Page 17: ...ve Mtr A A A A A A A A D E E E RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240 Turns Open 4 5 4 3 5 3 2 5 2 1 5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18...

Page 18: ...Motor Quantity 1 Standard Motor hp kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT...

Page 19: ...LEFT VIEW AIR COIL SIDE LEFT RETURN END DISCHARGE CBP EAP BSP CAP CAP FRONT E D F G CAP CBP CAP EAP BSP FRONT FRONT CONTROL BOX PLAN VIEW TOP V S U RIGHT RETURN RIGHT VIEW AIR COIL SIDE RIGHT RETURN E...

Page 20: ...8 18 3 N A N A 20 HBH160 H 208 3 60 197 254 A B C 2 23 2 164 0 8 5 54 9 60 7 5 600 80 H 208 3 60 197 254 D E 2 23 2 164 0 13 8 60 2 66 0 5 600 80 F 460 3 60 414 506 A B C 2 11 2 75 0 4 1 26 5 29 3 N...

Page 21: ...EQFGU QT 8 QRGTCVKQP FKUEQPPGEV 4 NGCF CV QT 8 QRGTCVKQP FKUEQPPGEV 8 1 NGCF CV CPF CVVCEJ 40 NGCF VQ PUWNCVG QRGP GPF QH 8 1 NGCF 5WHHKZ FGUKIPCVGU CUUQEKCVKQP YKVJ GCF EQORTGUUQT 5WHHKZ YKVJ CI EQOR...

Page 22: ...g m3 foil backed fiber insulation for ease of cleaning Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air...

Page 23: ...Pa working water pressure The refrigerant to water heat exchanger shall be electro coated with a low cure cathodic epoxy material a minimum of 0 4 mils thick 0 4 1 5 mils range on all surfaces The bla...

Page 24: ...t 5 minutes after trip if the fault has cleared If a fault occurs 3 times sequentially without thermostat meeting temperature then lockout requiring manual reset will occur j Ability to defeat time de...

Page 25: ...h memory stop and PT port c Y strainer with blowdown valve bronze material FPT connections d Motorized water valve slow acting 24v FPT connections Hose Kit Assemblies The following assemblies ship wit...

Page 26: ...OOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQF...

Reviews: