Heat Controller HBH Series Engineering Design Manual Download Page 22

Engineering Design Guide 

HBH SERIES 

Heat Controller, Inc.

22

HBH Series 60Hz
Engineering Specifi cations – Page 1

General:

Furnish and install the HBH Series as indicated on the plans. Equipment shall be completely assembled, piped and internally wired.
Capacities and characteristics as listed in the schedule and the specifi cations that follow.

Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120°F
(-6.7° to 48.9°C) as standard. Equivalent units from other manufacturers may be proposed provided approval to bid is given 10 days 
prior to bid closing. All equipment listed in this section must be rated and certifi ed in accordance with Air-Conditioning, Heating and 
Refrigeration Institute/International Standards Organization (AHRI/ISO 13256-1). All equipment must be tested, investigated, and de-
termined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/
CSA-C22.2 NO.236 for Canada, by Intertek Testing Laboratories (ETL). The units shall have AHRI/ISO and ETL-US-C labels.

All units shall be fully quality tested by factory run testing under normal operating conditions as described herein. Quality control system 
shall automatically perform via computer: triple leak check, pressure tests, evacuation and accurately charge system, perform detailed 
heating and cooling mode tests, and quality cross check all operational and test conditions to pass/fail criteria. Detailed report card 
will ship with each unit displaying status for critical tests and components. Note: If unit fails on any cross check, it shall not be allowed 
to ship. Serial numbers  will be recorded  by factory  and furnished to contractor on report card for ease of unit warranty  status. Units 
tested without water fl ow are not acceptable.

Basic Construction:

Horizontal units shall have one of the following air fl ow arrangements: Left Return/Back Discharge, Left Return/Straight Discharge, 
Right Return/Back Discharge, Right Return/Straight Discharge as shown on the plans. Units can be fi eld converted without requiring 
new panels or belts. Units that cannot be fi eld converted shall not be acceptable.

If units with these arrangements are not used, the contractor is responsible for any extra costs incurred by other trades. All units must 
have a minimum of two access panels for serviceability of compressor compartment. Units having only one access panel to compres-
sor/heat exchangers/expansion device/refrigerant piping  shall not be acceptable.

Compressor section interior surfaces shall be lined with 1/2 inch (12.7mm) thick, 1-1/2 lb/ft3 (24 kg/m3) acoustic type glass fi ber insula-
tion. Air handling section interior surfaces shall be lined with 1/2 in (12.7mm) thick, 1-3/4 lb/ft3 (28 kg/m3) foil backed fi ber insulation for 
ease of cleaning. Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction 
of glass fi bers into the air stream. Units without foil faced insulation in the air handling section  will not be accepted.

Horizontal heat pumps shall be fabricated from heavy gauge galvanized steel, with powder coat paint fi nish on front access panel. Color
to be pewter. Both sides of the panel shall be painted for added protection.

Standard insulation must meet NFPA Fire Hazard Classifi cation requirements 25/50 per ASTM E84, UL 723, CAN/ULC S102-M88 and 
NFPA 90A requirements; air erosion and mold growth limits of UL-181; stringent fungal resistance test per ASTM-C1071 and ASTM 
G21; and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not 
be accepted.

Horizontal units to have discharge air duct collar and 1” (25.4mm) fi lter rails with 1” (25.4mm) fi lters factory installed and factory in-
stalled mounting brackets. If units with these factory  installed provisions are not used, the contractor is responsible for any extra costs 
to fi eld install  these provisions, and/or the extra costs for his sub-contractor to install  these provisions.

All units must have an insulated panel separating the fan compartment from the compressor compartment. Units with the compressor in 
the air stream are not acceptable. Units shall have a factory installed 1 inch (25.4mm) wide fi lter rails with fi lter removal from either side. 
Units shall have a 1 inch (25.4mm) thick throwaway type glass fi ber fi lter. The contractor shall purchase one spare set of fi lters and 
replace factory shipped fi lters on completion of start-up. Filters shall be standard sizes. If units utilize non-standard fi lter sizes then the 
contractor shall provide 12 spare fi lters for each unit.

Cabinets shall have separate knockouts on front and sides for entrance of line voltage and low voltage control wiring. All factory- in-
stalled wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic 
ferrules. Supply and return water connections shall be copper FPT fi ttings, connections on both sides (installer to choose side and plug 
opposite) and shall be securely mounted fl ush to the cabinet side allowing for connection of a fl exible hose without the use of a back- 
up wrench. Water connections that protrude through the cabinet or require the use of a backup wrench shall not be allowed. Water 
connections on only one side will not be accepted. All water connections and electrical knockouts must not interfere with the serviceabil-
ity of unit. Contractor shall be responsible for any extra costs involved in the installation of units that do not have this feature. Contractor 
must ensure that units can be easily removed for servicing and coordinate locations of electrical conduit and lights with the electrical 
contractor.

Summary of Contents for HBH Series

Page 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ENGINEERING DESIGN GUIDE Commercial Horizontal Packaged Water Source Heat Pump HBH Series 6 10 Tons...

Page 2: ...Data HBH120 10 Performance Data Correction Tables 11 Antifreeze Correction Table 12 Blower Performance Data HBH072 Standard Unit 13 Blower Performance Data HBH096 Standard Unit 14 15 Blower Performanc...

Page 3: ...or desuperheater capacity Mbtuh FPT female pipe thread KW total power unit input kilowatts LAT leaving air temperature F LC latent cooling capacity BTUH LWT leaving water temperature F MBTUH 1000 BTU...

Page 4: ...d assess the selection If the units selected are not within 10 of the load calculations then review what effect changing the GPM water temperature and or air flow and air temperature would have on the...

Page 5: ...n horizontal units Cabinetry Compact design galvanized steel construction FPT water connections high and low voltage knockouts filter and filter brackets All horizontal units have field convertible di...

Page 6: ...for AHRI is 3 0 turns open Note 3 All HBH120 ratings 4000CFM 1888 l s w 30GPM 1 89 l s Sheave setting for AHRI is 3 0 turns open Note 4 Cooling capacities based upon 80 6 F DB 66 2 F WB entering air t...

Page 7: ...cutout due to the activation of the Low Temperature Protection JW3 should never be clipped for standard range equipment or systems without antifreeze Example At 50 F EWT Entering Water Temperature an...

Page 8: ...0 3 9 9 1 73 5 54 7 5 2 91 2 14 1 106 7 5 9 86 5 109 1 5 3 85 10 0 0 4 0 8 67 1 52 1 6 0 87 7 11 2 103 7 5 8 83 8 107 9 5 2 15 0 1 9 4 4 69 8 53 3 5 7 89 2 12 4 108 0 5 9 87 8 109 6 5 3 20 0 3 9 8 9 7...

Page 9: ...108 4 5 1 24 0 6 3 14 5 99 7 73 1 6 9 123 2 14 5 143 5 8 09 115 9 109 4 5 2 85 12 0 1 1 2 7 92 3 70 0 8 0 119 6 11 6 138 3 7 98 111 1 107 9 5 1 18 0 3 4 7 7 95 7 71 4 7 5 121 3 12 8 145 3 8 13 117 5 1...

Page 10: ...4 8 30 0 9 4 21 7 126 9 91 0 8 8 157 1 14 4 186 9 11 2 148 6 111 2 4 9 85 15 0 2 0 4 6 116 4 86 5 10 2 151 2 11 5 179 5 11 0 141 9 109 5 4 8 22 5 5 1 11 9 121 1 88 5 9 6 153 8 12 7 189 4 11 3 151 0 1...

Page 11: ...ier Entering DB F Power Heat of Rejection 60 65 70 75 80 80 6 85 90 95 50 0 7335 0 8825 0 9782 0 7834 55 0 8063 0 6757 0 8842 1 1119 0 9836 0 8424 60 0 8830 0 6734 0 8817 1 0918 0 9900 0 9301 65 0 977...

Page 12: ...989 0 997 1 070 15 0 986 0 986 1 009 0 968 0 990 1 210 25 0 978 0 978 1 014 0 947 0 983 1 360 Methanol 5 0 995 0 995 1 002 0 989 0 997 1 070 15 0 990 0 990 1 007 0 968 0 990 1 160 25 0 982 0 982 1 012...

Page 13: ...5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 780 815 850 885 920 950 985...

Page 14: ...920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20 1 26 1 32 1 38 1 44 Sheave Mtr B B...

Page 15: ...1 1 47 1 53 1 59 1 68 1 75 1 83 1 90 1 96 2 02 2 08 Sheave Mtr A A A A A A A A A A C C C C E E RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200 Turns Open 6 5 4 5 4 3 5 3 2...

Page 16: ...31 1 37 1 43 1 49 1 55 1 62 1 68 1 75 1 81 1 88 1 95 Sheave Mtr B B B B A A A A A A A A A A A C RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5...

Page 17: ...ve Mtr A A A A A A A A D E E E RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240 Turns Open 4 5 4 3 5 3 2 5 2 1 5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18...

Page 18: ...Motor Quantity 1 Standard Motor hp kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT...

Page 19: ...LEFT VIEW AIR COIL SIDE LEFT RETURN END DISCHARGE CBP EAP BSP CAP CAP FRONT E D F G CAP CBP CAP EAP BSP FRONT FRONT CONTROL BOX PLAN VIEW TOP V S U RIGHT RETURN RIGHT VIEW AIR COIL SIDE RIGHT RETURN E...

Page 20: ...8 18 3 N A N A 20 HBH160 H 208 3 60 197 254 A B C 2 23 2 164 0 8 5 54 9 60 7 5 600 80 H 208 3 60 197 254 D E 2 23 2 164 0 13 8 60 2 66 0 5 600 80 F 460 3 60 414 506 A B C 2 11 2 75 0 4 1 26 5 29 3 N...

Page 21: ...EQFGU QT 8 QRGTCVKQP FKUEQPPGEV 4 NGCF CV QT 8 QRGTCVKQP FKUEQPPGEV 8 1 NGCF CV CPF CVVCEJ 40 NGCF VQ PUWNCVG QRGP GPF QH 8 1 NGCF 5WHHKZ FGUKIPCVGU CUUQEKCVKQP YKVJ GCF EQORTGUUQT 5WHHKZ YKVJ CI EQOR...

Page 22: ...g m3 foil backed fiber insulation for ease of cleaning Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air...

Page 23: ...Pa working water pressure The refrigerant to water heat exchanger shall be electro coated with a low cure cathodic epoxy material a minimum of 0 4 mils thick 0 4 1 5 mils range on all surfaces The bla...

Page 24: ...t 5 minutes after trip if the fault has cleared If a fault occurs 3 times sequentially without thermostat meeting temperature then lockout requiring manual reset will occur j Ability to defeat time de...

Page 25: ...h memory stop and PT port c Y strainer with blowdown valve bronze material FPT connections d Motorized water valve slow acting 24v FPT connections Hose Kit Assemblies The following assemblies ship wit...

Page 26: ...OOHU LV UHVSRQVLEOH IRU YHULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQF...

Reviews: