8.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited per the table below.
Cooling mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
COOL_F10
ICOOLLMT6
The compressor frequency will decrease to COOL_F4 and
then run at COOL_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand, then rise to the next level up every 3
minutes (When the frequency>COOL_F4 via capacity
demand).
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later and re-check.
Heating mode:
Current frequency(Hz)
Current limit value(A)
Frequency limit
HEAT_F12
IHEATLMT8
The compressor frequency will decrease HEAT_F4 and
then run at HEAT_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand, then rise to the next level up every 3
minutes (When the frequency>Heat_F4 via capacity
demand).
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later and re-check.